detecting a fault or a shutdown command.
The inverter switches from shutdown mode to standby mode if receiving a
Startup command or detecting that a fault is rectified.
3. Storage
This chapter describes inverter storage requirements.
The following storage instructions apply if the PV inverter will not be deployed
immediately:
>Do not unpack the inverter (put desiccant in the original box if the PV inverter is
unpacked).
>Store the PV inverter at a temperature range of -40°C to +70°C and with the relative
humidity of 0% to 100% (no condensing).
>The PV inverter should be stored in a clean and dry place and be protected from dust
and water vapor corrosion.
> A maximum of eight layers of inverters can be stacked.
> Do not position the inverter at a front tilt, excessive back tilt, or side tilt, or upside
down.
> Conduct periodic inspection during storage. Replace the packing materials immediately
if any rodent bites are found.
>Ensure that qualified personnel inspect and test the inverter before use if it has been
stored for a long time.
4. Installation
DANGER
Do not install the PV inverter on flammable building materials.
Do not install the inverter in an area that stores flammable or explosive
materials.
CAUTION
Do not install the PV inverter in a place where personnel are likely to
come into contact with its enclosure and heat sinks to avoid electrical
shock/ burn.