MI003422-E

ENGLISH - 1/4

Z109S-DI

GALVANIC SEPARATION

CURRENT LOOP

WITH

Input current  0 - 20 mA or  4 - 20 mA.
Two-wire sensor supply:
20V , 20mA max protected against short circuit.

~

Measure and retransmission or analog insulated output,
current output  0 - 20 mA or  4 - 20 mA.
Front power supply presence indicator.
Safety i s lation  300 V

CAT II

n u

~

GENERAL FEATURES

TECHNICAL FEATURES

EN

10 - 40 V

, 19 - 28 V

50-60Hz, max 2.5 W.

~

~

Current  0 - 20 mA or 4 - 20 mA, 20 V

± 10%

~

loop supply, input impedance ~50Ω

Output:

Current 0 - 20 mA or 4 - 20 mA, loop impedance < 600Ω

Environemental conditions
- Temperature:
- Humidity:
- Storage temperature:
- Protection degree

From -20 to +60 °C.
min: 30%, max 90% no condensing

n

From -30 to +85 °C
IP20                          (

.

see the

section

How to install

)

Box specification
- Dimensions and weight:
- Material:

100 x 112 x 18mm, 130g
PA6, Black colo r

u

Errors referred to
Input’s measure range:

Connections:

Removable 3-way screw terminals, 5 mm pitch.
cable section's 0.25-2.5 mm²

Response time:

<200us, cutoff frequency (-3dB) 6kHz

Input protection:

30V continuous.

Against surge pulses 400 W / ms

Insulation:

Safety insulation  < 300 V

referred to ground CAT II

~

Test voltage  3500 V

3-way

~

EMI

<1%

Calibration

o

0.2%

10 A

µ

T erm

oeff

h

al c

.

0.02%/°K

Protection
Output / Power supply:

Summary of Contents for Z109S-DI

Page 1: ...0 mA loop impedance 600Ω Environemental conditions Temperature Humidity Storage temperature Protection degree From 20 to 60 C min 30 max 90 no condensing n From 30 to 85 C IP20 see the section How to install Box specification Dimensions and weight Material 100 x 112 x 18mm 130g PA6 Black colo r u Errors referred to Input s measure range Connections Removable 3 way screw terminals 5 mm pitch cable ...

Page 2: ...opriately sized fuse ELECTRICAL CONNECTIONS POWER ACTIVE INPUT use this for the two wire connection of transducers The transducer is directly powered by the Z109S DI module 20V 20mAmax protected against short circuit PASSIVE INPUT use this connection if the input current is external external loop power supply EN61000 6 4 electromagnetic compability industrial environment EN61000 6 2 electromagneti...

Page 3: ...o be on a bar installed IEC EN 60715 in a vertical position For correct operation and extended life make sure that adequate ventilation is provided for the module Do not place raceways or other objects in a way that might obstruct ventilation slots Do not install the module above equipment generating heat We recommend that the module is installed at the bottom of the cabinet We suggest you to inst...

Page 4: ...e negative consequences to the environmentandhumanhealth For more detailed information about the recycling of this product please contact your local city office wastedisposalserviceortheretailstorewhereyoupurchasedthisproduct SENECA s r l Via Austria 26 35127 PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 e mail info seneca it www seneca it Thisdocumentisproperty ofSENECAs r l Duplicat...

Reviews: