Display
Action
3.DSV C1 P1
C1 P1 is channel 1 parameter 1
Press and release both buttons together
01 1
Press the lower button to choose a channel (on left: 1 to 128)
03 1
Press the raise button to choose a parameter (on right: 1 to 8)
03 2
Press and release both buttons together
3.DSV C3 P2
C3 P2 is channel 3, parameter 2
Push the raise button once to change the menu item
4.DS 100
Display Span value is 100
Press and release both buttons together
100
Press raise/lower buttons to adjust display span value
20
Press and release both buttons together
4.DS 20
Display Span value is now 20
Push the raise button once to change the menu item
5.DZ 0
Display Zero value is 0
Press and release both buttons together
0
Press raise/lower buttons to adjust display zero value
4
Press and release both buttons together
5.DZ 4
Display Zero value is now 4
3.DSV Cc Pp is used to select the channel and parameter that need display values
changing, where c represents the channel and p indicates the parameter.
To select a different channel or parameter enter the submenu. The display will show the
channel on the left and the parameter on the right. The lower button increases the
channel (1 to 128) and the raise button increases the parameter (1 to 8).
The channel and parameter are chosen in menu 3:
4.DS span indicates what the display span value is (span is –999 to 9999)
To change the display span value, enter the sub-menu and adjust it.
5.DZ zero indicates what the display zero value is (zero is –999 to 9999)
To change the display zero value, enter the sub-menu and adjust it.
View Display Scaling Values (6. VIEW DSV)
To view all eight parameter scaling values of a particular channel, enter this sub-menu.
The first channel shown will be the one selected in 3.DSV Cc Pp. The scaling values will
be shown in a scrolling message in this format: e.g. channel 3:
C3.P1 100,0 P2 20,4 P3 100,0 P4 100,0 P5 100,0 P6 100,0 P7 100,0 P8 100,0
The channel being viewed can be changed using the lower or raise buttons, each press
will cause the scrolling message to begin again, for a different channel.
Linking Outputs to other Parameters (7. OUT Cc Pp, 8. LINK Cc Pp)
The IWR-Port 4-20 mA or 0-10 V output can represent the value of any parameter within
the system. The outputs of Isoslice units can also represent any parameter within the
system. This is done using a link table, which links the outputs to the parameters (usually
of input devices) they must represent.