Digital Trades Clock Operating Instructions

Change Button

 

Sets Hours, Minutes
 and Trade Times 
 

 

 

 

 

Programme Button

 

Used to select the clock time and the 4 
On/Off programmed times and to review 
them once set

 

iii. Press the 

Program Button

 once 

 clock is now 

 

set and display shows ready for the first ON 

 

programme time with ON and the hours digit 

 

flashing.

 

 

3. To Set Programme ON/OFF Times

 

(After clock setting)

 

 

Program 1 ON time

 

i. Press 

Change Button

 to advance the hour setting.

 

 

ii. Press the 

Program Button

 once to select the 

 

minute time 

 display shows minute digits and ON 

 

Flashing. Press 

Change Button 

to advance the 

 

minute setting. 

Note:

 16 hours shown as example

 

of hours set).

 

 

iii. Press the 

Program Button

 once – the first ON 

 

time is now set and the display will show ready for 

 

the first OFF programme time.

 

 

iv. Now set the hours and minutes as before.

 

 

v. Repeat steps I to iv to set the remainder of the 3 ON /OFF times as 
required. 

Note: 

Any unused ON/OFF programs should be skipped until 

the display shows normal operating mode. Do not program ‘0’s into 
unused programs.

 

 

4. Program Review

 

To fast review the set program or for quick exit to normal operating
mode press and hold the 

Program Button

 

5. Initiating Programme Mode

 

This can be initiated at any time during the normal operating mode. Press 

Program Button

 and the clock, hours and minutes symbols on the display 

will flash – this is the review mode. If any change to the programmes is 
required press the 

Change Button

 to initiate programme mode and then 

follow steps 2 and 3.

 

 

6. Cancelling Programmes

 

Any ON/OFF programme can be cancelled by 

 

clearing its ON and OFF time. Follow step 5 and 

 

when into the ON/OFF programme to be cancelled 

 

press the 

Change Button

 until the digits show 

 then press the 

Program 

Button

 to clear the programme. The display will show the hour and minute 

digits and ON or OFF flashing.

 

 

Self Cancelling Override

 

To change the output status from ON to OFF or vice versa during normal 
operation press the 

Change Button

. The output status will change and 

indicate override is in operation by flashing.

 

Programming 

 

Only two setting buttons are required, 

 and 

Change

Program 

In normal use the 

Change Button

 is used to switch ON or OFF 

overriding the time switch until the next program ON or OFF 
time. During programming the 

 Change Button

  is used to set the 

Hours and Minutes. The 

Program Button

  is only used when setting 

or adjusting the clock

   Time or the 4 programmed ON/OFF times, 

although it can be used to review the ON/OFF times once they 
have been set.. Each time the 

 

Program Button

  is pressed the 

display will flash either the hours or minutes in turn, starting with 
the clock, then the first  

  ON time, first OFF time, second ON time 

etc. 
Wherever the hours or minutes are flashing they maybe set using 
the 

Change Button

. Once the 

Program Button

 is pressed again to 

proceed to the next stage. 

 

Normal Operating Mode

 

In normal operation the time clock will display the 

 

correct time with the colon flashing. The output 

 

status will be shown be either ON or OFF on the 

 

display.

    

 

1. To Reset Display Mode

 

To clear programme from memory and reset the 

 

time controller press and hold down both buttons 

 

un

til the display goes blank. Release buttons and 

 

the display will fill with its complete range of 

 

characters and then clear to show the clock and hour digit flashing.

 

Programming Sequence

 

Setting Clock

 

 

 

 

Programme 1 ON

 

 

 

Programme 3 ON

 

Programme 1 OFF

 

 

 

Programme 3 OFF

 

Programme 2 ON

 

 

 

Programme 4 ON

 

Programme 2 OFF

 

 

 

Programme 4 OFF

 

 

 

 

 

Operating Mode

 

Note:

 

Button pauses greater than 0ne minute during programming will result in 
automatic return to the operating mode.

 

 

2. Setting Clock (after reset)

 

i. Hour setting 

 Press the 

Change Button

 to 

 

advance the hour setting. 

Note:

 For rapid hour 

 

selections press and hold the 

Change Button.

 

 

ii. Minute Setting 

 Press the 

Program Button

 once 

 

to select the minutes 

 display shows clock symbol 

 

and minute digits  flashing. Press the 

Change 

 

Button

 to advance the minutes setting. 

 

Note:

 For rapid minute selection press and hold the 

Change Button

 

(16 hours shown as example of hours set).

 

 

Output Status 

Showing Trades 
ON or OFF 

- 23 -

Digital Audio 

Installation Manual

Digital Audio

Revision 1.09 Date: 05/12/2011

Summary of Contents for Audio 16

Page 1: ...ctLine Selectine Select Manufacturing Limited Unit H1 The Seedbed Centre Wyncolls Road Severalls Business Park Colchester Essex CO4 9HT Telephone 44 0 1206 855800 Facsimile 44 0 1206 855801 E mail sal...

Page 2: ...e Full Facility Auxiliary BST GMT Clock Programming On Board Digital Clock Programming Controller Switch Settings Example Controller Switch Settings Controller Programming Instructions System Connecti...

Page 3: ...Digital Audio Systems 2 Digital Audio Installation Manual Digital Audio Revision 1 09 Date 05 12 2011...

Page 4: ...Type Cable Lock Release D 8 Wire 4 Pair CW1308 0 5mm dia Multipair Cable Minimum C 2 Wire 1 Pair CW1308 0 5mm dia Multipair Cable Minimum H 2 Wire 1 Pair 2 5mm Mains Type Cable 50V Power Rail PANEL 1...

Page 5: ...14 LINE 7 LINE 15 LINE 8 LINE 16 RESET A D H D C Battery 2 Amp Fuses Telephone Handset A D H Digital Interface Strobe Sounder C PANEL 1 PANEL 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10...

Page 6: ...4A Digital Audio Installation Manual 230VAC to 50VAC Supply Fused Spur 50VAC Rail to a Controller Digital 50VAC Main Power Supply Overview AC2 5Amp Fuse AC1 Digital Audio Revision 1 09 Date 05 12 2011...

Page 7: ...tor Call Indicator Lock Released Indicator DC Lock Power Healthy Indicator 12V DC Lock Release Output N O N C Request to Exit Timed Door Monitoring Switch Request to Exit Timed Door Monitoring Switch...

Page 8: ...12V 24VAC DC Lock Supply Input 12V 24VAC DC Lock Supply Input 12V 24VAC DC Sub Entrance Panel 2 Buttons 3 4 5 6 7 8 1 2 9 10 11 12 13 14 15 16 1 C 2 6 9 PS PL DL 1 C 2 6 9 PS PL DL 1 C 2 6 9 PS PL DL...

Page 9: ...Indicator Display System Busy Indicator Display Request to Exit Timed TR 1 2 0 CC DML SBL RTE T AC Lock Power Indicator Mains Fail Indicator DC Lock Power Indicator MFL MFL Mains Fail Indicator Door M...

Page 10: ...a 12VAC DC Lock Output is required use LS1 LS2 with a secondary power Supply If a Volt free contact is required to trigger a PAC Controller RTE then remove both links and use LS1 SA for Normally Close...

Page 11: ...2 12V 0V SCN SIG CAM2 Lobby 12V 0V SCN SIG CAM1 Panel _ 1 2 Display BUSY FLAT CALLED TALK NOW ENTER Board Healthy Indicator Door Open Tone Control pcb 2024 Iss 3 With DDA requirements PAC Digital Entr...

Page 12: ...Speech Adjustment SML 2036 Building Interface card A G R T RS232 D C B RS475 RS232 Transmission Input Output RS485 Transmission Input Output Concierge Building Interface Card Multi Building wiring det...

Page 13: ...DATA SWITCH FUNCTION SWITCH FUNCTION SWITCH FUNCTION SWITCH FUNCTION SWITCH 1 2 3 4 5 FUNCTION SWITCH 1 1 3 3 4 4 5 5 6 6 7 7 8 8 2 2 DATA SWITCH DATA SWITCH Controller Controller Controller Controlle...

Page 14: ...5 digit engineering code has already been entered the Digital Panel will display EA1 alternating with the remaining 4 numbers i e EA1 2345 This can if required be deleted by pressing the CANCEL button...

Page 15: ...he system into erase mode Erase mode will be indicated by the Display initially reading E 000 and then following on with a count of 30 The system will not reset itself to default at 30 To initiate the...

Page 16: ...t the programming mode Note 1 When there is a need to edit or check an already programmed flat on the system use the following procedure Enter Controller number i e 2 Enter Line Output number i e 03 a...

Page 17: ...h Door Monitoring Switch Data Select Data Select 0 Volts Positive External Alarm Strobe Sounder Negative External Alarm Strobe Sounder Fail Secure Lock Release Output Fail Safe Lock Release Output Loc...

Page 18: ...n of White Orange of White 2 5mm Mains Type Cable 2 5 Mains Type Cable Brown of White White of Brown Blue of White White of Blue Orange of White Green of White Digital Entrance Panel Board 12VDC Outpu...

Page 19: ...15 CA 1 2 6 10 9 Standard call input connection Telephone Handset Sounder Red Black Digital Audio Installation Manual AT PID Telephone Privacy Privacy On Indicator and Door Monitoring Indicator wirin...

Page 20: ...reen Common 1 Normally Open 4 Normally Closed 2 Emergency Override Switch For Fail Secure SE Lock Releases wire N O to RTE T only For Fail Safe SA Lock Releases SA SE LC LS2 LS RTE T RTE T DMS DMS PAN...

Page 21: ...that a 1N4007 diode is fitted at the lock release if you are using the System Controller for lock release power This is to protect the System Controller against back EMF If the locks are being powere...

Page 22: ...E 12V 12V 0V Sw1 Prog Sw2 Up Load Sw3 Down Load LS2 PAC PAC LS1 LC SA SE Stb Stb 0V CTS SD DMS DMS RTE T RTE T Vout 0V SCN Flat Programming Button Board Healthy Indicator 12V 0V SCN SIG CAM2 Lobby 12V...

Page 23: ...elay 1 Reader1 V LED RTE DC SIG GND N C COM N O L L PAC EASIKEY 1000 PAC DDA READER DO CLK 0V VCA D1 SIG 10 5 28V 1 2 VE VE 12V 12V 0V Sw1 Prog Sw2 Up Load Sw3 Down Load LS2 PAC PAC LS1 LC SA SE Stb S...

Page 24: ...rades Detail Trades Button Trades Button Request To Exit Timed Request To Exit Timed Lock Release Detail Lock Common DC Fail Safe DC Fail Secure DC Fail Secure DC Fail Secure DC PAC Detail See page 18...

Page 25: ...for Entrance Panel 2 TELEPHONE RING TIME FROM THE ENTRANCE PANEL Use the FUNCTION switches to select Entrance Panel 1 and the DATA switches to select the number of seconds for the ringing time duratio...

Page 26: ...P P 1 0 0 E 1 0 0 0 0 0 1 0 0 1 0 0 0 0 1 0 S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S 1 0 0 0 0 1 1 0 0 1 0 0 0 1 1 0 1 0 0 0 0 0 0 1 0 1 0 0 0 0...

Page 27: ...ion Time Entrance Panel 2 15 M inutes 4 0 1 0 0 0 0 1 1 1 1 1 1 1 1 0 0 Note 1 ON X Any Position 1 If an Extension Sounder or Strobe are required set Data switch 8 to ON 0 OFF S Seconds 2 Do not set a...

Page 28: ...output status will change and indicate override is in operation by flashing Programming Only two setting buttons are required and Change Program In normal usethe Change Buttonis used to switch ON or...

Page 29: ...er equals the current year i e 1 99 Note It is important for proper GMT BST operation that the correct date is entered When the display shows the correct date Press the PROG Yellow button 06 03 02 17...

Page 30: ...ct Switch Contact System Wiring Colour Codes Controllers to Functional and Landing Entrance Panels Controller 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 CC TR TR Note The CC connection on the Controller t...

Page 31: ...he first colour stated above The banding is the second colour stated above Therefore a wire stated as Black of Slate would be a Black main colour with a Slate banding Lock Release Fail Safe DC Lock Re...

Page 32: ...h of the above switches contains 8 ON and 8 OFF positions that can be selected in various combinations to achieve varying system functions Available Functions Description Default settings for all func...

Page 33: ...irm the door is being released for your visitor Door Open Warning Once the Main Entrance door has been opened the RED Door Open indicator will stop flashing and will stay illuminated until the Entranc...

Page 34: ...Name Commissioning Engineer Installer Name Site Address Telephone No Controller No Comments SELECT General System Comments Please use reverse Trades On On On On Off Off Off Off Trades settings Flat Nu...

Reviews: