DIGITAL OUTPUTS

MI001523-E

ENGLISH 5/8

Digital Outputs Connections from terminals

The total current entering on power supply terminal must be limited to 12 A with quick-break fuse or

quivalent protection.

Digital Outputs Connections from connectors (module rear side)

Connection suggested to supply 24 V relays. The total current entering on power supply terminal must be

limited to 0.6 A with quick-break fuse or equivalent protection. Max. current for each output: 25 mA.

IDC10: DOUT17..DOUT24

IDC20: DOUT1..DOUT16

Summary of Contents for ZC-24DO

Page 1: ...s r l Via Austria 26 35127 PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 For manuals EDS files and configuration software see www seneca it This document is property of SENECA srl Duplication and reprodution are forbidden if not authorized Contents of the present documentation refers to products and technologies described in it All technical data contained in the document may be modif...

Page 2: ...wer supply and CANopen MODBUS interface circuits Overtemperature and short circuit to ground of digital outputs continuous monitoring and consequent fault condition signalling Outputs value in case of no communication or fault condition programmable value or last set value Leds Signallings Power Supply Digital Outputs State CANopen MODBUS Communication MODBUS RTU Communication Node guarding or hea...

Page 3: ...raceways or other objects that obstruct the ventilation slots Never install modules above sources of heat we recommend installation in the lower part of the control panel Inserting on the DIN rail As it is illustrated in the next figure 1 Insert the rear IDC10 connector on a DIN rail free slot the inserting is univocal since the connectors are polarized 2 Tighten the four locks placed at the sides...

Page 4: ...ed GNDCAN GNDMODBUS CANH A CANL B CANH A CANL B CAN bus Connection Rules 1 Install the modules on the DIN rail max 120 2 Connect the remote modules using cables of proper length On the table the following data about the cables length are provided Bus Length CAN network maximum length as a function of the Baud rate It is the lenght of the cables which connect the two bus terminators modules see Sch...

Page 5: ...to 12 A with quick break fuse or quivalent protection Digital Outputs Connections from connectors module rear side Connection suggested to supply 24 V relays The total current entering on power supply terminal must be limited to 0 6Awith quick break fuse or equivalent protection Max current for each output 25 mA IDC10 DOUT17 DOUT24 IDC20 DOUT1 DOUT16 ...

Page 6: ... 4 4 8 9 6 19 2 38 4 57 6 115 2 We underline that on all the DIN rail supports a DIP switch is present and if it is set to ON position the CAN network termination is inserted Programming PROGRAMMING THROUGH CAN MODBUS INTERFACE Factory Parameters PROGRAMMING THROUGH RS232 FRONTAL JACK The module may be programmed configured through the CAN MODBUS interface refer to the User Manual for details abou...

Page 7: ...ounters of the CAN controller has reached or exceeded the warning level too many error frames A guard event NMT Slave or NMT master The SYNC message has not been received within the communication cycle period time out The CAN controller is bus off The device is receiving No error The Device is in working condition MI001523 E ENGLISH 7 8 ON ET002803C Factory Preset ModBus RTU PROTOCOL FRONT PANEL J...

Page 8: ...fice waste disposal service of the retail store where you purchased this product LED RUN Green LED RUN Green STATE Single flash On Blinking ON Pre operational Operational The Device is in the PRE OPERATIONAL state The Device is in the OPERATIONAL state The device is transmitting Stop The Device is in STOPPED state All DIP switch OFF MODBUS Protocol Communication parameters 38400 8 N 1 Addr 1 In ca...