The connection cable DB9 with a 3.5 mm

stereophonic  jack,  can  be  assembled  as

indicated in the following figure, or can be

bought as an accessory.

RS232 SERIAL PORT

DIP-switches Settings

The  DIP-switches  position  defines  the  module  CAN/MODBUS  communication

parameters: Address and Baud Rate. In the following figure the Baud Rate and Address

values are listed as a function of the DIP-switches position:

ON

KEY

BAUD RATE (

kbps)

ADDRESS

1 2 3 SOFTWARE

20

50

125

250
500

800

1000

 PROGRAMMED

.............. .............

0000000

4 5 6 7 8 9 10

0000001 ADD. 001

0000010

0000011

0000100
0000101

1111111

ADD. 002
ADD. 003
ADD. 004
ADD. 005

ADD. 127

SOFTWARE

 PROGRAMMED

..............

ModBus

CANopen

SW2 SW4

ModBus TERMINATOR

SW3

Type of communication

Protocol

State
ENABLE

DISABLE

CANopen ModBus

2.4

4.8

9.6

19.2

38.4

57.6

115.2

We underline that on all the DIN rail supports a DIP-switch is present  and if it is set to ON

position the CAN network termination is inserted.

Programming

PROGRAMMING THROUGH CAN/MODBUS INTERFACE

Factory Parameters

PROGRAMMING THROUGH  RS232 (FRONTAL JACK)

The module may be programmed/configured through the CAN/MODBUS interface; refer to

the User Manual for details about the communication.

The  module  may  be  programmed/configured  through  the  RS232  interface  by  using

MODBUS-RTU  protocol;  refer  to  the  User  Manual  for  details  about  the

communication. The connection parameters are the following:

Address: 1, Baud Rate: 2400 Baud, Parity: none, Stop bit: 1

.

With all the DIP-switches in OFF position (values from memory), the module is originally

programmed as follows:

MODBUS, Baud Rate: 38400, Bit: 8, Parity: None, Stop bit: 1, Address: 1

To switching ON SW2 and SW4 : CANOPEN, Baud Rate: 20 kbps, Address: 127

.

MI001523-E

ENGLISH 6/8

Summary of Contents for ZC-24DO

Page 1: ...s r l Via Austria 26 35127 PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 For manuals EDS files and configuration software see www seneca it This document is property of SENECA srl Duplication and reprodution are forbidden if not authorized Contents of the present documentation refers to products and technologies described in it All technical data contained in the document may be modif...

Page 2: ...wer supply and CANopen MODBUS interface circuits Overtemperature and short circuit to ground of digital outputs continuous monitoring and consequent fault condition signalling Outputs value in case of no communication or fault condition programmable value or last set value Leds Signallings Power Supply Digital Outputs State CANopen MODBUS Communication MODBUS RTU Communication Node guarding or hea...

Page 3: ...raceways or other objects that obstruct the ventilation slots Never install modules above sources of heat we recommend installation in the lower part of the control panel Inserting on the DIN rail As it is illustrated in the next figure 1 Insert the rear IDC10 connector on a DIN rail free slot the inserting is univocal since the connectors are polarized 2 Tighten the four locks placed at the sides...

Page 4: ...ed GNDCAN GNDMODBUS CANH A CANL B CANH A CANL B CAN bus Connection Rules 1 Install the modules on the DIN rail max 120 2 Connect the remote modules using cables of proper length On the table the following data about the cables length are provided Bus Length CAN network maximum length as a function of the Baud rate It is the lenght of the cables which connect the two bus terminators modules see Sch...

Page 5: ...to 12 A with quick break fuse or quivalent protection Digital Outputs Connections from connectors module rear side Connection suggested to supply 24 V relays The total current entering on power supply terminal must be limited to 0 6Awith quick break fuse or equivalent protection Max current for each output 25 mA IDC10 DOUT17 DOUT24 IDC20 DOUT1 DOUT16 ...

Page 6: ... 4 4 8 9 6 19 2 38 4 57 6 115 2 We underline that on all the DIN rail supports a DIP switch is present and if it is set to ON position the CAN network termination is inserted Programming PROGRAMMING THROUGH CAN MODBUS INTERFACE Factory Parameters PROGRAMMING THROUGH RS232 FRONTAL JACK The module may be programmed configured through the CAN MODBUS interface refer to the User Manual for details abou...

Page 7: ...ounters of the CAN controller has reached or exceeded the warning level too many error frames A guard event NMT Slave or NMT master The SYNC message has not been received within the communication cycle period time out The CAN controller is bus off The device is receiving No error The Device is in working condition MI001523 E ENGLISH 7 8 ON ET002803C Factory Preset ModBus RTU PROTOCOL FRONT PANEL J...

Page 8: ...fice waste disposal service of the retail store where you purchased this product LED RUN Green LED RUN Green STATE Single flash On Blinking ON Pre operational Operational The Device is in the PRE OPERATIONAL state The Device is in the OPERATIONAL state The device is transmitting Stop The Device is in STOPPED state All DIP switch OFF MODBUS Protocol Communication parameters 38400 8 N 1 Addr 1 In ca...

Reviews: