4/6
FIRST STARTUP AND IP CONFIGURATION
At the first startup the IP address is configured in static mode with address 192.168.90.101
By default the SW2 DIP-switch selectors are set to OFF.
In the case of configuration with an IP address obtained from DHCP, and if a DHCP server is not present in your
network, the device, after 5 minutes from startup, will initialize with the IP address:
169.254.x.y where the x and y
values are the last two MAC address digits (see product side label).
N.B.:
through the software for the
SDD
(SENECA Discovery Device) Windows PC, downloadable for free from the
www.seneca.it/prodotti/sdd site, it is possible to easily identify the device on the network and view / change the IP
address in a few steps (see USER manual for details).
SW1 DIP-SWITCH SETTINGS
Through DIP-SWITCH-SW1 it is possible to set the IP configuration of the device:
DESCRIPTION
DIP 1
DIP 2
To obtain the configuration from the Flash memory, both SW1
DIP switch selectors must be set to OFF
To reset the device to factory settings both SW1 DIP switches
must be set to ON
To force the device’s IP address to the standard value of
SENECA ethernet products: 192.168.90.101
Reserved
The DIP-switch settings are read only at boot time. At each change, perform a restart.
DEVICE CONFIGURATION
R-KEY-MBUS can be fully set up via integrated web server. The product programming and/or configuration tools,
as well as all the manuals, can be downloaded using the QR-CODE on the cover. For further information, refer to
the USER manual.
WEB SERVER
To access the maintenance Web Server with the factory IP address above, use the following credentials:
Account User:
admin
; Password:
admin