XW70LH 

2/5 

LED  MODE 

FUNCTION 

 

ON 

Defrost enabled 

 

Flashing  Drip time in progress 

 

ON 

Fans enabled 

 

Flashing  Fans delay after defrost in progress. 

  ON 

An alarm is occurring 

  ON 

Continuous cycle is running 

ECO

 

ON 

Energy saving enabled 

 

ON 

Light on 

  ON 

Auxiliary relay on 

°C/°F 

ON 

Measurement unit 

°C/°F 

Flashing  Programming phase 

5.

 

MAX & MIN TEMPERATURE MEMORIZATION 

5.1

 

HOW TO SEE THE MIN TEMPERATURE 

1. 

 

Press and release the 

n

 key. 

2. 

 

The “Lo” message will be displayed followed by the minimum temperature recorded. 

3. 

 

By pressing the 

n

 key again or by waiting 5s the normal display will be restored. 

5.2

 

HOW TO SEE THE MAX TEMPERATURE 

1. 

 

Press and release the 

o

 key. 

2. 

 

The “Hi” message will be displayed followed by the maximum  temperature recorded. 

3. 

 

By pressing the 

o

 key again or by waiting 5s the normal display will be restored. 

5.3

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

1.

 

Hold press the SET key for more than 3s, while the max. or min temperature is displayed. (rSt 

message will be displayed) 

2.

 

To confirm the operation the “rSt” message starts blinking and the normal temperature will be 

displayed. 

6.

 

MAIN FUNCTIONS 

6.1

 

TO SET THE CURRENT TIME AND DAY (ONLY FOR INSTRUMENTS 

WITH RTC) 

When the instrument is switched on, it’s necessary to program the time and day. 

1.

 

Enter the Pr1 programming menu, by pushing the SET + 

keys for 3s. 

2.

 

The rtc parameter is displayed. Push the SET key to enter the real time clock menu. 

3.

 

The Hur (hour) parameter is displayed. 

4.

 

Push the SET and set current hour by the UP and Down keys, then push SET to 

confirm the value.. 

5.

 

Repeat the  same operations on the Min (minutes) and dAy (day) parameters. 

To exit: 

Push SET+UP keys or wait for 15 sec without pushing any keys. 

6.2

 

HOW TO SEE THE SET POINT 

 

1.

 

Push and immediately release the 

SET 

key: the display will show the Set 

point value; 

2.

 

Push and immediately release the 

SET 

key or wait for 5 seconds to  

display the probe value again. 

6.3

 

HOW TO CHANGE THE SETPOINT 

1.

 

Push the 

SET 

key for more than 2 seconds to change the Set point value; 

2.

 

The value of the set point will be displayed and the “

°C” or “°F”

 LED starts blinking; 

3.

 

To change the Set value push the 

or 

n

 arrows within 10s. 

4.

 

To memorise the new set point value push the 

SET

 key again or wait 10s. 

6.4

 

HOW TO START A MANUAL DEFROST 

 

Push the 

DEF 

key for more than 2 seconds and a manual defrost will start. 

6.5

 

HOW TO CHANGE A PARAMETER VALUE 

To change the parameter’s value operate as follows:  

1.

 

Enter the Programming mode by pressing the 

Set

 + 

n

 keys for 3s (the “

°C” or “°F”

 LED starts 

blinking). 

2.

 

Select the required parameter. Press the “

SET

” key to display its value 

3.

 

Use “

UP

” or “

DOWN

” to change its value. 

4.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + UP 

or wait 15s without pressing a key. 

NOTE

: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

6.6

 

THE HIDDEN MENU 

The hidden menu Includes all the parameters of the instrument. 

6.6.1  HOW TO ENTER THE HIDDEN MENU 

1.

 

Enter the Programming mode by pressing the 

Set

 + 

n

 keys for 3s (the “

°C” or “°F”

 LED starts 

blinking). 

2.

 

Released the keys, then push again the Set+

n

  keys for more than 7s. The Pr2 label will be 

displayed immediately followed from the HY parameter.  

NOW YOU ARE IN THE HIDDEN MENU.

 

3.

 

Select the required parameter. 

4.

 

Press the “

SET

” key to display its value 

5.

 

Use 

or 

n

 to change its value. 

6.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + 

or wait 15s without pressing a key. 

NOTE1: 

if none parameter is present in Pr1, after 3s the “noP” message is displayed. Keep the keys 

pushed till the Pr2 message is displayed.  

NOTE2

: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

6.6.2  HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE 

FIRST LEVEL AND VICEVERSA. 

Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user 

level) by pressing 

“SET + 

n

.  

In HIDDEN MENU when a parameter is present in First Level the decimal point is on. 

6.7

 

HOW TO LOCK THE KEYBOARD 

1. 

 

Keep pressed for more than 3 s the 

UP

 +  

DOWN

 keys. 

2. 

 

The “POF” message will be displayed and the keyboard will be locked. At this point it will be 

possible only to see the set point or the MAX o Min temperature stored 

3. 

 

If a key is pressed more than 3s the “POF” message will be displayed. 

6.8

 

TO UNLOCK THE KEYBOARD 

Keep pressed together for more than 3s the 

and 

n

  keys, till the 

“Pon” 

message will be 

displayed. 

6.9

 

THE CONTINUOUS CYCLE 

When defrost is not in progress, it can be activated by holding the “

o

” key pressed for about 3 

seconds. The compressor operates to maintain the “

ccS

” set point for the time set through the “

CCt

” 

parameter. The cycle can be terminated before the end of the set time using the same activation key 

o

” for 3 seconds. 

6.10

 

THE ON/OFF FUNCTION 

 

 

With “

onF = oFF

”, pushing the 

ON/OFF

 key, the instrument is switched off. The 

“OFF” 

message is displayed. In this configuration, the regulation is disabled.  

To switch the instrument on, push again the ON/OFF key. 

 

WARNING: Loads connected to the normally closed contacts of the relays are always 

supplied and under voltage, even if the instrument is in stand by mode.  

7.

 

PARAMETERS 

rtc  Real time clock menu (only for controller with RTC): 

to set the time and date and defrost 

start time. 

REGULATION 
Hy Differential

: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point. Compressor Cut IN is 

Set Point +  differential (Hy). Compressor Cut OUT is when the temperature reaches the set 

point. 

LS  Minimum set point:

 (- 50°C÷SET/-58°F÷SET): Sets the minimum value for the set point. 

US Maximum set point: 

(SET÷110°C/ SET÷230°F). Set the maximum value for set point. 

Ot  Thermostat probe calibration

: (-12.0÷12.0°C; -120÷120°F) allows to adjust possible offset of 

the thermostat probe. 

P2P  Evaporator probe presence: n

= not present: the defrost stops by time; 

y=

 present: the defrost 

stops by temperature. 

OE Evaporator probe calibration:

 (-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of 

the evaporator probe. 

P3P  Third probe presence (P3): n

= not present:, the terminals 13-14 operate as digital input.; 

y=

 

present:, the terminals 13-14  operate as third probe. 

O3 Third probe calibration  (P3):

 (-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of 

the third probe. 

P4P Fourth probe presence

: (n = Not present; y = present). 

o4  Fourth probe calibration

: (-12.0

12.0°C) allows to adjust possible offset of the fourth probe. 

OdS Outputs activation delay at start up:

 (0÷255min) This function is enabled at the initial start up 

of the instrument and inhibits any output activation for the period of time set in the parameter.  

AC  Anti-short cycle delay

: (0÷50 min) minimum interval between the compressor stop and the 

following restart. 

AC1 2

nd

 compressor delay at start up 

(0÷255s) Used only with oA3 or oA4 = cP2 Time interval 

between the switching on of the first compressor and the second one. 

rtr  Percentage of the second and first probe  for  regulation (0÷100; 100 = P1, 0 = P2 ): 

it 

allows to set the regulation according to the percentage of the first and second probe, as for the 

following formula (rtr(P1-P2)/100 + P2). 

CCt Compressor ON time during continuous  cycle: 

(0.0÷24.0h; res. 10min) Allows to set the 

length of the continuous cycle: compressor stays on without interruption for the CCt time. Can be 

used, for instance, when the room is filled with new products. 

CCS Set point for continuous cycle: 

(-50÷150°C) it sets the set point used during the continuous 

cycle. 

COn Compressor ON time with faulty probe: 

(0÷255 min) time during which the compressor is 

active in case of faulty thermostat probe. With COn=0 compressor is always OFF. 

COF Compressor OFF time with faulty probe: 

(0÷255 min) time during which the compressor is 

OFF in case of faulty thermostat probe. With COF=0 compressor is always active. 

DISPLAY 
CF Temperature measurement unit: 

 

°C=

Celsius; 

°F

=Fahrenheit. WARNING: When the 

measurement unit is changed the SET point and the values  of the parameters Hy, LS, US, Ot, 

ALU and ALL have to be checked and modified if necessary). 

rES  Resolution (for °C)

: (in = 1°C; dE = 0.1 °C) allows decimal point display. 

Lod  Instrument display

: (P1; P2, P3, P4,  SET, dtr): it selects which probe is displayed by the 

instrument: 

P1

 = Thermostat probe; 

P2

 = Evaporator probe; 

P3

 = Third probe(only for model 

with this option enabled); 

P4

 = Fourth probe,

 SET

 = set point;  

dtr

 = percentage of visualization. 

rEd  X- REP display (

optional

)

: (P1; P2, P3, P4,  SET, dtr): it selects which probe is displayed by 

X- REP: 

P1

 = Thermostat probe; 

P2

 = Evaporator probe; 

P3

 = Third probe(only for model with 

this option enabled); 

P4

 = Fourth probe,

 SET

 = set point;  

dtr

 = percentage of visualization. 

dLy  Display delay: 

(0 ÷20.0m; resul. 10s) when the temperature increases, the display is updated 

of 1 °C/1°F after this time. 

dtr  Percentage of the second and first probe for visualization when Lod = dtr (0÷100; 100 = 

P1, 0 = P2 ): if Lod = dtr 

it allows to set the visualization according to the percentage of the 

first and second probe, as for the following formula (dtr(P1-P2)/100 + P2). 

DEFROST 
EdF  Defrost mode (only for controller with RTC):

    

 

rtc 

Real Time Clock mode

. Defrost time follows 

Ld1÷Ld6

  parameters on workdays  and 

Sd1÷Sd6

 on holidays. 

in

 = 

interval mode

. The defrost starts when the time “

idF

” is expired. 

tdF   Defrost type

: EL = electrical heater; in = hot gas 

Summary of Contents for 2000152

Page 1: ...3 2021 Pag 1 J P SELECTA s a u Autov a A 2 Km 585 1 Abrera 08630 Barcelona Espa a Tel 34 937 700 877 Fax 34 937 702 362 e mail selecta jpselecta es website http www grupo selecta com ARMARIO REFRIGERA...

Page 2: ...i n del personal 6 5 3 Utilizaci n con sustancias peligrosas 6 5 4 Mantenimiento 6 5 5 Garant a 6 Aviso a los clientes 6 6 Instalaci n 7 6 1 Emplazamiento 7 6 2 Conexi n a la red el ctrica 7 7 Regulad...

Page 3: ...enido coincide con lo indicado en el apartado de la Lista de embalaje Si se observa alg n componente da ado o la ausencia de alguno avisar r pidamente al distribuidor No instalar ni utilizar el equipo...

Page 4: ...rio dise ado para la conservaci n de productos farmac uticos medi camentos microtubos etc que requieran una temperatura constante a 4 C y donde se puedan dar fallos de alimentaci n que hagan peligrar...

Page 5: ...com La tecnolog a nica en el mercado de almacenamiento de energ a frig or fica y la gran capacidad de aislamiento de su carcasa permite que la c mara mantenga la temperatura interior durante periodos...

Page 6: ...o similar No utilizar disolventes agresivos 5 5 Garant a Este producto tiene una garant a de un a o La garant a no cubre los da os causados por uso indebido o causas ajenas a J P SELECTA s a u Cualqui...

Page 7: ...ctrica Escoger una toma de corriente cercana al equipo y adecuada a la potencia del equipo Utilizar el cable de conexi n suministrado u otro de similares caracter sticas Para su seguridad la toma de...

Page 8: ...los d as feriados La duraci n m xima est controlada por el par metro MdF mientras que el par metro P2P habilita la segunda sonda fin de deshielo a temperatura o queda deshabilitada fin de deshielo a...

Page 9: ...FORMA MANUAL 1 Mantenga presionadas las teclas o y n durante algunos segundos hasta que aparezca el mensaje POF intermitente 2 Llegados a este punto el teclado ha quedado bloqueado solo se puede ver e...

Page 10: ...del set point de las alarmas de temperatura y de la activaci n de los ventiladores ALd Retardo de la alarma de temperatura 0 255 min intervalo de tiempo entre la detecci n de una alarma de temperatur...

Page 11: ...igital invierte el estado del rel auxiliar 8 7 INVERSI N DE LA ACCI N DEL CONTROLADOR FR O CALIENTE i1F o i2F Htr Hasta que la entrada digital se activa se invierte la acci n del controlador de fr o a...

Page 12: ...ipci n Rango C F Nivel SET Set point LS US 5 0 rtC Men de visualizaci n Pr1 Hy Hist resis de regulaci n del compresor 0 1 25 5 C 1 255 F 2 0 Pr1 LS Set Point m nimo 50 C SET 58 F SET 50 0 Pr2 US Set P...

Page 13: ...Minutos actuales 0 59 rtc dAY d as de la semana actual Sun SAt rtc Hd1 Primer d a festivo semanal Sun SAt nu nu rtc Hd2 Segundo d a festivo semanal Sun SAt nu nu rtc ILE Horario di inicio del ciclo de...

Page 14: ...es contact with J P SELECTA s technical service Do not use the equipment in explosive flammable or corrosive atmospheres 2 Packing list Model 2000152 Shelves guides 2x 2000011 Shelves 2x 2000021 3 Tec...

Page 15: ...12 14 16h 12h Ambient 25 C Ambient 20 C Temperatura interior Ejemplo de la evoluci n de la temperatura a dos condiciones ambiente distintas desde que se produce el fallo de alimentaci n OFF 4 Equipme...

Page 16: ...ttp www grupo selecta com Unique on the market technology for storing cooling energy The high in sulation capacity of its casing allows the chamber to maintain internal tem peratures for periods of mo...

Page 17: ...ator with a cloth and a cleaner or a similar solution Do not use aggressive solvents 5 5 Warranty This product is guaranteed for one year It does not cover damages caused by an incorrect use or causes...

Page 18: ...at the rear part 6 2 Connection to the mains Plug the equipment to a near socket suitable for the equipment power Use the connection cable supplied or a similar one For your safety the equipment must...

Page 19: ...ORATOR FANS The fan control mode is selected by means of the FnC parameter FnC C_n fans will switch ON and OFF with the compressor and not run during defrost FnC o_n fans will run even if the compress...

Page 20: ...p pressed together for more than 3s the o and n keys till the Pon message will be displayed 6 9 THE CONTINUOUS CYCLE When defrost is not in progress it can be activated by holding the o key pressed fo...

Page 21: ...bLL Compressor off with low temperature alarm of condenser n no compressor keeps on working Y yes compressor is switched off till the alarm is present in any case regulation restarts after AC time at...

Page 22: ...imum current allowed for all the loads is 20A 12 1 PROBE CONNECTION The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration It is recommended to place th...

Page 23: ...ary relay operating during defrost n y n Pr2 ALP Alarm probe selection nP P1 P2 P3 P4 P1 Pr2 ALc Temperat alarms configuration rE related to set Ab absolute Ab Pr2 ALU MAXIMUM temperature alarm Set 11...

Page 24: ...MANUAL CODE 80412 REV 0 03 2021 Page 24 J P SELECTA s a u Autov a A 2 Km 585 1 Abrera 08630 Barcelona Espa a Tel 34 937 700 877 Fax 34 937 702 362 e mail selecta jpselecta es website http www grupo s...

Reviews: