background image

ENGLISH - 1/8

MI00146 -E

2

S200G 

0 - 20 mA  Stignal Generator with  3 ½ Digits Digital 
Display

I

GENERAL FEATURES

TECHNICAL SPECIFICATIONS

Operating conditions:

Connections :
Protection Index :
Box material:
Dimensioms, weight :
Standards

Output:

Power Supply:

Functioning Temperature: 0..50°C. 
Humidity: 90% at 40°C non-condensing.
Storage Temperature: -25..+60 °C.
Removable terminals.
IP20

Nylon “V0” flame-retardant, impact-resistant.

96 x 96 x 117 mm, 750 g.
EN61000-6-4 02  (electromagnetic  emission,  industrial 

/8

environment)
EN61000-6-2 05  (electromagnetic  immunity,  industrial 

/8

environment)
EN61010-1 01 (safety).

/8

All  circuits  must  be  insulated  from  the  other  circuits  under 
dangerous voltage with double insulation. The power supply 
transformer  must  comply  with  EN60742:  “Insulated 
transformers and safety transformers”.

0..20 mA  with 24 V  loop power supply,

DC

Max load: 600 ohm

230 V   10 % 50-60 Hz, Consumption: 7 VA.

AC



Accuracy and Stability:

Stability to power supply 
variations :

< 0,3 %
0,01 % / 20 %

EN

Instrument from front panel, designed to generate and display a signal from 0 to 20 
mA. 
The front includes multiturn precision potentiometer and 3 digit display and 1 / 2 red 
LED high brightness with height 14 mm. 
The container is plastic V0. 
Typical applications include, for example, to generate the signal for manual opening of 
a valve positioner.

Summary of Contents for S201D

Page 1: ...ut Power Supply Current 4 20 mA adjustable by potentiometer accuracy 10 turns on the indicator frontal panel Functioning Temperature 0 50 C Humidity 90 at 40 C non condensing Storage Temperature 25 60...

Page 2: ...5 6 7 8 9 S201D S201DP IN S P 24V 230V Only for S201DP CALIBRATION 6 Set Point 24V IN 5 2 1 Green Grey White Yellow Pink connection present only with MFC and S201DP D 62XX MF S201D D 62XX MFC S201DP...

Page 3: ...1 5 V 0 10 V 2 10 V Jumper P14 Closed Opened Opened Opened Closed Opened Opened Closed Opened Closed Opened Opened Opened Closed Opened Closed Opened Opened Closed Opened Opened Opened Closed Closed...

Page 4: ...d a specific display view In this case a label is present on the calibration panel where the following informations are listed input signal the scale of display view If no label is present the instrum...

Page 5: ...ironment EN61010 1 01 safety 8 All circuits must be insulated from the other circuits under dangerous voltage with double insulation The power supply transformer must comply with EN60742 Insulated tra...

Page 6: ...MI00146 E 2 ENGLISH 2 8 S200D ELECTRIC CONNECTIONS 1 2 3 4 5 6 7 8 9 S200G 230V TARATURA 0 20 mA...

Page 7: ...ternal jumpers within the board is illustrated on the below figure Setting of the View Scale To set the o display view work on the jumper scale f instantaneous P5 closed full scale of display 0 1000 o...

Page 8: ...if not authorized Contents ofthe presentdocumentation referstoproductsandtechnologiesdescribed init Alltechnicaldatacontainedin the documentmaybemodified withoutpriornoticeContentofthisdocumentationi...