background image

ENGLISH - 1/8

MI000951-E

K-SUPPLY

K-BUS power supply for K-Series modules

General Description

The K-SUPPLY module permits the delivery of power supply to numerous K-Series
modules through K-BUS connection by creating interface between an external power
supply system and the user module distribution bus. The impossibility of tapping
current from the bus to the input terminals permits the connection of numerous K-
SUPPLY modules in parallel on the same bus together with the protection provided
against polarity inversion permits the module to offer valid protection against
erroneous connections.
Main features:

two independent inputs that permit the use of one power supply system; redundant
power supply that guarantees the presence of power supply even whenever the
source of either input undergoes power failure;
indication of the presence of each channel: the LED switches on only when there is
sufficient voltage for the operation of the K-Series modules connected;
a LED that signals input inverted polarity or alternating current;
built-in over-voltage (surge) protection;
differential mode filter.

Technical features

Number:

Type:

Voltage:

Current carrying capacity:

Protection:

2, with shared negative terminal.

Pass-through: each input can be accessed by two
pairs of terminals, in this way permitting the same
power supply source to be used for more than one
K-Supply module (see the section entitled

Example

of Connection to more than one bus

).

19,2..30 Vdc

Maximum current per terminal: 4 A

Each positive input must be provided with protection
by an external fuse (see the section entitled

Fuse

Sizing Selection

).

The device has no limit on maximum current.

Input characteristics

EN

Summary of Contents for K-SUPPLY

Page 1: ...power supply even whenever the source of either input undergoes power failure indication of the presence of each channel the LED switches on only when there is sufficient voltage for the operation of...

Page 2: ...e stripping Box Dimensions and weight Reference standards IP20 Temperature 20 65 C Humidity 10 90 non condensing Altitude up to 2000 m a s l 40 85 C Cable clamp terminals 0 2 2 5 mm2 8 mm PBT black 6...

Page 3: ...e 2 Rotate the module upwards Inserting the module in the rail Removing the module from the rail Using the K BUS connector 1 Compose the K BUS connectors as required in order to obtain the number of p...

Page 4: ...ower Fuse sizing selection 630 mA 1250 mA 750 mA 1600 mA _ 100 mA 200 mA 400 mA 630 mA _ _ _ Numbers of modules Rapid type _ _ _ 1250 mA 1500 mA 2 A Average type Delayed type 2 5 10 20 35 50 70 100 60...

Page 5: ...Terminal 7 Terminal 6 Terminal 8 Terminals 2 4 6 and 8 are connected together Output The module provides a K BUS output equal to the input voltage minus the internal drooping value The negative termi...

Page 6: ...5 5 6 6 6 7 7 7 8 8 8 2 2 2 3 3 3 4 4 4 INPUT 2 INPUT 2 INPUT 2 INPUT 1 INPUT 1 INPUT 1 OUT OUT OUT Power supply 2 Power supply 1 Power supply Main Main Main Bus for supplying K serie devices Bus 1 B...

Page 7: ...ent voltage for the first input The illumination threshold is 19 2 V 0 3 V Green Led 2 When illuminated this LED signals the presence of sufficient voltage for a second input The illumination threshol...

Page 8: ...ealth whichcouldotherwisebecausedbyinappropriatedisposalofthisproduct Therecyclingof materials will help to conserve natural resources For more detailed information about the recycling of this product...