background image

ATSEL HMI User Manual

                              

ATSEL HMI User

Manual

(Version

2.02)

Selec Controls Pvt. Ltd.

Summary of Contents for SP112 Series

Page 1: ...ATSEL HMI User Manual ATSEL HMI User Manual Version 2 02 Selec Controls Pvt Ltd ...

Page 2: ... Animation Design 13 Recipe 15 Data Transmission 17 Alarm 18 Multi Language 22 History Data Record 24 User Encryption 29 Update Program by U Flash 34 QR Code 35 One HMI Multi PLCs 37 Time Setting 40 Installment 42 System Configuration 49 Internal Register of System 51 Printer Settings 54 ...

Page 3: ... ATSEL HMI User Manual Installation Dimension for installation opening SP112 series of HMI SP112 GT70 S CE and SP112 GT70 ET CE SP112 192 138mm Interface SP112 interface Cable layout back side of the HMI ...

Page 4: ...t for long distance communication Remark the pluggable terminal COM1 and the DB9 COM1 share the same RS485 series port thus they can t be used at the same time HMI DB9 Male Pluggable terminals picture interface PIN Pin Definition interface PIN Pin definition remark picture SP112 COM2 1 COM1 1 R 120Ω resistance 2 RS232 RXD 2 A RS485 A 3 RS232 TXD 3 B RS485 B 4 4 PE Shielded ground 5 GND remark The ...

Page 5: ...on brief Our HMI support many kinds of communication protocols such as PPI MPI Modbus smart S7 Mitsubishi Panasonnic Omron etc Series communication COM1 RS485 SiemensS7 200 smart CPU SiemensS7 300 CPU All Modbus Devices COM2 RS232 Mitsubishi Fx1 Fx2N Fx3U ...

Page 6: ...unning stop Connect with PLC SP112 Siemens SP112 Mitsubishi Fx1N Fx2N DB9 SP112 Panasonic Fp SP112 Mitsubishi Fx2N 3U 8 pin circular hole SP112 Omron CP PPI MPI SP112 7 485 8 485 3 485 8 485 Fx1N 2N SP112 2 RX 3 TX 5 GND 2 TXD 1 RXD 3 GND Fp SP112 2 RX 3 TX 5 GND 2 TXD 3 RXD 1 GND Fx3U SP112 SG Shield 2 RX 3 TX SG Shield 4 TX 1 RX 5 GND 2 RX 7 TX 500Ω 500Ω Cp SP112 2 RX 3 TX 5 GND 2 TXD 3 RXD 9 GN...

Page 7: ...s address SMB dddd 0 4095 word special bit memory SMB0 SMB29 read only each word occupies one byte address SMW dddd 0 4094 word special bit memory SMW0 SMW28 read only each word occupies two bytes address SMD dddd 0 4092 word special bit memory SMD0 SMD26 read only each word occupies two bytes address VB ddddd 0 10239 Byte variable memory VW ddddd 0 10238 word variable memory each word occupies tw...

Page 8: ...6 bit what be input register Read only 4x ddddd 1 65536 word the word with 16 bit what be output register 3x_double ddddd 1 65535 Double word input register high low 16bits upside down with 3x double word read only 4x_double ddddd 1 65535 Double word output register high low 16bits upside down with 3x double word Note d decimal the input range is 0 9 o octal and the input range is 0 7 DDD block nu...

Page 9: ...D 255 0 C bit DDD 255 0 D word DDDD 7999 0 SD word DDDD 8255 8000 TV word DDD 255 0 CV word DDD 199 0 32CV word DDD 255 200 Fx3U Register Name bit word Address format Max address Mini address X bit OOO 377 0 Y bit OOO 377 0 M bit DDDD 7679 0 S bit DDD 4095 0 SM bit DDDD 8255 8000 T bit DDD 255 0 C bit DDD 255 0 D word DDDD 7999 0 SD word DDDD 8255 8000 TV word DDD 255 0 CV word DDD 199 0 32CV word...

Page 10: ... 0 SV word DDDD 9999 0 EV word DDDD 9999 0 WX word DDDD 9999 0 WY word DDDD 9999 0 WR word DDDD 9999 0 WL word DDDD 9999 0 IX word D 13 0 IY word D 13 0 ID word D 32 0 6 Omron CP1H Register Name bit word Address format Max address Mini address CIO_bit bit dddd DD 6143 15 0 0 LR_bit bit ddd DD 199 15 0 0 HR_bit bit dddd DD 1535 15 0 0 AR_bit bit ddd DD 959 15 448 0 DM_bit bit ddddd DD 32767 15 0 0 ...

Page 11: ...3 0 WR word DDD 199 0 HR word DDDD 1535 0 AR word DDD 959 448 TC word DDD 127 0 DM word DDDDD 32767 0 7 Address searching function Click the search function of edition or shortcut key crtl F then the address search menu is popped up which can search the bit or word of the internal address and external connection address or the current scene and all the scenes and supports the address replacement a...

Page 12: ...10 ATSEL HMI User Manual 2 PPI communication parameters setting as showing in below chart 3 Put a few bit buttons onto the screen and setting the written addresses of these bit buttons Q0 0 Q0 1 ...

Page 13: ...S7 200 program software is shown as the following diagram 5 Connect the HMI to PLC through 485 communication cable and power them together then download the corresponding project to HMI When click the components on the screen the corresponding PLC output points will be lighten ...

Page 14: ... or shortcut key ctrl F to pop up the search interface You can search bit and word in the current scene or all of the scenes At the same time you can replace the selected addresses double click the corresponding addresses to pop up corresponding control option of corresponding scene ...

Page 15: ...isplayed by the bar graph Flow Block Flow Block is used to simulate in animated pictures the liquid flow status in pipeline Whether a flow block is flowing is determined by the status of the trigger when the trigger is 1 the flow block is flowing when the trigger is 0 the flow block is static The flowing speed is specified by user Dynamic Rectangle and Dynamic Circle Their function is similar whic...

Page 16: ...of Graphic Components select a liquid storage tank from Gallery and drag into a Bar graph of Object components to cover the liquid area of tank 3 Rotation motor First put a picture and set as display when bit control value being 0 put a similar GIF component and set as display when bit control value being 1 These two components must be set the same size and same position Use alignment function Or ...

Page 17: ...ing production process For example a bread factory produces bread there will be a basic ingredient recipe this recipe will list all ingredient lists that used for producing bread for example water flour sugar egg sesame oil etc Besides also list all choosable ingredient lists for example fruits kernel chocolate chips etc These choosable ingredient can be added to basic recipe to produce various br...

Page 18: ...e key operation 2 How to achievement Click recipe control add a new recipe group and set ingredients number of recipe each recipe contains different ingredients proportion and then save the recipe Add the corresponding components and set corresponding variables to project scene and group index is modify Internal Register LW60802 can achieve switch over of recipe ...

Page 19: ...al device and HMI or between device and device Click Data Transmission in Project Manager to pop up the data transmission list as below 1 Click Add you can add data transmission At present maximum number entries is 100 Triggered type is interval trigger and minimum time unit is 200ms the data types which can be transfered is bit word double word and the maximum transmission data size by each trigg...

Page 20: ...peration of the device the system will make warning and record the time and content of the corresponding events The alarm is used to set the alarm information Only the alarm is configured the alarm control and the dynamic alarm bar can be used normally 1 Set the alarm information firstly set the trigger condition 2 Record the real time alarm to show the real time alarm data alarm scrollbar 3 Syste...

Page 21: ...19 ATSEL HMI User Manual 4 Clear alarm voice the alarm sound can be set on off by the function button Example A Set the real time alarm 1 Double click Alarm icon to open Alarm Setting in software window ...

Page 22: ...m event in the alarm setting and change the trigger condition 3 Add an alarm control and change the corresponding display parameters 4 When the corresponding alarm event is triggered the Alarm Control will display the alarm time date and content etc ...

Page 23: ...on the scene 6 When setting the overall alarm the alarm information will be displayed at the corresponding position of all pages B Historical alarm setting 1 Query historical alarm Query the historical record triggered time faulty information and fault clearance time etc Insert a function button which set to display alarm data Then well done ...

Page 24: ...n download the historical data to the U disk by the function button Select the Download History Alarm Data in the function buttons Multilingual Function introduction The function realizes the multilingual setting Double click language settings and pop up the following dialog Current language the current language used for text Language quantity 8 languages in total ...

Page 25: ...sh 2 Project setting Create a new project put the corresponding controls at scene and set the relevant alarm make these all be displayed in Hindi Then add two function buttons at the scene and set one for Hindi and another for English As follows Click the language setting in the left project window select 2 of the language and translate for Language1 After the translation is completed click confir...

Page 26: ... the corresponding historical data record table and draws the historical curve trend map to the data Data can also be downloaded to the U disk and we can read the data of the U disk through the computer or other devices historical data records can not show changes in data records by off line simulation it is necessary to download to the touch screen to view the related records data Historical data...

Page 27: ...op up window as below Name user can change the name displayed in project manager accordingly only for letters or numbers Read address to read the starting address of the data Sampling length the number of data to read from memory at most is 16 The total number of sampling is the number of data extracted which supports 100000 articles at most Sampling mode timing sampling and reading data according...

Page 28: ...riable is triggered the relevant function 3 Adding the address variables that need to record the historical data and the way of data sampling the number of individual historical data variables is up to 8 supporting the discrete address variables There are three ways of sampling historical data including time sampling trigger sampling and timing sampling each historical data collector has a maximum...

Page 29: ... add historical data displays to the software scene and set up historical data items to display After the device operating on HMI it will display the change of the corresponding component address variable value and data will be saved when power off 5 When adding historical trend picture at scene set the corresponding attribute of the XY axis interface including the time setting of the X axis the n...

Page 30: ...ding time range or sampling time 6 Historical data query We can query historical data and record information according time Just pull a function button and select the query history data on the function button 7 Download the historical data Download the collected historical data to the USB disk in CSV file format It can be opened directly by Excel Just pull a function button and select the query hi...

Page 31: ...user level which is in advanced pages to use For example the user level control in the advanced page setting the bit button is D the D level of the Uni001 user in the user password setting is N and the D level of the Uni002 user is Y then the Uni001 user can not touch the use button and the Uni002 user can touch the use button Users can set up the upload password here When setting up the password ...

Page 32: ...login it displays the current user name When no user login it shows that the user does not exist as NULL Add user This function is used to add users set up their passwords and corresponding permissions and its authority is only owned by administrator Clicking this control to add a user enter a new user name in the account enter his password and enter the highest permission password of the administ...

Page 33: ...right of the current users and re assign the corresponding permissions after entering the administrator password Note the administrator s password can be logged in any valid account Example 1 Create the relevant user name user password and the corresponding user rights can set the highest authority the highest authority can open all functional rights when the password is allowed to upload in the u...

Page 34: ...3 A control is encrypted Visibility that is the user who has the relevant right can log in and touch 4 The Supreme Authority Operation is that the task user enters the corresponding password and then can operate on all controls ...

Page 35: ...nction under project window can protect users rights opening the file need password 7 It supports show user add user delete user modify password modify level In the advanced components drag into the new user the related interface is automatically generated where the rights of the corresponding user can be added the administrator password is the highest authority password such as the above figure s...

Page 36: ...ht select save path and store it in the U disk Click confirm Check the configuration again click on the right select save path and store it in the U disk Click confirm Note firmware is the version of the upper computer software It is recommended to save it into the U disk to ensure that the version matches the configuration U disk max supports up to 8 different configuration projects A project nee...

Page 37: ...ollowing is the firmware Click the firmware and the two red buttons that need to be updated and then click Upgrade to start updating program and firmware After the update pop up Update all success 8 Pull out the U disk and restart the touch screen to complete the U disk update QR Code Function In application some information needs to be converted to QR code on the touch screen In ATSEL we can achi...

Page 38: ... the specified address to edit box when the check box is checked Note the two dimensional code generator only displays the default two dimensional code in the offline simulation and online simulation and does not generate a new two dimensional code It generates a new two dimensional code on the screen only Example 1 Two dimensional code is the fixed information Select two dimensional code in the a...

Page 39: ... master HMI slave1 HMI slave2 Communication protocol which extension mode supported PPI MPI MODBUS Parameter settings at extension mode baud rate slave number data bits parity bits and other system parameters Master HMI number is not recommended to be broadcast address or same as the slave number which cause the communication failure Example One panel with multi devices PPI On ATSEL double click t...

Page 40: ...On Atsel double click to open communication port settings of Link1 and change the address mode at extended mode and save it in parameter interface Add corresponding components of two PLC slave address at screen 1 is PLC Slave1 2 is PLC slave2 PLC program as below ...

Page 41: ...ystem time information to the corresponding PLC address The data type and length are defaults The default value of data type is 16 bit BCD and the default value of length is 7 Write address write the system time to the corresponding PLC address The start up model Time interval set the time interval as a time unit and write the system time information to the corresponding PLC address circularly Tri...

Page 42: ...nformation in the corresponding PLC address Trigger when the trigger address is 1 read the information in the corresponding PLC address Note the range of the input year is 1970 2037 Example 1 Set the system time on the touch screen Achieve by the function button to set system time function or to enter the touch screen system setting interface for system time settings 2 Download system time to HMI ...

Page 43: ...s write PLC once per second B Set 7 numeric display or numeric input display in the screen and set their address as VW100 to VW112 respectively which as year month day time minute second week correspondingly C Monitor corresponding VM100 to VM112 address at PLC and adjust the corresponding format to hexadecimal to display the time PLC has a real time clock and updates the clock through one bit ...

Page 44: ...is VB10 VB17 D Add a bit button the address is M0 0 set it as the trigger switch of the clock Pay at installments Function introduction The installment function is the user is able to use HMI within a certain period if the time exceeds the time limit then HMI will jump to the specified screen of the user so that the HMI cannot continue to use it If you want to reuse the HMI the user has to unlock ...

Page 45: ...rd level multilevel password level can share a deadline protection screen Password password required to be completed at the current password level When the date and time of the corresponding password level arrive automatically pop up deadline unlock screen after input the password then withdraw from the time frame and return to the original picture Otherwise continue to stay in the current deadlin...

Page 46: ...the download time of the project That is there is still 1 days before the expiration date if modify time at this moment will still be triggered on the second day 6 User expiration pop up When create a new deadline protection there will be two blanks in the screen password input is the expiration pop up window When the deadline reaches the window is popped up automatically and the password of the r...

Page 47: ...line screen to remind the client trial time has arrived and should pay the related equipment When a part of the money is paid the next level password is provided until the next deadline is reached to pop up again When the customer provides all the payment give the highest password permissions and unlock all renewals 2 Sample operation A In the left side of the project window click the deadline pro...

Page 48: ...ow screen can be user defined edited C To save the above two steps then complete the set up of installment payment Ladder chart Function introduction Support for ladder logic control in ATSEL software The associated external or internal address is corresponding to the address dedicated to the ladder diagram and is programmed by the special address of the ladder diagram The instruction contains the...

Page 49: ...ructions input address information then the editing screen shows the corresponding ladder diagram instructions The editing method is basically same as PLC And there are common instructions on the ladder menu which can be directly clicked insert line to insert structure vertical line delete structure vertical line clearing delete on off the relevant address import ladder diagram export ladder diagr...

Page 50: ...s 4 inputs 3 outputs and 1 multi state display word address Add notices of the address name Remarks The address of the ladder diagram can be numbered arbitrary not relevant with bit word or double word Register LI and LQ no need to attention actual input and output For example V0 0 can be relevant LQ10 B Ladder diagram Programming is based on ladder address During programming click to display the ...

Page 51: ...ng property interface The hmi system can be set up and the system storage information can be viewed System settings in the system settings you can view the current system information including the current application software version number version type and the IP address of the machine if no Ethernet shows no support can adjust the backlight brightness through a scroll bar in calibration the touc...

Page 52: ...ponding update file to click the update after the update is completed click restart and pull out the U disk to complete the U disk update Internal register of the system Function introduction The internal registers of the system mainly display and control some special functions by the system address which is convenient for users to trigger relevant system operation ...

Page 53: ...finished then OFF W R LB60116 Recipe upload instruction when recipe is in read to the device it is ON upload finished then OFF W R LB60126 Save the instalment password which set deadline protection W R LB60900 Level A automatic reset W R LB60901 Level B automatic reset W R LB60902 Level C automatic reset W R LB60903 Level D automatic reset W R LB60904 Level E automatic reset W R LB60905 Level F au...

Page 54: ...983 Link2 Shield Station No 3 W R LB60984 Link2 Shield Station No 4 W R LB60985 Link2 Shield Station No 5 W R LB60986 Link2 Shield Station No 6 W R LB60987 Link2 Shield Station No 7 W R LB60988 Link2 Shield Station No 8 W R LB60989 Link2 Shield Station No 9 W R LB60990 Link3 Shield Station No 0 W R LB60991 Link3 Shield Station No 1 W R LB60992 Link3 Shield Station No 2 W R LB60993 Link3 Shield Sta...

Page 55: ...ft coordinate X the coordinate value of X axis when touch left R LW60014 Touch left coordinate Y the coordinate value of Y axis when touch left R LW60802 index of recipe group search one recipe group from some groups W R LW60803 index the present recipe search one recipe from present formula group W R LW60900 account name W R LW60930 Old password new user password modified password old password W ...

Page 56: ...the printer option is turned on 2 Choose to open the printing history data There are two options below One is the printing time and the other is the printing date When neither option is checked the printer only prints the value when the printing time is checked the printer prints the time plus the value when the printing date is checked the printer prints the date plus the value ...

Page 57: ...ATSEL HMI User Manual 3 Drag historical data control and function button and set function button as the option of Querying Historical data ...

Page 58: ...Manual 4 Click on the query history data button and then query the data of the relevant time period Click on print it will print the data queried on the current page which can print up to 100 pieces of data at a time ...

Page 59: ...ATSEL HMI User Manual Printing of alarm data 1 Open the parameter settings and select the print option The printer will not work until the printer option is checked in the option ...

Page 60: ...ptions below One is the print time and the other is the print date When neither option is checked the printer only prints the value when the printing time is checked the printer prints the time plus the value when the printing date is checked the printer prints the date plus the value ...

Page 61: ...MI User Manual 3 Add alarm function set trigger conditions drag out alarm control 4 Set relevant trigger conditions when the alarm event triggers the printer will automatically start printing alarm information ...

Page 62: ...tting The option on the right is to configure the printer s related functions Only the baud rate can be selected The baud rate is the transmission rate of the configuration data At present the data printed by the printer under 1900 is correct ...

Page 63: ...ATSEL HMI User Manual Pinter connection Pinter Model No WH E45 More printer details please check http en weihuang com cn products_detail productId 128 html ...

Page 64: ...Manual Connection The series Port need to be wired by ourselves HMI DB9 Pin2 to Printer 3 HMI DB9 Pin3 to Printer 5 HMI DB9 Pin5 to Printer 7 Cautions the power cable input should be 5V don t wire the wrong direction ...

Reviews: