Sel SEL-487B Manual Download Page 28

SEL-487B Data Sheet

Schweitzer Engineering Laboratories, Inc.

28

PTP—Ethernet Port 5A, 5B

Input:

IEEE 1588 PTPv2

Profiles:

Default, C37.238-2011 (Power Profile)

Synchronization 

Accuracy:

±100 ns @ 1-second Sync Intervals when 

communicating directly with master 
clock

IRIG Time Output

Capable of driving 300 ohm termination with <200 ns propagation 

delay

The IRIG time output does not support high-accuracy IRIG-B 

timekeeping.

Operating Temperature

–40° to +85°C (–40° to +185°F)

Note: LCD contrast impaired for temperatures below –20° and above 

+70°C.

Humidity

5% to 95% without condensation

Weight (Maximum)

4U Rack Unit (TiDL only): 6.4 kg (14.1 lb)

7U Rack Unit:

16.8 kg (36.9 lb)

9U Rack Unit:

20.8 kg (45.9 lb)

Terminal Connections

Rear Screw-Terminal Tightening Torque, #8 Ring Lug

Minimum:

1.0 Nm (9 in-lb)

Maximum:

2.0 Nm (18 in-lb)

User terminals and stranded copper wire should have a minimum 

temperature rating of 105°C. Ring terminals are recommended.

Wire Sizes and Insulation

Wire sizes for grounding (earthing), current, voltage, and contact 

connections are dictated by the terminal blocks and expected load 
currents. You can use the following table as a guide in selecting wire 
sizes. The grounding conductor should be as short as possible and 
sized equal to or greater than any other conductor connected to the 
device, unless otherwise required by local or national wiring 
regulations.

Type Tests

Note: These tests do not apply to optoisolated control inputs rated for 24 V.

Electromagnetic Compatibility (EMC)

Electromagnetic 

Emissions:

IEC 60255-25:2000

Connection Type

Min. Wire Size

Max. Wire Size

Grounding (Earthing) 

Connection

14 AWG (2.5 mm

2

)

N/A

Current Connection

16 AWG (1.5 mm

2

)

10 AWG (5.3 mm

2

)

Potential (Voltage) 

Connection

18 AWG (0.8 mm

2

)

14 AWG (2.5 mm

2

)

Contact I/O

18 AWG (0.8 mm

2

)

10 AWG (5.3 mm

2

)

Other Connection

18 AWG (0.8 mm

2

)

10 AWG (5.3 mm

2

)

Electromagnetic Compatibility Immunity

Conducted RF Immunity:

IEC 60255-22-6:2001

Severity Level: 10 V rms

IEC 61000-4-6:2008

Severity Level: 10 V rms

Electrostatic Discharge 

Immunity:

IEC 60255-22-2:2008

Severity Level: 2, 4, 6, 8 kV contact; 2, 
4, 8, 15 kV air

IEC 61000-4-2:2008

Severity Level: 2, 4, 6, 8 kV contact; 2, 
4, 8, 15 kV air

IEEE C37.90.3-2001

Severity Level: 2, 4, 8 kV contact; 4, 8, 
15 kV air

Fast Transient/Burst 

Immunity:

IEC 60255-22-4:2008, Class A

Severity Level: 4 kV, 5 kHz; 2 kV 5 kHz 
on communication ports

IEC 61000-4-4:2011

Severity Level: 4 kV, 5 kHz

Magnetic Field Immunity: IEC 61000-4-8:2009

Severity Level: 900 A/m for 3 s, 
100 A/m for 1 min.

IEC 61000-4-9:2001

Severity Level: 1000 A/m

Power Supply Immunity:

IEC 60255-11:2008
IEC 61000-4-11:2004
IEC 61000-4-29:2000

Radiated Digital Radio 

Telephone RF 
Immunity:

ENV 50204:1995

Severity Level: 10 V/m at 900 MHz and 
1.89 GHz

Radiated Radio Frequency 

Immunity:

IEC 60255-22-3:2007

Severity Level: 10 V/m

IEC 61000-4-3:2010

Severity Level: 10 V/m

IEEE C37.90.2-2004

Severity Level: 35 V/m

Surge Immunity:

IEC 60255-22-5:2008

Severity Level: 1 kV line-to-line, 2 kV 
line-to-earth

IEC 61000-4-5:2005

Severity Level: 1 kV line-to-line, 2 kV 
line-to-earth

Damped Oscillatory 

Magnetic Field:

IEC 61000-4-10:2001

Severity Level: 100 A/m

Surge Withstand 

Capability:

IEC 60255-22-1:2007

Severity Level: 2.5 kV peak common 
mode,
1.0 kV peak differential mode

IEEE C37.90.1-2002

Severity Level: 2.5 kV oscillatory, 4 kV 
fast transient waveform

Environmental

Cold:

IEC 60068-2-1:2007

Severity Level: 16 hours at –40

C

Damp Heat, Cyclic:

IEC 60068-2-30:2005

Severity Level: 25°C to 55

C, 6 cycles, 

Relative Humidity: 95%

Dry Heat:

IEC 60068-2-2:2007

Severity Level: 16 hours at +85

C

Vibration:

IEC 60255-21-1:1988

Severity Level: Class 2 (endurance); 
Class 2 (response)

IEC 60255-21-2:1988

Severity Level: Class 1 (shock withstand, 
bump); Class 2 (shock response)

IEC 60255-21-3:1993

Severity Level: Class 2 (quake response)

Object Penetration

IEC 60529:2001 + CRGD:2003    

Protection Class: IP30

Summary of Contents for SEL-487B

Page 1: ...tem stability margins and reduce equipment damage Flexible zone selection and six differential zones provide protection for multiple busbar applications Failed CT detection elements reliably indicate...

Page 2: ...unctions in a Double Bus Application ANSI NUMBERS ACRONYMS AND FUNCTIONS 16 SEC Access Security Serial Ethernet 27 59 Over and Undervoltage 50 Overcurrent 50BF Breaker Failure Overcurrent 51 Time Over...

Page 3: ...lay for complex busbar arrangements The SEL 487B provides station wide protection through the use of up to six zones of differential protection advanced zone selection algorithms and per terminal brea...

Page 4: ...ration According to Disconnect Switch Positions Figure 4 Bus Arrangement With Disconnect DS2 Closed the New Zone 1 That Includes Bus Zones North and East ZONE Enter BUS PROTECTION Rinadel Station Term...

Page 5: ...tween an open circuit breaker and CT of a feeder at a substation This area is a dead zone because neither busbar protection nor local line protection can clear this fault the remote end of the feeder...

Page 6: ...estraint and operate current The advanced CT supervision in the SEL 487B monitors dif ferential zone restraint and operating current for these changes to provide rapid and dependable detection of open...

Page 7: ...g the close to open operation the 89b contact must close during the transition zone after the main contact arcing is extinguished disconnect is OPEN as shown in Figure 12 The 89a contact must open in...

Page 8: ...e CT as opposed to both main zones with an overlapping tie breaker arrangement Figure 15 Two CTs Configured With a Differential Element Across the Breaker Six Independent Settings Groups Increase Oper...

Page 9: ...current inputs in each relay measures only one phase with six dedicated zones of protection available Each relay operates independently the only communication among relays is MIRRORED BITS communicat...

Page 10: ...B Relays Protect Two Main Busbars and a Transfer Busbar Bus Coupler and 20 Terminals Optimize your SEL 487B by protecting both HV and LV busbars with three relays Figure 19 shows two HV busbars and tw...

Page 11: ...ct Both HV and LV Busbars Bus 1 Bus 2 52 400 5 400 5 800 5 400 5 800 5 800 5 52 52 52 52 Bus 3 Bus 4 52 400 5 400 5 800 5 4000 5 1600 5 52 52 400 5 52 52 FDR_1 FDR_4 TRFR_1 TRFR_2 FDR_2 FDR_12 FDR_3 3...

Page 12: ...c intervals the relay can be synchronized to an accuracy of 100 ns The relay is capable of receiving as many as 32 sync messages per second Figure 21 Example PTP Network SNTP Time Synchronization Use...

Page 13: ...perations e g trip settings group selection Replace traditional latching relays for such functions as remote control enable with 32 latching control points Program latch set and latch reset conditions...

Page 14: ...er settings you create offline by using a PC communications link with the SEL 487B The relay converts event reports to oscillograms with time coordinated element assertion and phasor diagrams The ACSE...

Page 15: ...transfers Choose Ethernet connection media options for primary and stand by connections 10 100BASE T Twisted Pair Network 100BASE FX Fiber Optic Network Communicate using IEC 61850 Logical Nodes and G...

Page 16: ...supports as many as seven simultaneous client associations Relevant Relay Word bits are available within the logical node data so you can use the IEC 61850 data server in the relay to monitor the stat...

Page 17: ...r programmable display points The rotating display scrolls through any active nonblank display points If none are active the relay scrolls through displays of the differential operating and restraint...

Page 18: ...following additional input output I O per interface board six independent inputs eighteen common inputs in two groups of nine six high speed high interrupting Form A outputs two standard Form A output...

Page 19: ...s of 1 kHz event data Relay settings operational in the relay at the time of the event display at the end of each filtered event report Use event report settings in the relay to assign up to 20 analog...

Page 20: ...Use this feature to gain a broad perspective of relay ele ment operation Items that trigger an SER entry are selectable and can include as many as 250 monitoring points such as input output change of...

Page 21: ...487B Data Sheet 21 Front and Rear Panel Diagrams Figure 32 Standard Front Panel Diagram 9U Chassis Size Panel Mount Option Showing the Front Panel With LCD Navigation Pushbuttons 16 Target LEDs Reset...

Page 22: ...eering Laboratories Inc 22 Figure 33 Expanded Front Panel Diagram 9U Chassis Size Panel Mount Option Showing Extended Front Panel HMI With LCD Navigation Pushbuttons 24 Tricolor LEDs Reset and 12 Prog...

Page 23: ...Schweitzer Engineering Laboratories Inc SEL 487B Data Sheet 23 Figure 34 Rear Panel Diagram of the 9U Chassis With Four INT4 Interface Boards...

Page 24: ...SEL 487B Data Sheet Schweitzer Engineering Laboratories Inc 24 Figure 35 Rear Panel Diagram of the 7U Chassis With Two INT4 Interface Boards Figure 36 Rear Panel With EtherCAT Board...

Page 25: ...Schweitzer Engineering Laboratories Inc SEL 487B Data Sheet 25 Relay Dimensions Figure 37 Dimensions for Rack and Panel Mount Models...

Page 26: ...1 A Nominal 100 A 5 A Nominal 500 A One Cycle Thermal Rating Peak 1 A Nominal 250 A 5 A Nominal 1250 A Burden Rating 1 A Nominal 0 1 VA 1 A 5 A Nominal 0 5 VA 5 A AC Voltage Inputs Rated Voltage Range...

Page 27: ...Vdc 110 Vdc Pickup 88 0 132 0 Vdc Dropout 66 0 Vdc 125 Vdc Pickup 105 150 Vdc Dropout 75 Vdc 220 Vdc Pickup 176 264 Vdc Dropout 132 Vdc 250 Vdc Pickup 200 300 Vdc Dropout 150 Vdc AC Thresholds Ratings...

Page 28: ...WG 5 3 mm2 Electromagnetic Compatibility Immunity Conducted RF Immunity IEC 60255 22 6 2001 Severity Level 10 V rms IEC 61000 4 6 2008 Severity Level 10 V rms Electrostatic Discharge Immunity IEC 6025...

Page 29: ...nts 32 each remote bits local control bits latch bits in protection logic and latch bits in automation logic Relay Element Pickup Ranges and Accuracies Differential Elements Number of Zones 6 Number o...

Page 30: ...tting Range 0 99999 cycles 1 cycle step Breaker Status Monitor Number 21 Coupler Security Logic Number 4 Timer Setting Range 0 1000 cycles 1 12 cycle step Control Input Timers Setting Range Pickup 0 0...

Page 31: ...Schweitzer Engineering Laboratories Inc SEL 487B Data Sheet 31 Notes...

Page 32: ...nd international copyright and patent laws in its products including without lim itation software firmware and documentation The information in this document is provided for informational use only and...

Reviews: