Page   8

Copyright © 2020 Sensata Technologies, Inc. 

10000

1000

100

10

1

.1

.01

.001

0        100  150 200       300       400        500       600        700        800       900      1000

    

PERCENT OF RATED CURRENT

135

TIME IN SECOND

S

INSTANT

MA

Y  TRI

P

10000

1000

100

10

1

.1

.01

.001

0        100  150 200       300       400        500       600        700       800        900      100

0

    

PERCENT OF RATED CURRENT

135

TIME IN SECOND

S

   FAST   

MA

Y  TRI

P

10000

1000

100

10

1

.1

.01

.001

0        100  150 200       300       400        500       600        700       800        900      1000

    

PERCENT OF RATED CURRENT

135

TIME IN SECONDS

    SLOW

MA

Y  TRI

P

 Ambient Operation

Operates normally in temperatures between –40° C and +85°C. 

Insulation Resistance

Not less than 100 megohms at 500Vdc. 

Dielectric Strength

Withstands 1500 volts, 60Hz for 60 seconds or 1800Vac for one second between all electrically isolated terminals. 

Endurance

Mechanical life in excess of 50,000 operations. In manyapplications, however, contact wear due to the electrical load determines unit life. At 

maximum electrical ratings, the SNAPAK® can perform 10,000 operations at rated current and voltage. Under UL 1077, the SNAPAK® can perform 

50 operations at 150% of maximum rated current followed by 6,000 operations at maximum rated current. Under EN60934 the SNAPAK® can 

perform 6,000 electrical operations. After any endurance cycle, the breaker will calibrate and have working 

Summary of Contents for AIRPAX SNAPAK

Page 1: ...ck connect terminals are standard UNC 8 32 or M4 screw terminals are available as additional termination options Since the SNAPAK is snap acting it assures immediate opening and closing of the contacts Its design also prevents operator teasing of the contacts and minimizes arcing SNAPAK circuit protectors are UL Recognized as supplementary protectors per UL STD 1077 CSA Certified as supplementary ...

Page 2: ...030 12 70 0 76 1 2 32 THD 680 0 010 17 27 0 25 031 0 79 250 6 35 1 375 0 010 34 93 0 25 1 LINE 2 Single Pole Toggle 2 4 1 LINE LINE 3 POLE 1 POLE 2 15º 15º ON OFF FLAT 1 715 0 030 43 56 0 76 375 0 010 9 53 0 25 1 125 0 030 28 58 0 76 125 0 010 3 17 0 25 468 0 010 11 89 0 25 0 500 0 030 12 70 0 76 1 2 32 THD 625 0 010 15 88 0 25 031 0 79 250 6 35 1 375 0 010 34 93 0 25 1 304 0 010 33 12 0 25 Two Po...

Page 3: ...5 0 305 0 010 7 75 0 25 Handle Guards Single Pole Handle Guards Two Pole 1 047 0 010 26 60 0 25 0 305 0 010 7 75 0 25 0 093 0 010 2 36 0 25 0 625 0 010 15 88 0 25 0 125 0 010 3 18 0 25 0 030 0 325 8 26 0 76 1 304 0 010 33 12 0 25 0 031 0 79 0 250 6 35 1 840 0 030 46 74 0 76 0 375 0 010 9 53 0 25 1 125 0 030 28 58 0 76 1 375 0 010 34 93 0 25 0 972 0 010 24 69 0 25 1 560 0 010 39 62 0 25 0 400 0 010...

Page 4: ...010 33 12 0 25 9 53 025 000 375 010 000 162 0 002 4 11 0 05 0 76 0 030 OFF 6 35 0 25 FLUSH 0 030 ON FLUSH 0 25 Mounting Detail Single Pole and Two Pole Push to Reset Actuation Single and Two Pole Push Pull Single Pole 1 960 0 030 49 78 0 76 375 0 010 9 53 0 25 400 0 010 10 16 0 25 0 500 0 030 12 70 0 76 OFF SHOWN 0 250 0 030 6 35 0 76 ON WHITE BAND VISIBLE IN OFF POSITION ONLY 3 8 32 THD FLAT Push...

Page 5: ... protection for the critical load When the current through this load becomes excessive and reaches the trip point the protector will open and remove power from both loads simultaneously The current rating of both loads must not exceed the maximum contact rating Relay Trip This permits the overload sensing coil to be placed in a circuit which is electrically isolated from the contacts The coil may ...

Page 6: ...rations Power Switch In the event that over current protection is not desired the coil mechanism can be deleted providing an excellent low cost single or double pole power switch Maximum current rating is 20 amps 2 4 1 LINE LINE 3 C N C N O 0 093 2 36 0 040 1 02 DIA HOLE FOR SOLDER ATTACHMENT 560 0 030 1 4 22 0 76 LOAD LINE BREAKER SHOW N IN OFF POSITION C NC NO LOAD LIN E BREAKER SHO WN IN OFF PO...

Page 7: ...RENT VS TRIP TIME IN SECONDS AT 25 C VERTICAL MOUNT Delay 100 135 150 200 400 600 800 Instant No Trip May Trip 100 Max 100 Max 100 Max 100 Max 100 Max Fast No Trip 3 to 7 2 to 5 1 to 2 03 to 50 015 to 30 010 to 150 Slow No Trip 3 to 70 2 to 40 1 to 15 10 to 4 0 015 to 2 0 010 to 800 PULSE TOLERANCE Delay Pulse Tolerance 1 2 61 62 9 Times Rated Current 3 4 61F 62F 13 Times Rated Current 400 Hz DC 5...

Page 8: ...between 40 C and 85 C Insulation Resistance Not less than 100 megohms at 500Vdc Dielectric Strength Withstands 1500 volts 60Hz for 60 seconds or 1800Vac for one second between all electrically isolated terminals Endurance Mechanical life in excess of 50 000 operations In manyapplications however contact wear due to the electrical load determines unit life At maximum electrical ratings the SNAPAK c...

Page 9: ...dress nuts are also available in a matte black finish Every SNAPAK comes with a hex nut but you may order the front panel nuts which will best enhance your design Miscellaneous Hardware SNAPAK circuit protectors with 1 2 32 thread may also be equipped with optional locking rings to prevent rotation of the unit after it is installed 3 8 32 Hex Nut and Panel Nuts The hardware will be supplied with e...

Page 10: ...ector S Screw Terminals Single pole 1 and series only 5th decision group V screw terminal option is required when 1st decision S is specified PR Push To Reset 2 Two Pole 3 Shunt Circuit Protector R Rocker 5 Two Pole 4 Relay Circuit Protector CR Rocker 5 Series w Silver Aux Switch CPP Push Pull 6 Series w Gold Aux Switch CPR Push to Reset 9 Mixed Construction 2 Pole Only UL CSA Construction Non UL ...

Page 11: ... number are now complete except if you require S screwterminal option from the 5th Decision Table Paddle T Handle Color 01 Black 02 Red 03 Yellow 04 Green 05 Blue 06 White If you have chosen a handle from this table your 4th Decision is now complete except for hardware options in 5th Decision Table Push Pull PP CPP and CPR XX XX No button markings desired not available for CPP CPR OA LINE 5 Marked...

Page 12: ...000 U1 1000 P R only 65 DC 1 10 10 7 5 U 2 500 U1 500 65 DC 2 10 10 15 U1 1000 65 DC 2 10 10 20 10 20 U2 500 U1 5005 00 65 2 D C 11 0 10 30 10 30 U2 120 120R PP PR only 65 2 D C 2 only 10 10 25 U1 100 R only 65 2 D C 21 0 10 25 U2 500 R only 125 50 60 11 10 10 20 7 6 20 U1 10005 00 125 50 60 11 10 10 30 3 U1 1000 T only 125 2 50 60 11 10 10 30 U2 1000 R PP PR only 125 2 50 60 11 11 10 30 20 1 30 U...

Page 13: ...IS SOLELY RESPONSIBLE FOR COMPLIANCE WITH ALL LEGAL REGULATORY AND SAFETY RELATED REQUIREMENTS CONCERNING ITS PRODUCTS AND ANY USE OF SENSATA COMPONENTS IN ITS APPLICATIONS NOTWITHSTANDING ANY APPLICATIONS RELATED INFORMATION OR SUPPORT THAT MAY BE PROVIDED BY SENSATA Mailing Address Sensata Technologies Inc 529 Pleasant Street Attleboro MA 02703 USA Revised 01 17 20 Notes A A neon bulb is provide...

Reviews: