USER MANUAL – Z-4AI
5
RS485 Register table
BAUD-RATE (Dip-Switches: DIP-SWITCH STATUS)
1
2
Meaning
Baud-rate=9600 Baud
Baud-rate=19200 Baud
Baud-rate=38400 Baud
Baud-rate=57600 Baud
ADDRESS (Dip-Switches: DIP-SWITCH STATUS)
3
4
5
6
7
8
Meaning
Address and Baud-Rate are acquired from memory(EEPROM)
Address=1
Address=2
Address=3
Address=4
X
X
X
X
X
X
……………………
Address=63
RS485 TERMINATOR (Dip-Switches: DIP-SWITCH STATUS)
9
10
Meaning
RS485 terminator disabled
RS485 terminator enabled
INPUT TYPE (Dip-Switches: ANALOG INPUTS)
1
2
3
4
5
6
7
8
Meaning
IN 1=voltage
IN 1=current
IN 2=voltage
IN 2=current
IN 3=voltage
IN 3=current
IN 4=voltage
IN 4=current
Name
Range
Interpretation of
register
R/W
Default
Address
MachineID
/
MSB, LSB
R
40001
Id_Code (Module ID)
0x07
Bit [15:8]
Ext_Rev (Module version)
Bit [7:0]
FWREV
/
Word
R
40035
Firmware Code
Status
/
Bit
R/W
40016
Input 4 underflow: 0=
there isn’t; 1=there is
/
Bit 15
Input 4 overflow: 0=
there isn’t; 1=there is
/
Bit 14
Input 3 underflow: 0=
there isn’t; 1=there is
/
Bit 13
Input 3 overflow: 0=
there isn’t; 1=there is
/
Bit 12
Input 2 underflow: 0=
there isn’t; 1=there is
/
Bit 11
Input 2 overflow: 0=
there isn’t; 1=there is
/
Bit 10