IN0020
Revision 05
004799
– 7 of 8
POWER PERFORMANCE PASSION
Installation Notes
Appendix I: SP LINK Configuration Check
AC
S
OURCE
–
AC
I
NPUT
Check the Alternative Source is set to accommodate the different power limit and
voltage/frequency range that the SP PRO will accept when the backup generator is running.
The Primary Source settings are shown by way of comparison between grid and backup
generator.
Alternate AC Source Power – maximum power SP PRO will draw from backup generator
Min, Max AC Voltage – allowable voltage range from generator
Min, Max AC Frequency – allowable frequency range from generator
Note: Default Values shown - Adjust values to suit the backup generator.
External CT
and
Extern. Contactor/CT
settings are not used in this configuration.
AC
S
OURCE
–
G
ENERATOR
C
ONTROLLER
S
ETTINGS
Generator Controller: Enabled
Note: Remaining settings can
be adjusted based on specific
backup generator
requirements. See SP PRO
User Manual – Generator
Controller Settings for further
details.