SenseAir eSENSE Duct-TR Installation Manual Download Page 3

 

 

 

 

 

Document 

IMA0215

  

Rev 

7

 

Page 
3 (8)

 

 

Mounting of 

eSENSE

 on to the duct

10

 

 

10 

Hole with 25 mm diameter 

 

Figure 3 Mounting of the sensor to the ventilation duct 
 

Mounting Instruction 

 

Since there might be a substantial pressure difference in duct mounting applications, 
it is essential to avoid ambient air from suction into the duct mounting box. For 
correct function it is indispensable that the sealing of the box cover, the cable entry 
bushings, the cable feed through and the duct entrance are absolutely tight. The duct 
entrance may need extra sealing paste in order to prevent leakage. The PCB must 
be handed carefully and protected from electrostatic discharge. 
 
1)   

Place the

 

O-ring

 around the hole at the back of the box. See figure 2. 

 
2)   

Electrical cable entry:

 The box has a factory mounted cable entry bushing. 

Never feed more than one cable through each cable entry bushing, or else gas 
might leak through! 

 
3)   

Mounting the tube:

 Drill a hole (10) with 25 mm diameter (or 1 inch) for the 

sampling probe and two holes with 4 mm diameter for the screws (5) into the air 
duct and mount the tube (1) with the gasket (2). The sampling probe should be 
mounted with the largest locking knob on top. The unit can be mounted with the 
air coming from the left or right. 
 

4)   

Attaching the sensor box

 is made to the sampling probe by a snap-in bayonet 

fitting. Orient the box onto the sampling probe so that the box upside is on the 
same side as the largest locking knob (3). When the probe is fitted into the 
notches of the box, then turn the box clockwise until stop (see Figure 2). Position 
1 indicates

 open

 where the box can be removed from the sampling probe. In 

position 2 the box is locked to the probe

 

Summary of Contents for eSENSE Duct-TR

Page 1: ...the measured CO2 value in ppm parts per million on the LCD The units are designed for connecting to Direct Digital Control DDC with 0 10V or 2 10V signal inputs The two parallel signal outputs Out 1...

Page 2: ...9 8 1 Sampling probe 6 O ring 29 2x3 53 2 Sealing gasket 7 PCB Factory supplied mounted in box 3 Largest locking nob 8 Snap in lid 4 2 washers Not included 9 Cable entry bushing 5 2 screws Not includ...

Page 3: ...ctrical cable entry The box has a factory mounted cable entry bushing Never feed more than one cable through each cable entry bushing or else gas might leak through 3 Mounting the tube Drill a hole 10...

Page 4: ...eSENSE unit and for the control system Terminal Function Electrical data Remarks Standard settings Remarks Settings of this sensor Power Power ground 24 VAC DC 20 2W 24 VAC DC System voltage referenc...

Page 5: ...with the jumper set to voltage output right position Self diagnostics The system contains a complete self diagnostic procedure that is executed automatically when the sensor is in operation Sensors w...

Page 6: ...uilt in self correcting ABC algorithm Discuss your application with SenseAir in order to get advice for a proper calibration strategy PLEASE NOTE The sensor accuracy is defined at continuous operation...

Page 7: ...Document IMA0215 Rev 7 Page 7 8 Dimensions Figure 7 The dimensions of the sensor in mm and inches...

Page 8: ...marking Directive 93 68 EEC The product fulfils the following demands EN 61000 4 2 level 2 EN 61000 4 3 level 2 EN 61000 4 4 level 4 EN 61000 4 6 EN 61000 4 8 level 4 EN 55022 class B SenseAir AB head...

Reviews: