XW70LH 

3/5 

dFP  Probe selection for defrost termination: nP

  = no probe; 

P1

  =thermostat probe; 

P2 = 

evaporator probe; 

P3

 =configurable probe; 

P4

 = Probe on Hot Key plug. 

dtE  Defrost termination temperature

: (-50÷50 °C/  

-58÷122°F) (Enabled only when EdF=Pb) sets the temperature measured by the evaporator 

probe, which causes the end of defrost. 

IdF   Interval between defrost cycles

: (0÷120h) Determines the time interval between the 

beginning of two defrost cycles. 

MdF  (Maximum) length for defrost

: (0÷255min) When 

P2P = n

, (not evaporator probe: timed 

defrost) it sets the defrost duration, when 

P2P = y

 (defrost end based on temperature) it sets 

the maximum length for defrost. 

dSd Start defrost delay

: ( 0÷99min) This is useful when different defrost start times are necessary 

to avoid overloading the plant.  

dFd  Temperature displayed during defrost

: (

rt

 = real temperature; 

it

 = temperature at defrost 

start; 

SEt

 = set point; 

dEF

 = “dEF” label) 

dAd MAX display delay after defrost

: (0÷255min). Sets the maximum time between the end of 

defrost and the restarting of the real room temperature display. 

Fdt  Drip time

: (0

120 min) time interval between reaching defrost termination temperature and the 

restoring of the control’s normal operation. This time allows the evaporator to eliminate water 

drops that might have formed due to defrost. 

dPo  First defrost after start-up

: (y = immediately; n = after the IdF time) 

dAF  Defrost delay after continuous cycle

: (0

23.5h) time interval between the end of the fast 

freezing cycle and the following defrost related to it. 

FANS 
FnC Fans operating mode

C-n

= runs with the compressor, OFF during defrost;  

o-n

 = continuous mode, OFF during defrost;  

C-Y

 = runs with the compressor, ON during defrost;  

o-Y

 = continuous mode, ON during defrost;  

Fnd Fans delay after defrost:

 (0÷255min) Interval between end of defrost and evaporator fans start.

 

Fct  Temperature differential avoiding short cycles of fans 

(0÷59°C; Fct=0 function disabled). If 

the difference of temperature between the evaporator and the room probes is more than the 

value of the Fct parameter, the fans are switched on.

 

FSt   Fans stop temperature

: (-50÷50°C/122°F) setting of temperature, detected by evaporator 

probe, above which fans are always OFF. 

Fon Fan ON time:

 (0÷15 min)

 with 

Fnc = C_n or C_y, (fan activated in parallel with compressor). it 

sets the evaporator fan ON cycling time when the compressor is off. With Fon =0 and FoF 

≠ 0 

the fan are always off, with Fon=0 and FoF =0 the fan are always off.

 

FoF Fan OFF time:

 (0÷15 min)

 with 

Fnc = C_n or C_y, (fan activated in parallel with compressor). it 

sets the evaporator fan off cycling time when the compressor is off. With Fon =0 and FoF 

≠ 0 

the fan are always off, with Fon=0 and FoF =0 the fan are always off.

 

FAP  Probe selection for fan management: nP

 = no probe; 

P1

 =thermostat probe; 

P2 = 

evaporator 

probe; 

P3

 =configurable probe; 

P4

 = Probe on Hot Key plug. 

AUXILIARY THERMOSTAT CONFIGURATION (terms. 20-21) – OA4 = AUS 
ACH Kind of regulation for auxiliary relay

Ht 

= heating; 

CL 

= cooling 

SAA Set Point for auxiliary relay:

 (-50,0÷110,0°C; -58÷230°F) it defines the room temperature set 

point  to switch auxiliary relay.

 

SHy  Differential for auxiliary output: 

(0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for 

auxiliary output set point.  

With ACH = cL 

AUX Cut in is SAA + SHy; . AUX Cut  out is SAA 

With ACH = Ht 

AUX Cut in is SAA - SHy; . AUX Cut out  is SAA 

ArP  Probe selection for auxiliary

: nP = no probe, the auxiliary relay is switched only by button; 

P1 

Probe 1 (Thermostat probe); 

P2 = 

Probe 2 (evaporator probe); 

P3 = 

Probe 3 (display probe); 

P4 = 

Probe 4 fourth probe. 

Sdd  Auxiliary relay off during defrost: n = 

the auxiliary relay operates during defrost. 

 

y = 

the auxiliary relay is switched off during defrost. 

ALARMS 
ALP  Probe selection for alarm

: nP = no probe, the temperature alarms are disabled; 

P1 = 

Probe 1 

(Thermostat probe); 

P2 = 

Probe 2 (evaporator probe); 

P3 = 

Probe 3 (display probe); 

P4 = 

Fourth probe. 

ALC  Temperature alarms configuration:

 (Ab; rE) 

 

Ab

= absolute temperature: alarm temperature is given by the ALL or ALU values.  

rE

  = 

temperature alarms are referred to the set point. Temperature alarm is enabled when the 

temperature exceeds the “SET+ALU” or “SET-ALL” values. 

ALU  MAXIMUM temperature alarm

: (SET÷110°C; SET÷230°F) when this temperature is reached  

the alarm is enabled, after the “ALd” delay time. 

ALL Minimum temperature alarm

: (-50.0 ÷ SET°C; -58÷230°F when this temperature is reached  

the alarm is enabled, after the “ALd” delay time. 

AFH  Differential for temperature alarm/ fan recovery: 

(0,1÷25,5°C; 1÷45°F) Intervention 

differential for recovery of temperature alarm. It’s also used for the restart of the fan when the 

FSt temperature is reached  

ALd  Temperature alarm delay

: (0÷255 min) time interval between the detection of an alarm 

condition and alarm signalling. 

dAO Exclusion of temperature alarm at startup

: (from 0.0 min to 23.5h) time interval between the 

detection of the temperature alarm condition after instrument power on and alarm signalling. 

CONDENSER TEMPERATURE ALARM 
AP2  Probe selection for temperature alarm of condenser: nP

 = no probe; 

P1

 =thermostat probe; 

P2 = 

evaporator probe; 

P3

 =configurable probe; 

P4

 = Probe on Hot Key plug. 

AL2 Low temperature alarm of condenser

:

 

(-55÷150°C) when this temperature is reached the LA2 

alarm is signalled, possibly after the Ad2 delay. 

Au2  High temperature alarm of condenser

:

 

(-55÷150°C) when this temperature is reached the 

HA2 alarm is signalled, possibly after the Ad2 delay. 

AH2 Differential for temperature condenser alarm recovery

:

 

(0,1÷25,5°C; 1÷45°F) 

Ad2 Condenser temperature alarm delay

: (0÷255 min) time interval between the detection of the 

condenser alarm condition and alarm signalling. 

dA2  Condenser temperature alarm exclusion at start up

: (from 0.0 min to 23.5h, res. 10min) 

bLL  Compressor off with low temperature alarm of condenser

:

 n = no: 

compressor keeps on 

working

; Y = yes, 

compressor is switched off till the alarm is present, in any case regulation 

restarts after AC time at minimum.

 

AC2 Compressor off with high temperature alarm of condenser

:

 n = no: 

compressor keeps on 

working

; Y = yes, 

compressor is switched off till the alarm is present, in any case regulation 

restarts after AC time at minimum.

 

AUXILIARY RELAYS 
tbA  Alarm relay silencing (with oA3 or oA4=ALr):  

n

= silencing disabled: alarm relay stays on till alarm condition lasts,  

=silencing enabled: alarm relay is switched OFF by pressing a key during an alarm 

oA3 Fourth relay configuration (1-3):

 

dEF, FAn: 

do not select it!.

  ALr

: alarm; 

Lig

: light;

 AuS

Auxiliary relay; 

onF

: always on with instrument on; 

db= 

neutral zone; 

cP2 = 

second compressor;  

dEF2: 

do not select it!;.

 HES:

. night blind

 

oA4 Fifth relay configuration (20-21):

 

dEF, FAn: 

do not select it!.

  ALr

: alarm; 

Lig

: light;

 AuS

Auxiliary relay; 

onF

: always on with instrument on; 

db= 

neutral zone; 

cP2 = 

second compressor;  

dEF2: 

do not select it!;.

 HES:

. night blind

 

AoP  Alarm relay polarity: 

it set if the alarm relay is open or closed when an alarm happens. 

CL

terminals 1-2 closed during an alarm; 

oP

 = terminals 1-2 open during an alarm

 

DIGITAL INPUTS 
i1P  Digital input polarity (13-14): oP: 

the digital input is activated by opening the contact; 

CL: 

the 

digital input is activated by closing the contact.

 

i1F Digital input configuration (13-14): EAL

= external alarm: “EA” message is displayed; 

bAL

serious alarm “CA” message is displayed. 

PAL

= pressure switch alarm, “CA” message is 

displayed; 

dor

= door switch function; 

dEF

= activation of a defrost cycle; 

AUS

=not enabled; 

Htr

= kind of action inversion (cooling – heating); 

FAn

=

 not set it; ES

=

 

Energy saving; 

HdF 

=

 

Holiday defrost (enable only with RTC); 

onF = 

to switch the controller off. 

did 

(0

255 min) 

with

 

i1F= EAL or i1F = bAL digital input alarm delay (13-14):

 delay between the 

detection of the external alarm condition and its signalling. 

with

 

i1F= dor: door open signalling delay 

with i1F= PAL: time for pressure switch function: 

time interval to calculate the number of 

the pressure switch activation. 

i2P  2

nd

 digital input polarity (13-19): oP: 

the digital input is activated by opening the contact; 

CL: 

the digital input is activated by closing the contact.

 

i2F  2

nd

  digital input configuration (13-19): EAL

= external alarm: “EA” message is displayed; 

bAL

= serious alarm “CA” message is displayed. 

PAL

= pressure switch alarm, “CA” message is 

displayed; 

dor

= door switch function; 

dEF

= activation of a defrost cycle; 

AUS

=not enabled; 

Htr

= kind of action inversion (cooling – heating); 

FAn

=

 not set it; ES

=

 

Energy saving; 

HdF 

=

 

Holiday defrost (enable only with RTC); 

onF = 

to switch the controller off. 

d2d 

(0

255 min) 

with

 

i2F= EAL or i2F= bAL 2

nd

 digital input alarm delay (13-19):

 delay between 

the detection of the external alarm condition and its signalling. 

with

 

i2F= dor: door open signalling delay 

with i2F= PAL: time for pressure switch function: 

time interval to calculate the number of 

the pressure switch activation. 

nPS Pressure switch number:

 (0 

15) Number of activation of the pressure switch, during the “

did

” 

interval, before signalling the alarm event (I2F= PAL).  

If the nPS activation in the did time is reached, switch off and on the instrument to 

restart normal regulation. 

odc  Compressor and fan status when open door:

  

no

  = normal; 

Fan

  = Fan OFF; 

CPr 

Compressor OFF; 

F_C

 = Compressor and fan OFF.  

rrd  Outputs restart after doA alarm: no= 

outputs not affected by the doA alarm;  

yES = 

outputs 

restart with the doA alarm. 

HES Temperature increase during the Energy Saving cycle: 

(-30,0°C

30,0°C) it sets the increasing value of the set point during the Energy Saving cycle.  

TO SET CURRENT TIME AND WEEKLY HOLIDAYS (ONLY FOR MODELS WITH RTC) 
Hur 

Current hour 

(0 ÷ 23 h) 

Min 

Current minute

 (0 ÷ 59min) 

dAY  Current day

 (Sun ÷ SAt) 

Hd1  First weekly holiday 

(Sun ÷ nu) Set the first day of the week which follows the holiday 

times. 

Hd2  Second weekly holiday 

(Sun ÷ nu) Set the second day of the week which follows the 

holiday times. 

N.B.   Hd1,Hd2 

can be set also as

 “nu” 

value (Not Used).

  

TO SET ENERGY SAVING TIMES (ONLY FOR MODELS WITH RTC) 
ILE 

Energy Saving cycle start during workdays

: (0 ÷ 23h 50 min.) During the Energy Saving 

cycle the set point is increased by the value in HES so that the operation set point is SET + 

HES.  

dLE  Energy Saving cycle length during workdays

: (0 ÷ 24h 00 min.) Sets the duration of the 

Energy Saving cycle on workdays.  

ISE 

Energy Saving cycle start on holidays

. (0 ÷ 23h 50 min.) 

dSE  Energy Saving cycle length on holidays

 (0 ÷ 24h 00 min.) 

TO SET DEFROST TIMES (ONLY FOR MODELS WITH RTC) 
Ld1÷Ld6 Workday defrost start

 (0 ÷ 23h 50 min.) These parameters set the beginning of the 6 

programmable defrost cycles during workdays. Ex. When 

Ld2

 = 12.4 the second defrost starts 

at 12.40 during workdays.  

Sd1÷Sd6 Holiday defrost start

  (0 ÷ 23h 50 min.) These parameters set the beginning of the 6 

programmable defrost cycles on holidays. Ex. When 

Sd2

 = 3.4 the second defrost starts at 3.40 

on holidays.  

N.B. :To disable a defrost cycle set it to “nu”(not used). 

Ex. 

 If

 Ld6

=nu

 ; 

 the sixth defrost 

cycle is disabled 

OTHER 
Adr   Serial address

  (1÷244): Identifies the instrument address when connected to a ModBUS 

compatible monitoring system. 

PbC Type of probe:

 it allows to set the kind of probe used by the instrument: 

PbC

 = PBC probe, 

ntc 

NTC probe. 

onF  on/off key enabling: nu = 

disabled; 

oFF = 

enabled; 

ES = not set it

dP1  Thermostat probe display 

dP2  Evaporator probe display 

dP3  Third probe display

optional

dP4  Fourth probe display

rSE  Real set point:

  it shows the set point used during the energy saving cycle or during the 

continuous cycle. 

rEL  Software release 

for internal use

Ptb  Parameter table code: 

readable only

8.

 

DIGITAL INPUTS  

The first digital input 13-14 is enabled  with P3P = n. 

With P3P = n and i1F = i2F the second digital input is disabled 

The free voltage digital inputs are programmable by the “

i1F

” and i2F  parameters. 

8.1

 

GENERIC ALARM (i1F or i2F = EAL) 

As soon as the digital input  is activated the unit will wait for “

did

” time delay before signalling the 

EAL

” alarm message. The outputs status don’t change. The alarm stops just after the digital input is 

de-activated. 

Summary of Contents for 2000152

Page 1: ...3 2021 Pag 1 J P SELECTA s a u Autov a A 2 Km 585 1 Abrera 08630 Barcelona Espa a Tel 34 937 700 877 Fax 34 937 702 362 e mail selecta jpselecta es website http www grupo selecta com ARMARIO REFRIGERA...

Page 2: ...i n del personal 6 5 3 Utilizaci n con sustancias peligrosas 6 5 4 Mantenimiento 6 5 5 Garant a 6 Aviso a los clientes 6 6 Instalaci n 7 6 1 Emplazamiento 7 6 2 Conexi n a la red el ctrica 7 7 Regulad...

Page 3: ...enido coincide con lo indicado en el apartado de la Lista de embalaje Si se observa alg n componente da ado o la ausencia de alguno avisar r pidamente al distribuidor No instalar ni utilizar el equipo...

Page 4: ...rio dise ado para la conservaci n de productos farmac uticos medi camentos microtubos etc que requieran una temperatura constante a 4 C y donde se puedan dar fallos de alimentaci n que hagan peligrar...

Page 5: ...com La tecnolog a nica en el mercado de almacenamiento de energ a frig or fica y la gran capacidad de aislamiento de su carcasa permite que la c mara mantenga la temperatura interior durante periodos...

Page 6: ...o similar No utilizar disolventes agresivos 5 5 Garant a Este producto tiene una garant a de un a o La garant a no cubre los da os causados por uso indebido o causas ajenas a J P SELECTA s a u Cualqui...

Page 7: ...ctrica Escoger una toma de corriente cercana al equipo y adecuada a la potencia del equipo Utilizar el cable de conexi n suministrado u otro de similares caracter sticas Para su seguridad la toma de...

Page 8: ...los d as feriados La duraci n m xima est controlada por el par metro MdF mientras que el par metro P2P habilita la segunda sonda fin de deshielo a temperatura o queda deshabilitada fin de deshielo a...

Page 9: ...FORMA MANUAL 1 Mantenga presionadas las teclas o y n durante algunos segundos hasta que aparezca el mensaje POF intermitente 2 Llegados a este punto el teclado ha quedado bloqueado solo se puede ver e...

Page 10: ...del set point de las alarmas de temperatura y de la activaci n de los ventiladores ALd Retardo de la alarma de temperatura 0 255 min intervalo de tiempo entre la detecci n de una alarma de temperatur...

Page 11: ...igital invierte el estado del rel auxiliar 8 7 INVERSI N DE LA ACCI N DEL CONTROLADOR FR O CALIENTE i1F o i2F Htr Hasta que la entrada digital se activa se invierte la acci n del controlador de fr o a...

Page 12: ...ipci n Rango C F Nivel SET Set point LS US 5 0 rtC Men de visualizaci n Pr1 Hy Hist resis de regulaci n del compresor 0 1 25 5 C 1 255 F 2 0 Pr1 LS Set Point m nimo 50 C SET 58 F SET 50 0 Pr2 US Set P...

Page 13: ...Minutos actuales 0 59 rtc dAY d as de la semana actual Sun SAt rtc Hd1 Primer d a festivo semanal Sun SAt nu nu rtc Hd2 Segundo d a festivo semanal Sun SAt nu nu rtc ILE Horario di inicio del ciclo de...

Page 14: ...es contact with J P SELECTA s technical service Do not use the equipment in explosive flammable or corrosive atmospheres 2 Packing list Model 2000152 Shelves guides 2x 2000011 Shelves 2x 2000021 3 Tec...

Page 15: ...12 14 16h 12h Ambient 25 C Ambient 20 C Temperatura interior Ejemplo de la evoluci n de la temperatura a dos condiciones ambiente distintas desde que se produce el fallo de alimentaci n OFF 4 Equipme...

Page 16: ...ttp www grupo selecta com Unique on the market technology for storing cooling energy The high in sulation capacity of its casing allows the chamber to maintain internal tem peratures for periods of mo...

Page 17: ...ator with a cloth and a cleaner or a similar solution Do not use aggressive solvents 5 5 Warranty This product is guaranteed for one year It does not cover damages caused by an incorrect use or causes...

Page 18: ...at the rear part 6 2 Connection to the mains Plug the equipment to a near socket suitable for the equipment power Use the connection cable supplied or a similar one For your safety the equipment must...

Page 19: ...ORATOR FANS The fan control mode is selected by means of the FnC parameter FnC C_n fans will switch ON and OFF with the compressor and not run during defrost FnC o_n fans will run even if the compress...

Page 20: ...p pressed together for more than 3s the o and n keys till the Pon message will be displayed 6 9 THE CONTINUOUS CYCLE When defrost is not in progress it can be activated by holding the o key pressed fo...

Page 21: ...bLL Compressor off with low temperature alarm of condenser n no compressor keeps on working Y yes compressor is switched off till the alarm is present in any case regulation restarts after AC time at...

Page 22: ...imum current allowed for all the loads is 20A 12 1 PROBE CONNECTION The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration It is recommended to place th...

Page 23: ...ary relay operating during defrost n y n Pr2 ALP Alarm probe selection nP P1 P2 P3 P4 P1 Pr2 ALc Temperat alarms configuration rE related to set Ab absolute Ab Pr2 ALU MAXIMUM temperature alarm Set 11...

Page 24: ...MANUAL CODE 80412 REV 0 03 2021 Page 24 J P SELECTA s a u Autov a A 2 Km 585 1 Abrera 08630 Barcelona Espa a Tel 34 937 700 877 Fax 34 937 702 362 e mail selecta jpselecta es website http www grupo s...

Reviews: