background image

TECHNICAL SPECIFICATIONS

3/4

STANDARDS

ETSI EN 301-489-7

EN 301 511

EN 301 489-1

IEC / EN 60950

Power supply

Voltage

Absorption

Internal batteries

6 - 15 Vdc; 500 mA Max

3.5 W Max

Lithium Ion 3.7 V, 1100 mAh, rechargeable, non-replaceable

Voltage

output

+12 Vdc 50 mA (maximum current)

Temperature

sensor

NTC internal (as standard), external (option*) thermistor

Ambient

conditions

Temperature

Humidity
Storage

temperature
Protection

rating

Seneca recommends use at 0 to 45°C for correct operation

With the power supply present: -20 

÷

 55°C. 

With use of the battery (when discharged): -20 

÷

 5°C Charging is possible in the range: 0 

÷

 45°C.

30%– 90% non condensing.
From 

-20°C to 20°C < 1 year; from -20°C to 45°C < 3 months; from -20°C to 60°C < 1 month
IP40

Connections

Spring clamps, 3.5 mm pitch, connector for Micro USB and SMA connector for GSM, MMCX 

for GPS antennas (option*)

Internal memories

FLASH 1 MB + 8 MB

Slot Type/ 

Memory Micro SD

Push-Push for SD card and SD HC card / max 32GB

Slot Type SIM

Push-Push for mini SIM (15 x 25 mm)

Digital inputs

Type

Maximum 

frequency

Threshold OFF

Threshold ON

4 inputs Reed, contact, PNP, Pulscap
30 Hz

÷

 3 Vdc, I > 1 mA

÷

 24 Vdc, I > 3 mA

Analogue

inputs

2 inputs, Voltage 0 

÷

 30 Vdc / Current 0 

÷

 20 mA, 0.1% of full scale

Display

128x32 LCD Dots with visible area of 39 mm x 8.6 mm

USB

1 micro USB for configuration and supply

CPU

120 MHz 32 bit ARM

GSM

QUAD BAND (850 / 900 / 1800 / 1900 MHz)

Digital outputs

2 outlets Relay 3 A max - 250 V SPST (with shared terminal)

GPS SPECIFICATIONS (if present in the purchased model)

RECEIVER

22 channels

SENSITIVITY

-165 dBm

FIX TIME

32 s usually

ACCURACY

Up to 2.5 m

* To view all accessories visit www.seneca.it/products/myalarm3-cloud.

Reviews: