MI000951-E

ENGLISH - 3/8

Installation rules

This module has been designed for assembly on a DIN 46277 rail. Assembly in vertical
position is recommended in order to increase the module's ventilation, and no raceways or
other objects that compromise aeration must be positioned in the vicinity.
Do not position the module above equipment that generates heat; we recommend
positioning the module in the lower part of the control panel or container compartment.

K

-SU

PPL

Y

K-SUPPL

Y

1 - Attach the module in the upper part of

the rail.

2 - Press the module downwards.

1 - Apply leverage using a screwdriver (as

shown in the figure).

2 - Rotate the module upwards.

Inserting the module in the rail

Removing the module from the rail

Using the K-BUS connector

1 - Compose the K-BUS connectors as required in order to obtain the number of positions

necessary (each K-BUS permits the insertion of no. 2 modules).

2 - Insert the K-BUS connectors in the rail by positioning them on the upper side of the rail

and then rotating them downwards.

s

IMPORTANT: Pay particular attention to the po ition of the protrudent terminals of the
K-BUS. The K-bus must be inserted in the guide with the protrudent terminals on the left
(as shown in the figure) otherwise the modules are turned upside downs.

- Never connect the power supply directly to the bus connector on the DIN

rail.

- Never tap power supply from the bus connector either directly or by using

the module's terminals.

!

Summary of Contents for K-SUPPLY

Page 1: ...power supply even whenever the source of either input undergoes power failure indication of the presence of each channel the LED switches on only when there is sufficient voltage for the operation of...

Page 2: ...e stripping Box Dimensions and weight Reference standards IP20 Temperature 20 65 C Humidity 10 90 non condensing Altitude up to 2000 m a s l 40 85 C Cable clamp terminals 0 2 2 5 mm2 8 mm PBT black 6...

Page 3: ...e 2 Rotate the module upwards Inserting the module in the rail Removing the module from the rail Using the K BUS connector 1 Compose the K BUS connectors as required in order to obtain the number of p...

Page 4: ...ower Fuse sizing selection 630 mA 1250 mA 750 mA 1600 mA _ 100 mA 200 mA 400 mA 630 mA _ _ _ Numbers of modules Rapid type _ _ _ 1250 mA 1500 mA 2 A Average type Delayed type 2 5 10 20 35 50 70 100 60...

Page 5: ...Terminal 7 Terminal 6 Terminal 8 Terminals 2 4 6 and 8 are connected together Output The module provides a K BUS output equal to the input voltage minus the internal drooping value The negative termi...

Page 6: ...5 5 6 6 6 7 7 7 8 8 8 2 2 2 3 3 3 4 4 4 INPUT 2 INPUT 2 INPUT 2 INPUT 1 INPUT 1 INPUT 1 OUT OUT OUT Power supply 2 Power supply 1 Power supply Main Main Main Bus for supplying K serie devices Bus 1 B...

Page 7: ...ent voltage for the first input The illumination threshold is 19 2 V 0 3 V Green Led 2 When illuminated this LED signals the presence of sufficient voltage for a second input The illumination threshol...

Page 8: ...ealth whichcouldotherwisebecausedbyinappropriatedisposalofthisproduct Therecyclingof materials will help to conserve natural resources For more detailed information about the recycling of this product...

Reviews: