INSTRUCTION MANUAL
CODE 80412 REV 0
03/2021
Page: 20
J
.P. SELECTA s.a.u.
Autovía A-2 Km 585.1 Abrera 08630 (Barcelona) España
Tel 34 937 700 877 Fax 34 937 702 362
e-mail: [email protected] - website: http://www.grupo-selecta.com
1592036010 XW70LH GB r1.0 14.02.2014.docx
XW70LH
2/5
LED MODE
FUNCTION
ON
Defrost enabled
Flashing Drip time in progress
ON
Fans enabled
Flashing Fans delay after defrost in progress.
ON
An alarm is occurring
ON
Continuous cycle is running
ECO
ON
Energy saving enabled
ON
Light on
ON
Auxiliary relay on
°C/°F
ON
Measurement unit
°C/°F
Flashing Programming phase
5.
MAX & MIN TEMPERATURE MEMORIZATION
5.1
HOW TO SEE THE MIN TEMPERATURE
1.
Press and release the
n
key.
2.
The “Lo” message will be displayed followed by the minimum temperature recorded.
3.
By pressing the
n
key again or by waiting 5s the normal display will be restored.
5.2
HOW TO SEE THE MAX TEMPERATURE
1.
Press and release the
o
key.
2.
The “Hi” message will be displayed followed by the maximum temperature recorded.
3.
By pressing the
o
key again or by waiting 5s the normal display will be restored.
5.3
HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED
1.
Hold press the SET key for more than 3s, while the max. or min temperature is displayed. (rSt
message will be displayed)
2.
To confirm the operation the “rSt” message starts blinking and the normal temperature will be
displayed.
6.
MAIN FUNCTIONS
6.1
TO SET THE CURRENT TIME AND DAY (ONLY FOR INSTRUMENTS
WITH RTC)
When the instrument is switched on, it’s necessary to program the time and day.
1.
Enter the Pr1 programming menu, by pushing the SET +
n
keys for 3s.
2.
The rtc parameter is displayed. Push the SET key to enter the real time clock menu.
3.
The Hur (hour) parameter is displayed.
4.
Push the SET and set current hour by the UP and Down keys, then push SET to
confirm the value..
5.
Repeat the same operations on the Min (minutes) and dAy (day) parameters.
To exit:
Push SET+UP keys or wait for 15 sec without pushing any keys.
6.2
HOW TO SEE THE SET POINT
1.
Push and immediately release the
SET
key: the display will show the Set
point value;
2.
Push and immediately release the
SET
key or wait for 5 seconds to
display the probe value again.
6.3
HOW TO CHANGE THE SETPOINT
1.
Push the
SET
key for more than 2 seconds to change the Set point value;
2.
The value of the set point will be displayed and the “
°C” or “°F”
LED starts blinking;
3.
To change the Set value push the
o
or
n
arrows within 10s.
4.
To memorise the new set point value push the
SET
key again or wait 10s.
6.4
HOW TO START A MANUAL DEFROST
Push the
DEF
key for more than 2 seconds and a manual defrost will start.
6.5
HOW TO CHANGE A PARAMETER VALUE
To change the parameter’s value operate as follows:
1.
Enter the Programming mode by pressing the
Set
+
n
keys for 3s (the “
°C” or “°F”
LED starts
blinking).
2.
Select the required parameter. Press the “
SET
” key to display its value
3.
Use “
UP
” or “
DOWN
” to change its value.
4.
Press “
SET
” to store the new value and move to the following parameter.
To exit
: Press
SET + UP
or wait 15s without pressing a key.
NOTE
: the set value is stored even when the procedure is exited by waiting the time-out to expire.
6.6
THE HIDDEN MENU
The hidden menu Includes all the parameters of the instrument.
6.6.1 HOW TO ENTER THE HIDDEN MENU
1.
Enter the Programming mode by pressing the
Set
+
n
keys for 3s (the “
°C” or “°F”
LED starts
blinking).
2.
Released the keys, then push again the Set+
n
keys for more than 7s. The Pr2 label will be
displayed immediately followed from the HY parameter.
NOW YOU ARE IN THE HIDDEN MENU.
3.
Select the required parameter.
4.
Press the “
SET
” key to display its value
5.
Use
o
or
n
to change its value.
6.
Press “
SET
” to store the new value and move to the following parameter.
To exit
: Press
SET +
o
or wait 15s without pressing a key.
NOTE1:
if none parameter is present in Pr1, after 3s the “noP” message is displayed. Keep the keys
pushed till the Pr2 message is displayed.
NOTE2
: the set value is stored even when the procedure is exited by waiting the time-out to expire.
6.6.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE
FIRST LEVEL AND VICEVERSA.
Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user
level) by pressing
“SET +
n
”
.
In HIDDEN MENU when a parameter is present in First Level the decimal point is on.
6.7
HOW TO LOCK THE KEYBOARD
1.
Keep pressed for more than 3 s the
UP
+
DOWN
keys.
2.
The “POF” message will be displayed and the keyboard will be locked. At this point it will be
possible only to see the set point or the MAX o Min temperature stored
3.
If a key is pressed more than 3s the “POF” message will be displayed.
6.8
TO UNLOCK THE KEYBOARD
Keep pressed together for more than 3s the
o
and
n
keys, till the
“Pon”
message will be
displayed.
6.9
THE CONTINUOUS CYCLE
When defrost is not in progress, it can be activated by holding the “
o
” key pressed for about 3
seconds. The compressor operates to maintain the “
ccS
” set point for the time set through the “
CCt
”
parameter. The cycle can be terminated before the end of the set time using the same activation key
“
o
” for 3 seconds.
6.10
THE ON/OFF FUNCTION
With “
onF = oFF
”, pushing the
ON/OFF
key, the instrument is switched off. The
“OFF”
message is displayed. In this configuration, the regulation is disabled.
To switch the instrument on, push again the ON/OFF key.
WARNING: Loads connected to the normally closed contacts of the relays are always
supplied and under voltage, even if the instrument is in stand by mode.
7.
PARAMETERS
rtc Real time clock menu (only for controller with RTC):
to set the time and date and defrost
start time.
REGULATION
Hy Differential
: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point. Compressor Cut IN is
Set Point + differential (Hy). Compressor Cut OUT is when the temperature reaches the set
point.
LS Minimum set point:
(- 50°C÷SET/-58°F÷SET): Sets the minimum value for the set point.
US Maximum set point:
(SET÷110°C/ SET÷230°F). Set the maximum value for set point.
Ot Thermostat probe calibration
: (-12.0÷12.0°C; -120÷120°F) allows to adjust possible offset of
the thermostat probe.
P2P Evaporator probe presence: n
= not present: the defrost stops by time;
y=
present: the defrost
stops by temperature.
OE Evaporator probe calibration:
(-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of
the evaporator probe.
P3P Third probe presence (P3): n
= not present:, the terminals 13-14 operate as digital input.;
y=
present:, the terminals 13-14 operate as third probe.
O3 Third probe calibration (P3):
(-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of
the third probe.
P4P Fourth probe presence
: (n = Not present; y = present).
o4 Fourth probe calibration
: (-12.0
12.0°C) allows to adjust possible offset of the fourth probe.
OdS Outputs activation delay at start up:
(0÷255min) This function is enabled at the initial start up
of the instrument and inhibits any output activation for the period of time set in the parameter.
AC Anti-short cycle delay
: (0÷50 min) minimum interval between the compressor stop and the
following restart.
AC1 2
nd
compressor delay at start up
(0÷255s) Used only with oA3 or oA4 = cP2 Time interval
between the switching on of the first compressor and the second one.
rtr Percentage of the second and first probe for regulation (0÷100; 100 = P1, 0 = P2 ):
it
allows to set the regulation according to the percentage of the first and second probe, as for the
following formula (rtr(P1-P2)/100 + P2).
CCt Compressor ON time during continuous cycle:
(0.0÷24.0h; res. 10min) Allows to set the
length of the continuous cycle: compressor stays on without interruption for the CCt time. Can be
used, for instance, when the room is filled with new products.
CCS Set point for continuous cycle:
(-50÷150°C) it sets the set point used during the continuous
cycle.
COn Compressor ON time with faulty probe:
(0÷255 min) time during which the compressor is
active in case of faulty thermostat probe. With COn=0 compressor is always OFF.
COF Compressor OFF time with faulty probe:
(0÷255 min) time during which the compressor is
OFF in case of faulty thermostat probe. With COF=0 compressor is always active.
DISPLAY
CF Temperature measurement unit:
°C=
Celsius;
°F
=Fahrenheit. WARNING: When the
measurement unit is changed the SET point and the values of the parameters Hy, LS, US, Ot,
ALU and ALL have to be checked and modified if necessary).
rES Resolution (for °C)
: (in = 1°C; dE = 0.1 °C) allows decimal point display.
Lod Instrument display
: (P1; P2, P3, P4, SET, dtr): it selects which probe is displayed by the
instrument:
P1
= Thermostat probe;
P2
= Evaporator probe;
P3
= Third probe(only for model
with this option enabled);
P4
= Fourth probe,
SET
= set point;
dtr
= percentage of visualization.
rEd X- REP display (
optional
)
: (P1; P2, P3, P4, SET, dtr): it selects which probe is displayed by
X- REP:
P1
= Thermostat probe;
P2
= Evaporator probe;
P3
= Third probe(only for model with
this option enabled);
P4
= Fourth probe,
SET
= set point;
dtr
= percentage of visualization.
dLy Display delay:
(0 ÷20.0m; resul. 10s) when the temperature increases, the display is updated
of 1 °C/1°F after this time.
dtr Percentage of the second and first probe for visualization when Lod = dtr (0÷100; 100 =
P1, 0 = P2 ): if Lod = dtr
it allows to set the visualization according to the percentage of the
first and second probe, as for the following formula (dtr(P1-P2)/100 + P2).
DEFROST
EdF Defrost mode (only for controller with RTC):
rtc
=
Real Time Clock mode
. Defrost time follows
Ld1÷Ld6
parameters on workdays and
Sd1÷Sd6
on holidays.
in
=
interval mode
. The defrost starts when the time “
idF
” is expired.
tdF Defrost type
: EL = electrical heater; in = hot gas