background image

SENS EnerGenius Technical Manual 

Service hotline: 1.800.742.2326 
                           1.303.678.7500  

4. NEUTRAL CONNECTION 

The grounded circuit conductor (neutral) should be connected to the terminal marked “N” on the input 
terminal block, TB1. 
 

5. WIRE RATINGS 

A. All conductors should be rated for use at 90º C or higher. 
B. All input and output conductor sizes should be coordinated with the fault protection devices: 10A on AC 

input (14 AWG, 2.5 mm

2

 typical), 30A on DC output (10 AWG, 6.0 mm

2

 typical). 1 A on Alarm terminal 

block (20 AWG, 0.5 mm

2

  typical).   

C.

Before installation

, ensure adequate battery to charger wire gauge. Wire gauge that is too small may 

activate the open battery detector and the charger will shut down. The maximum allowed resistance seen 
by the charger is found in TABLE 1. These figures already include an allowance for charger variations 
(they are 80% of the typical trip-point) and are for the complete circuit: total of battery leads, battery's 
internal resistance, and any external equipment. The total resistance seen by the charger must not exceed 
the following values:    

TABLE 1 

 

12V 24V 

Maximum Resistance 

58m

Ω

  

116m

Ω

 

D. To determine the appropriate cable and length, please refer to the following table: 

The above lengths consider the resistance of the battery and cables only and do not take into account any    
additional interconnects.  
The above lengths are for operation at 25C. For high temperature installations (40C) reduce lengths by 10%.  

 

In the case of high resistance in the cables to the battery the charger may cycle between AC Fail and 
Battery Fault LEDs (approximately every 10 seconds). Cable runs exceeding the proper length for the 
cable gauge used most often cause this problem. The appropriate solution is to change the cable gauge 
to properly correspond with the necessary cable length (see TABLE 2). In some cases where the resis-
tance is not too far above maximum, the charger may recover after some time (approximately 10 min-
utes) and start charging the batteries. If it is not possible to decrease the system resistance the Battery 
Fault feature can be disabled. Please contact SENS at 1-800-742-2326 for further information. 

E.

Refer to local electrical codes for additional requirements. 

F.

See Section 10 for Terminal Block wire ranges. 

TABLE 2 

Wire Size 

 

Resistance 

per Foot 

Maximum Charger to  

Battery Distance (Ft.) 

 

AWG  mm

m

/Ft. 

12V 

24V 

12V 

24V 

10 

6.0 

1.00 

25 

50 

10 

19 

10 

0.63 

40 

79 

15 

30 

16 

0.40 

63 

126 

24 

48 

Recommended Charger to  

Battery Distance (Ft.) 

 

6. FUSE RATINGS 

A. CAUTION: For continued protection against risk of fire, replace only with same type and rating of fuse. 
B. DC Output Fuse – SENS part number 304530. Bussman Type BK/ATC-30, or Littelfuse 257030 

[ATO30], 30A, 32V, fast acting, blade type automotive 

C. AC Input Fuse – SENS part number 304473. Bussman Type BK/AGC-10, 10A, 250VAC, fast acting, 

ferrule type cylindrical, ¼” X 1-¼” 

Summary of Contents for EnerGenius NRG22-10

Page 1: ...y Charger SENS Part Number Document Revision DCN Number Date 101295 L 105749 July 28 2009 Installation or service questions Call SENS at 1 800 742 2326 303 678 7500 between 8 a m and 5 p m Mountain Ti...

Page 2: ...gs on these products and on the engine A Someone should be within range of your voice or close enough to come to your aid when you work near a storage battery B Have plenty of fresh water and soap nea...

Page 3: ...ber Breakout NRG 22 10 Model Output Output Input Voltage Alarm System Agency Category Voltage Current Frequency Code 12 12 volts 10 10 Amps H 120 208 240V C 5 Alarms L UL S Standard 24 24 volts 50 60...

Page 4: ...WITH LOCAL ELECTRICAL CODES AND OTHER APPLICABLE INSTALLATION CODES B INSTALLATION MUST BE MADE ACCORDING TO THE INSTALLATION INSTRUCTIONS AND ALL APPLICABLE SAFETY REGULATIONS WARNING ONLY TRAINED A...

Page 5: ...ected for service remove the output wiring in the reverse of the order given above D Be sure battery terminals are clean and properly tightened Be careful to keep corrosion from coming in contact with...

Page 6: ...or battery owner s manual and make sure that the 12V 24V select jumper is set to the correct voltage 2 CHARGER LOCATION Do not set a battery or any other object on top of the charger This will obstru...

Page 7: ...erconnects The above lengths are for operation at 25C For high temperature installations 40C reduce lengths by 10 In the case of high resistance in the cables to the battery the charger may cycle betw...

Page 8: ...rger by the chassis only Remove the cover only when access is essential for installation and service and replace it promptly when finished B If possible wear an approved static protection strap If one...

Page 9: ...nch pounds 10 WIRING A All wiring must comply with applicable codes and local ordinances See Section 5 for recommended gauges B The charger contains a DC output fuse for internal fault protection but...

Page 10: ...KDOWN FIGURE 2A FIGURE 2B E Connect the AC line and neutral conductors at TB1 If there is an identified grounded circuit con ductor neutral attach it to the terminal marked N TB1 will accept 14 6 AWG...

Page 11: ...K with no AC input TB5 6 FAIL Defaults to Fail with no AC input TB5 9 FAIL Defaults to OK with no AC input TB5 12 FAIL Defaults to OK with no battery TB5 15 FAIL Defaults to fail with no battery RELAY...

Page 12: ...e 230V position for nominal mains voltages between 208V and 240V B Set the battery range jumper JP1A according to nominal battery voltage Use the 12V position for 12V batteries Use the 24V position fo...

Page 13: ...SERVICE CONSULT THE BATTERY MANUFACTURER TO DETERMINE IF AND HOW THEY CAN BE SAFELY RESTORED TO SERVICE WARNING NEVER LEAVE A JUMPER IN THE JUMP POSITION DURING NORMAL OPERATION THIS DISABLES THE BATT...

Page 14: ...onnect AC power then correct the jumper setting or battery voltage before proceeding E After a short delay typically 10 seconds or less the charger will produce output F If the meter display jumper is...

Page 15: ...a ture increases The output voltage is clamped at 0 and 40 Degrees C to protect against extremely high or low output voltage See chart below Fault Tolerant The charger is protected from the following...

Page 16: ...short circuit is removed In addition to detecting low battery voltage and short circuits the battery charger also monitors the peak voltage at its DC output terminals and will enter lockout if the DC...

Page 17: ...On if Temperature Com pensation Working Off if Temperature Compen sation Option not used Confirm if temperature compensation is in tended to be used Only one sensor Local or re mote should be connect...

Page 18: ...anch circuit breaker and any other disconnect devices 2 The meter display should light immediately after power on The green AC ON LED should be lighted If a temperature sensor is present either intern...

Reviews: