The connection cable DB9 with a 3.5 mm
stereophonic jack, can be assembled as
indicated in the following figure, or can be
bought as an accessory.
RS232 SERIAL PORT
DIP-switches Settings
The DIP-switches position defines the module CAN/MODBUS communication
parameters: Address and Baud Rate. In the following figure the Baud Rate and Address
values are listed as a function of the DIP-switches position:
ON
KEY
BAUD RATE (
kbps)
ADDRESS
1 2 3 SOFTWARE
20
50
125
250
500
800
1000
PROGRAMMED
.............. .............
0000000
4 5 6 7 8 9 10
0000001 ADD. 001
0000010
0000011
0000100
0000101
1111111
ADD. 002
ADD. 003
ADD. 004
ADD. 005
ADD. 127
SOFTWARE
PROGRAMMED
..............
ModBus
CANopen
SW2 SW4
ModBus TERMINATOR
SW3
Type of communication
Protocol
State
ENABLE
DISABLE
CANopen ModBus
2.4
4.8
9.6
19.2
38.4
57.6
115.2
We underline that on all the DIN rail supports a DIP-switch is present and if it is set to ON
position the CAN network termination is inserted.
Programming
PROGRAMMING THROUGH CAN/MODBUS INTERFACE
Factory Parameters
PROGRAMMING THROUGH RS232 (FRONTAL JACK)
The module may be programmed/configured through the CAN/MODBUS interface; refer to
the User Manual for details about the communication.
The module may be programmed/configured through the RS232 interface by using
MODBUS-RTU protocol; refer to the User Manual for details about the
communication. The connection parameters are the following:
Address: 1, Baud Rate: 2400 Baud, Parity: none, Stop bit: 1
.
With all the DIP-switches in OFF position (values from memory), the module is originally
programmed as follows:
MODBUS, Baud Rate: 38400, Bit: 8, Parity: None, Stop bit: 1, Address: 1
To switching ON SW2 and SW4 : CANOPEN, Baud Rate: 20 kbps, Address: 127
.
MI001523-E