background image

4/6

FIRST STARTUP AND IP CONFIGURATION

At the first startup the IP address is configured in static mode with address 192.168.90.101

By default the SW2 DIP-switch selectors are set to OFF.

In the case of configuration with an IP address obtained from DHCP, and if a DHCP server is not present in your 

network, the device, after 5 minutes from startup, will initialize with the IP address: 

169.254.x.y where the x and y 

values are the last two MAC address digits (see product side label).

N.B.: 

through the software for the 

SDD 

(SENECA Discovery Device) Windows PC, downloadable for free from the 

www.seneca.it/prodotti/sdd site, it is possible to easily identify the device on the network and view / change the IP 

address in a few steps (see USER manual for details).

SW1 DIP-SWITCH SETTINGS

Through DIP-SWITCH-SW1 it is possible to set the IP configuration of the device:

DESCRIPTION

DIP 1

DIP 2

To obtain the configuration from the Flash memory, both SW1 

DIP switch selectors must be set to OFF
To reset the device to factory settings both SW1 DIP switches 

must be set to ON

To force the device’s IP address to the standard value of 

SENECA ethernet products: 192.168.90.101

Reserved

The DIP-switch settings are read only at boot time. At each change, perform a restart.

DEVICE CONFIGURATION

R-KEY-MBUS can be fully set up via integrated web server. The product programming and/or configuration tools, 

as well as all the manuals, can be downloaded using the QR-CODE on the cover. For further information, refer to 

the USER manual.

WEB SERVER

To access the maintenance Web Server with the factory IP address above, use the following credentials: 

Account User: 

admin

; Password: 

admin

Reviews: