USER MANUAL – Z-DAQ-PID
3
Potentiometer-type IN
Scale range is configurable: from 1 k
to 100 k
(with parallel
resistor R=330
to connect externally). Excitation current:1 mA.
Input impedance:>5M
Thermocouple-type IN
For TC type: J, K, R, S, T, B, E, N. Input impedance:>5 M
.
Automatic detection if a TC interruption occurs
RTD-type IN
For RTD type: PT100, PT500, PT1000, NI100. Resistance measure
(for 2,3 or 4-wires connection) and wire-resistance measure (for 3,4-
wires connection). Excitation current: 1.1 mA (PT100) and 0.11
mA(PT1000, PT500). Automatic detection if a wire or RTD
interruption occurs
Millivoltmeter-type IN
Scale range is configurable: from -10 mV to 80 mV. Input
impedance:>5 M
Errors related to max
measuring range
Accuracy
Thermal
stability
Linearity error
EMI
Voltage or current-type
input
0.1%
0.01%/°K
0.05%
<1% (2)
TC-type input:
J,K,E,T,N
0.1%
0.01%/°K
0.2°C
<1% (2)
TC-type input:R,S
0.1%
0.01%/°K
0.5°C
<1% (2)
TC-type input:B
(3)
0.1%
0.01%/°K
1.5°C
<1% (2)
Cold junction
compensation (for TC-
type input)
2°C
between
0-50°C
/
/
/
POT-type IN
0.1%
0.01%/°K
0.1%
<1%
RTD-type IN
(4)
0.1%
0.01%/°K
0.02% (if t>0°C)
0.05% (if t<0°C)
<1% (5)
(1) For the input scale ranges, see “Connections”
(2) Influence of wire resistance: 0.1
V/
(3) Output zero if t<400°C
(4) For RTD type: PT100, PT500, PT1000, NI100. All the errors have to be calculated with
reference to resistive value
(5) Influence of wires resistance: 0.005%/
, max20