| IWR-PORT SERIES
UTILITY OPERATING MANUAL
C
opyright © 2021 Sensata Technologies, Inc.
Page 36
Sensata Technologies, Inc. (“Sensata”) data sheets are solely intended to assist designers (“Buyers”) who are developing systems that
incorporate Sensata products (also referred to herein as “components”). Buyer understands and agrees that Buyer remains responsible for
using its independent analysis, evaluation and judgment in designing Buyer’s systems and products. Sensata data sheets have been created
using standard laboratory conditions and engineering practices. Sensata has not conducted any testing other than that specifically described
in the published documentation for a particular data sheet. Sensata may make corrections, enhancements, improvements and other changes
to its data sheets or components without notice.
Buyers are authorized to use Sensata data sheets with the Sensata component(s) identified in each particular data sheet. HOWEVER, NO
OTHER LICENSE, EXPRESS OR IMPLIED, BY ESTOPPEL OR OTHERWISE TO ANY OTHER SENSATA INTELLECTUAL PROPERTY RIGHT, AND
NO LICENSE TO ANY THIRD PARTY TECHNOLOGY OR INTELLECTUAL PROPERTY RIGHT, IS GRANTED HEREIN. SENSATA DATA SHEETS
ARE PROVIDED “AS IS”. SENSATA MAKES NO WARRANTIES OR REPRESENTATIONS WITH REGARD TO THE DATA SHEETS OR USE OF THE
DATA SHEETS, EXPRESS, IMPLIED OR STATUTORY, INCLUDING ACCURACY OR COMPLETENESS. SENSATA DISCLAIMS ANY WARRANTY
OF TITLE AND ANY IMPLIED WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, QUIET ENJOYMENT, QUIET
POSSESSION, AND NON-INFRINGEMENT OF ANY THIRD PARTY INTELLECTUAL PROPERTY RIGHTS WITH REGARD
TO SENSATA DATA SHEETS OR USE THEREOF.
All products are sold subject to Sensata’s terms and conditions of sale supplied at
www.sensata.com
SENSATA ASSUMES NO LIABILITY
FOR APPLICATIONS ASSISTANCE OR THE DESIGN OF BUYERS’ PRODUCTS. BUYER ACKNOWLEDGES AND AGREES THAT IT IS SOLELY
RESPONSIBLE FOR COMPLIANCE WITH ALL LEGAL, REGULATORY AND SAFETY-RELATED REQUIREMENTS CONCERNING ITS PRODUCTS,
AND ANY USE OF SENSATA COMPONENTS IN ITS APPLICATIONS, NOTWITHSTANDING ANY APPLICATIONS-RELATED INFORMATION OR
SUPPORT THAT MAY BE PROVIDED BY SENSATA.
Mailing Address: Sensata Technologies, Inc., 529 Pleasant Street, Attleboro, MA 02703, USA.
CONTACT US
EUROPE
+44 (0)1202 897969
Cynergy3 Components Ltd.
7 Cobham Road,
Ferndown Industrial Estate,
Wimborne, Dorset,
BH21 7PE, United Kingdom
USA
+1 310 561 8092 / +1 866 258 5057
13. SPECIFICATIONS (@ 25°C)
Operating Temperature
0 to 55 °C
Operating Altitude
Sea Level to 2000m
Humidity
0-90% RH (Relative Humidity)
Power Requirements
DC Supply
16 to 30 V dc
AC Supply
16 to 32 V ac
Current Consumption
120 mA @ 24 V dc (20mA in & out)
Transmitter Power Supply
22 V to 29 V @ up to 24 mA
Dependant on supply voltage and load
Maximum Voltage Output
11.5 V into a minimum of 7Kohm
Maximum Current Output
23.0 mA into a maximum of 1Kohm
The unit has full 2 port Isolation to 1kV between Power Supply and Output.
The unit can also withstand transients of 2.5 kV for 50 µsecs.
Dimensions
114.5 mm x 99 mm x 22.5 mm (H x D x W)
Mounting
DIN Rail TS35
Connections
Screw Clamp with pressure plate
Conductor Size
0.5 to 4.0 mm
Insulation Stripping
12 mm
Maximum Terminal Torque
0.4 Nm
Weight
Approx. 140 g
EMC Emissions
BS EN61326
LVD Standards
EN61010-1
Installation Category (IEC 664)
II
Pollution Degree (EN61010-1)
2
Equipment Class (IEC 536)