SETTING THE DIP-SWITCHES
The position of the DIP-switches defines the Modbus communication parameters of the module: Address and
Baud Rate The following table shows the Baud Rate and Address values according to the DIP-switch
setting:
DIP-Switch status
SW1 POSITION
BAUD
RATE
SW1 POSITION
ADDRESS
POSITION
TERMINATOR
1 2 3 4 5 6 7 8
3 4 5 6 7 8
10
9600
#1
Disabled
19200
#2
Enabled
38400
#...
57600
#63
From
EEPROM
From
EEPROM
Note:
When DIP switches 1 to 8 are OFF, the communication settings are taken from programming (EEPROM).
Note 2
: The R S 485 line must be terminated only at the ends of the communication line.
Modbus registers: Holding registers
Register
Name
Description
40013
IN CH1
Channel measurement value, depending on the type of input selected
1bit = 5µV or 0.1°C.
40014
IN CH2
Channel measurement value, depending on the type of input selected
1bit = 5µV or 0.1°C.
40015
IN CH3
Channel measurement value, depending on the type of input selected
1bit = 5µV or 0.1°C.
40016
IN CH4
Channel measurement value, depending on the type of input selected
1bit = 5µV or 0.1°C.
SETTING THE DIP-SWITCHES
The parameters of each of the 4 inputs can be set using the Z-NET and EASY-Z-PC configuration software. It is
possible to get a voltage signal or a thermocouple signal. The following table indicates the start and full scale values
for each type of thermocouple and for the voltage.
TC
Type
Range
Linearisation
error
TC
Type
Range
Linearisation
error
J
-210°C / 1200°C
0.05°C
S
-50°C / 1768°C
0.02°C
K
-200°C / 1372°C
0.05°C
R
-50°C / 1768°C
0.02°C
E
-200°C / 1000°C
0.02°C
B
250°C / 1820°C
0.03°C
N
-210°C / 1300°C
0.04°C
T
-200°C / 400°C
0.04°C
Input range for voltage
-160 mV / 160 mV