background image

www.sensata.com

Page   7

Copyright © 2020 Sensata Technologies, Inc. 

OPERATING CHARACTERISTICS

Inrush Pulse Tolerance

Many circuit protector applications involve a transformer turn-on, an incandescent lamp load, or a capacitor charge from a DC source. Each of these 

applications has one common factor: a steep transient of very high current amplitude and short duration. This takes the form of a spike or a single pulse 

and is the cause of most nuisance tripping associated with magnetic circuit breakers.

SNAPAK® will withstand, without tripping, a single pulse of 8 milli-seconds duration (half sine wave configuration) and peak amplitude of 9 times its

rating without the inertia wheel and 13 times its rating with an inertia wheel. (Not applicable to instant trip delays).

MAXIMUM DCR AND IMPEDANCE

Current Ratings (Amps)

T/R/PP/PR DC Resistance

T/R/PP/PR 50/60Hz Impedance

CR/CPP/CPR DC Resistance

.100

175

181

274

.500

6.34

6.63

9.77

1.00

1.63

1.69

2.31

2.00

.400

.425

.465

3.00

.175

.188

.261

4.00

.103

.106

.156

5.00

.076

.078

.091

7.50

.038

.039

.053

10.0

.026

0.28

.023

12.5

.020

0.21

.020

15.0

.013

.014

.010

20.0

.010

.011

.008

25.0

.004

30.0

.003

PERCENTAGE OF RATED CURRENT VS TRIP TIME IN SECONDS AT +25°C (VERTICAL MOUNT)

Delay

100%

135%

150%

200%

400%

600%

800%

Instant

No Trip

May Trip

.100 Max

.100 Max

.100 Max

.100 Max

.100 Max

Fast

No Trip

.3 to 7

.2 to 5

.1 to 2

.03 to .50

.015 to .30

.010 to .150

Slow

No Trip

3 to 70

2 to 40

1 to 15

.10 to 4.0

.015 to 2.0

.010 to .800

PULSE TOLERANCE

Delay

Pulse Tolerance

1, 2, 61, 62

*9 Times Rated Current

3, 4, 61F, 62F

*13 Times Rated Current

400 Hz, DC, 50/60Hz Delay Curves (typ)

A choice of delays is offered for DC, 50/60Hz and 400Hz applications. Delays 0, 49, 59 and 69 provide fast-acting, instantaneous trip and are often 

used to protect sensitive electronic equipment (not recommended where known inrush exists). Delays 1, 41, 51 and 61 have a short delay for general 

purpose applications. Delays 2, 42, 52 and 62 are long enough to start certain types of motors and most transformer and capacitor loads.

Trip Free

Will trip open on overload, even when forcibly held on.This prevents operator from damaging the circuit by holding handle in the ON position.

Trip Indication

The operating handle moves forcibly and positively to the OFF position on overload.

DELAY CURVES & SPECIFICATIONS

DCR and Impedance is measured after 1 hour at 100% rated current using the Voltmeter-Ammeter Method

* Units above 15 amps are derated to 8 and 12 times rated current

* Minimum trip for all instantaneous and 400Hz units.

Summary of Contents for AIRPAX SNAPAK

Page 1: ...ck connect terminals are standard UNC 8 32 or M4 screw terminals are available as additional termination options Since the SNAPAK is snap acting it assures immediate opening and closing of the contacts Its design also prevents operator teasing of the contacts and minimizes arcing SNAPAK circuit protectors are UL Recognized as supplementary protectors per UL STD 1077 CSA Certified as supplementary ...

Page 2: ...030 12 70 0 76 1 2 32 THD 680 0 010 17 27 0 25 031 0 79 250 6 35 1 375 0 010 34 93 0 25 1 LINE 2 Single Pole Toggle 2 4 1 LINE LINE 3 POLE 1 POLE 2 15º 15º ON OFF FLAT 1 715 0 030 43 56 0 76 375 0 010 9 53 0 25 1 125 0 030 28 58 0 76 125 0 010 3 17 0 25 468 0 010 11 89 0 25 0 500 0 030 12 70 0 76 1 2 32 THD 625 0 010 15 88 0 25 031 0 79 250 6 35 1 375 0 010 34 93 0 25 1 304 0 010 33 12 0 25 Two Po...

Page 3: ...5 0 305 0 010 7 75 0 25 Handle Guards Single Pole Handle Guards Two Pole 1 047 0 010 26 60 0 25 0 305 0 010 7 75 0 25 0 093 0 010 2 36 0 25 0 625 0 010 15 88 0 25 0 125 0 010 3 18 0 25 0 030 0 325 8 26 0 76 1 304 0 010 33 12 0 25 0 031 0 79 0 250 6 35 1 840 0 030 46 74 0 76 0 375 0 010 9 53 0 25 1 125 0 030 28 58 0 76 1 375 0 010 34 93 0 25 0 972 0 010 24 69 0 25 1 560 0 010 39 62 0 25 0 400 0 010...

Page 4: ...010 33 12 0 25 9 53 025 000 375 010 000 162 0 002 4 11 0 05 0 76 0 030 OFF 6 35 0 25 FLUSH 0 030 ON FLUSH 0 25 Mounting Detail Single Pole and Two Pole Push to Reset Actuation Single and Two Pole Push Pull Single Pole 1 960 0 030 49 78 0 76 375 0 010 9 53 0 25 400 0 010 10 16 0 25 0 500 0 030 12 70 0 76 OFF SHOWN 0 250 0 030 6 35 0 76 ON WHITE BAND VISIBLE IN OFF POSITION ONLY 3 8 32 THD FLAT Push...

Page 5: ... protection for the critical load When the current through this load becomes excessive and reaches the trip point the protector will open and remove power from both loads simultaneously The current rating of both loads must not exceed the maximum contact rating Relay Trip This permits the overload sensing coil to be placed in a circuit which is electrically isolated from the contacts The coil may ...

Page 6: ...rations Power Switch In the event that over current protection is not desired the coil mechanism can be deleted providing an excellent low cost single or double pole power switch Maximum current rating is 20 amps 2 4 1 LINE LINE 3 C N C N O 0 093 2 36 0 040 1 02 DIA HOLE FOR SOLDER ATTACHMENT 560 0 030 1 4 22 0 76 LOAD LINE BREAKER SHOW N IN OFF POSITION C NC NO LOAD LIN E BREAKER SHO WN IN OFF PO...

Page 7: ...RENT VS TRIP TIME IN SECONDS AT 25 C VERTICAL MOUNT Delay 100 135 150 200 400 600 800 Instant No Trip May Trip 100 Max 100 Max 100 Max 100 Max 100 Max Fast No Trip 3 to 7 2 to 5 1 to 2 03 to 50 015 to 30 010 to 150 Slow No Trip 3 to 70 2 to 40 1 to 15 10 to 4 0 015 to 2 0 010 to 800 PULSE TOLERANCE Delay Pulse Tolerance 1 2 61 62 9 Times Rated Current 3 4 61F 62F 13 Times Rated Current 400 Hz DC 5...

Page 8: ...between 40 C and 85 C Insulation Resistance Not less than 100 megohms at 500Vdc Dielectric Strength Withstands 1500 volts 60Hz for 60 seconds or 1800Vac for one second between all electrically isolated terminals Endurance Mechanical life in excess of 50 000 operations In manyapplications however contact wear due to the electrical load determines unit life At maximum electrical ratings the SNAPAK c...

Page 9: ...dress nuts are also available in a matte black finish Every SNAPAK comes with a hex nut but you may order the front panel nuts which will best enhance your design Miscellaneous Hardware SNAPAK circuit protectors with 1 2 32 thread may also be equipped with optional locking rings to prevent rotation of the unit after it is installed 3 8 32 Hex Nut and Panel Nuts The hardware will be supplied with e...

Page 10: ...ector S Screw Terminals Single pole 1 and series only 5th decision group V screw terminal option is required when 1st decision S is specified PR Push To Reset 2 Two Pole 3 Shunt Circuit Protector R Rocker 5 Two Pole 4 Relay Circuit Protector CR Rocker 5 Series w Silver Aux Switch CPP Push Pull 6 Series w Gold Aux Switch CPR Push to Reset 9 Mixed Construction 2 Pole Only UL CSA Construction Non UL ...

Page 11: ... number are now complete except if you require S screwterminal option from the 5th Decision Table Paddle T Handle Color 01 Black 02 Red 03 Yellow 04 Green 05 Blue 06 White If you have chosen a handle from this table your 4th Decision is now complete except for hardware options in 5th Decision Table Push Pull PP CPP and CPR XX XX No button markings desired not available for CPP CPR OA LINE 5 Marked...

Page 12: ...000 U1 1000 P R only 65 DC 1 10 10 7 5 U 2 500 U1 500 65 DC 2 10 10 15 U1 1000 65 DC 2 10 10 20 10 20 U2 500 U1 5005 00 65 2 D C 11 0 10 30 10 30 U2 120 120R PP PR only 65 2 D C 2 only 10 10 25 U1 100 R only 65 2 D C 21 0 10 25 U2 500 R only 125 50 60 11 10 10 20 7 6 20 U1 10005 00 125 50 60 11 10 10 30 3 U1 1000 T only 125 2 50 60 11 10 10 30 U2 1000 R PP PR only 125 2 50 60 11 11 10 30 20 1 30 U...

Page 13: ...IS SOLELY RESPONSIBLE FOR COMPLIANCE WITH ALL LEGAL REGULATORY AND SAFETY RELATED REQUIREMENTS CONCERNING ITS PRODUCTS AND ANY USE OF SENSATA COMPONENTS IN ITS APPLICATIONS NOTWITHSTANDING ANY APPLICATIONS RELATED INFORMATION OR SUPPORT THAT MAY BE PROVIDED BY SENSATA Mailing Address Sensata Technologies Inc 529 Pleasant Street Attleboro MA 02703 USA Revised 01 17 20 Notes A A neon bulb is provide...

Reviews: