MI00369-3-EN
ENGLISH4/8
5 INSTALLATION PROCEDURE
The module has been designed for vertical installation on a IEC EN 60715 DIN rail. For optimal
operation and long life, adequate ventilation must be provided. Avoid positioning cable ducts or other
objects that obstruct the ventilation slots. Avoid mounting modules over equipment that general heat.
Installation in the bottom part of the switchboard is recommended.
OMEGA IEC EN 60715 guide installation and removal.
Insertion on IEC EN 60715 guide:
1) Move the two hooks on the back of the module
outward as illustrated in fig. 1b.
2) Put the module on the OMEGA guide.
3) To secure the module to the OMEGA guide, tighten
the two hooks on the side of the IDC10 rear connector
as illustrated in fig. 1a.
Removal from IEC EN 60715 DIN guide:
As illustrated in figure 1b:
1) Move the two side hooks outward
from the module, assisted by a screwdriver.
2) Extract the module from the guide.
6 ELECTRICAL CONNECTIONS
IDC10 rear connector (POWER AND PORT 1)
The illustration indicates the meanings of the
various IDC10 connector pins if signals are to be
directly sent via them.
Module power is available from the rear connector
or via terminals 2 and 3.
Potential Z-PC-DINAL2-17.5 use
If the Z-PC-DINAL1-17.5 accessory is used, signals
can be sent via terminal board. The illustration
shows the meaning of the various terminals and
DIP-switch position, found in all Seneca supports for
DIN IEC EN 60715 guide, not used for the Modbus
network. GNDSHLD: Connection cable signal
protection shield (recommended).
Summary of Contents for Z-KEY