Sel SEL-2725 Installation And Maintenance Manual Download Page 4

SEL-2725 Data Sheet

Schweitzer Engineering Laboratories, Inc.

4

Operating Environment

Pollution Degree:

2

Overvoltage Category:

II

Insulation Class:

I

Enclosure Protection

IEC/EN 60255-27:2014

Power Inputs:

IP2X

Enclosure:

IP4X

Power Supply

Rated Voltage

1

:

12–250 Vdc, 110–240 Vac (50/60 Hz)

Operational Voltage:

10.8–275 Vdc, 85–264 Vac (50/60 Hz)

Maximum Burden:

5 W, 250 mA

1

 Rated Voltage — UL Tested at this voltage.

Type Tests

Communication Product Testing

IEEE 1613:2009, Class II
IEC 61850-3:2013, Class II

Electromagnetic Compatibility (EMC) Emissions

Generic Emissions:

EN 60255-26:2013
EN 61850-3:2014

47 CFR Part 15

ICES-001, Issue 5
CISPR 11:2009 + A1:2010
CISPR 22:2008
EN 55011:2009 + A1:2010
EN 55022:2010 + AC:2011
EN 55032:2012 + AC:2013

Severity Level: Class B

Electromagnetic Compatibility Immunity

Conducted RF Immunity:

IEC 60255-26: 2013
IEC 61000-4-6:2013

Severity Level: 10 Vrms

Electrostatic Discharge 

Immunity:

IEC 60255-26:2013
IEC 61000-4-2:2008
IEEE C37.90.3-2001

Severity Level: 2, 4, 8 kV contact; 
4, 8, 15 kV air

Fast Transient/Burst 

Immunity:

IEC 60255-26:2013
IEC 61000-4-4:2012

Severity Level: Zone A

Magnetic Field Immunity:

IEC 60255-26:2013
IEC 61000-4-8:2009

Severity Level: 1000 A/m for 3 seconds, 
100 A/m for 1 minute

IEC 61000-4-9:2001

Severity Level: 1000 A/m

IEC 61000-4-10:2001

Severity Level: 100 A/m

Power Supply Ripple:

EN 61000-4-17:1999 

+A1:2004 +A2:2009

IEC 61000-4-17:1999 

+A1:2001 +A2:2008

Power Supply Dips and 

Interruptions:

EC 60255-26:2013
IEC 61000-4-11:2004
IEC 61000-4-29:2000

Power Supply Gradual 

Shutdown and Startup:

IEC 60255-26:2013

Power Supply Discharge 

Capacitors:

IEC 60255-27:2013

Power Supply Reverse 

Polarity and Slow Ramp:

IEC 60255-27:2013

Radiated RF Immunity:

IEC 60255-26:2013
IEC 61000-4-3:206 + A1:2007 + A2:2010

Severity Level: 10 V/m unmodulated
80 MHz–1 GHz, 1.4 GHz–2.7 GHz

IEEE C37.90.2-2004

Severity Level: 20 V/m 80% AM,
0.5 s keyed, 80 MHz–1 GHz

Surge Immunity:

IEC 60255-26:2013
IEC 61000-4-5:2005

Severity Level: Zone B

Surge Withstand Capability:

IEC 60255-26:2013
IEC 61000-4-18:2010

Severity Level: 2.5 kV peak common 
mode, 1.0 kV peak differential mode

IEEE C37.90.1-2002

Severity Level: 2.5 kV oscillatory, 
4 kV fast transient waveform

Environmental

Cold:

IEC 60068-2-1:2007

Severity Level: 16 hours at –40°C

IEC 60255-27:2013

Damp Heat, Cyclic:

IEC 60068-2-30:2005

Severity Level: 25°C, 
Relative Humidity: 93%
Duration: 6 cycles

IEC 60255-27:2013

Dry Heat:

IEC 60068-2-2:2007

Severity Level: 16 hours at +85°C

IEC 60255-27:2013

Damp Heat, Steady State:

IEC 60068-2-78:2012

Severity Level: 40°C at 90% for 10 days

IEC 60255-27:2013

Cyclic Temperature:

IEC 60062-2-30:2005

Severity Level: -40˚C to +85˚C

Vibration:

IEC 60255-21-1:1988

Severity Level: Class 2 endurance,
Class 2 response

IEC 60255-21-2:1998

Severity Level: Class 1 shock withstand, 
bump, and Class 2 shock response

IEC 60255-21-3:1993

Severity Level: Class 2 (quake response)

IEC 60255-27:2013

Safety

Dielectric Strength:

IEC 60255-27:2013
IEC 61850-3:2013
IEEE C37.90-2005

±3.6 kVdc on power supply
±1.5 kVac on Ethernet ports
Type tested for 1 minute

Impulse:

IEC 60255-27:2013
IEC 61850-3:2013
IEEE C37.90-2005

Severity Level: Common Mode ±5 kV 
power supply, ±1.5 kV Ethernet ports 
Common Mode, Port to Port 5 kV 
power supply, zero-rated, Ethernet ports

Protective Bonding 

Resistance:

IEC 60255-27:2013
IEC 61850-3:2013
IEEE C37.90-2005

Laser (LED) Safety:

EN 60825-1:2007
EN 60825-2:2004 + A1:2007 + A2:2010

Complies with 21 CFR Chapter 1, 
Subchapter J, Part 1040.10.

Summary of Contents for SEL-2725

Page 1: ...for crossover cables autospeed detects for 10 or 100 Mbps links and automatically detects half or full duplex operation Reliable Power Supply 10 275 Vdc power supplies exceed all harsh environmental...

Page 2: ...supplied packaging and must be kept between 40 degrees to 176 degrees Fahrenheit Protective Ground Use 1 5 mm2 16 AWG wire or heavier to connect to the Protective Ground terminal Disconnect Device Dis...

Page 3: ...rol Address Table 1000 MAC addresses RJ45 Ports Recommended Cable Category 5 e Shielded Twisted Pair Cable STP SEL C627 Autonegotiation 10 or 100 Mbps full or half duplex and MDI MDI X crossover Fiber...

Page 4: ...pply Reverse Polarity and Slow Ramp IEC 60255 27 2013 Radiated RF Immunity IEC 60255 26 2013 IEC 61000 4 3 206 A1 2007 A2 2010 Severity Level 10 V m unmodulated 80 MHz 1 GHz 1 4 GHz 2 7 GHz IEEE C37 9...

Page 5: ...of any protective conductor connection must be checked before carrying out any other actions It is the responsibility of the user to ensure that the equipment is installed operated and used for its i...

Page 6: ...NT Ne pas appliquer une proc dure ou un ajustement qui n est pas d crit explicitement dans ce manuel d instruction WARNING During installation maintenance or testing of the optical ports use only test...

Page 7: ...he responsibility of the user to ensure that the equipment is installed operated and used for its intended function and in the manner this manual specifies The equipment should not be serviced If this...

Page 8: ...nternational copyright and patent laws in its products including without lim itation software firmware and documentation The information in this document is provided for informational use only and is...

Reviews: