Figure 1 The eSENSE Duct with and without display

 

 

General

 

 
The IAQ-sensor product 

eSENSE Duct

 (for mounting in ventilation ducts) is designed 

to measure carbon dioxide (CO

2

). Option - TR is prepared for temperature 

measurements by the resistive temperature probe mounted by the user. Option -Disp 
displays the measured CO

2

 value in ppm (parts-per-million) on the LCD. 

 
The units are designed for connecting to Direct Digital Control (DDC) with 0-10V or  
2-10V signal inputs. The two parallel signal outputs Out(1) (0-10V) and Out(2) (2-10V 
or 4-20 mA) give linear signal voltages or currents corresponding to the measuring 
range.  
 
The output Out(2)

 

also indicates the 

status

 by setting the output voltage to 1V or the 

output current to 2 mA when the sensor self-diagnostics detects any error. 
 
 

 

 

Gas and Air Sensors 

eSENSE Duct (Disp) 

Installation Manual 

 

 

 

 

Summary of Contents for eSENSE Duct-TR

Page 1: ...the measured CO2 value in ppm parts per million on the LCD The units are designed for connecting to Direct Digital Control DDC with 0 10V or 2 10V signal inputs The two parallel signal outputs Out 1...

Page 2: ...9 8 1 Sampling probe 6 O ring 29 2x3 53 2 Sealing gasket 7 PCB Factory supplied mounted in box 3 Largest locking nob 8 Snap in lid 4 2 washers Not included 9 Cable entry bushing 5 2 screws Not includ...

Page 3: ...ctrical cable entry The box has a factory mounted cable entry bushing Never feed more than one cable through each cable entry bushing or else gas might leak through 3 Mounting the tube Drill a hole 10...

Page 4: ...eSENSE unit and for the control system Terminal Function Electrical data Remarks Standard settings Remarks Settings of this sensor Power Power ground 24 VAC DC 20 2W 24 VAC DC System voltage referenc...

Page 5: ...with the jumper set to voltage output right position Self diagnostics The system contains a complete self diagnostic procedure that is executed automatically when the sensor is in operation Sensors w...

Page 6: ...uilt in self correcting ABC algorithm Discuss your application with SenseAir in order to get advice for a proper calibration strategy PLEASE NOTE The sensor accuracy is defined at continuous operation...

Page 7: ...Document IMA0215 Rev 7 Page 7 8 Dimensions Figure 7 The dimensions of the sensor in mm and inches...

Page 8: ...marking Directive 93 68 EEC The product fulfils the following demands EN 61000 4 2 level 2 EN 61000 4 3 level 2 EN 61000 4 4 level 4 EN 61000 4 6 EN 61000 4 8 level 4 EN 55022 class B SenseAir AB head...

Reviews: