Sel SEL-2725 Installation And Maintenance Manual Download Page 3

Schweitzer Engineering Laboratories, Inc.

SEL-2725 Data Sheet

3

Mechanical Diagrams

                    

Specifications

                    

                    

Figure 2

SEL-2725 Dimension Drawing

LEGEND

in

[mm]

5.94

[150.9]

5.38

[136.7]

1.08

[27.3]

3.00

[76.2]

4.90

[124.5]

Ø.21

 [Ø5.4]

TOP

5.38

[136.7]

1.51

[38.4]

FRONT

i9400a

Compliance

Designed and manufactured under an ISO 9001 certified quality 

management system

FCC CFR 47 Part 15, Class B

RoHS Compliant

UL Listed to US and Canadian Safety Standards File E220228; NRAQ2/

NRAQ8

CE Mark

General

Switching Technology

Non-blocking, store and forward

Latency

Less than 10 

s

LED Indicators

Power (green)

Link/Activity (green per port)

Full duplex/collision (yellow per port)

Network

IEEE 802.3u:

100BASE-T and 100BASE-FX or 

100BASE-LX10

IEEE 802.3:

10BASE-T

IEEE 802.x:

Flow control

Address Table:

1000 MAC addresses

RJ45 Ports

Recommended Cable:

Category 5(e) Shielded, Twisted-Pair 

Cable (STP) (SEL-C627)

Autonegotiation:

10 or 100 Mbps, full- or half-duplex and 

MDI/MDI-X crossover

Fiber Optics

Class 1 LASER/LED 

Product:

IEC 60825-1:1993 + A1:1997 + A2:2001

Data Rate:

100 Mbps

Connector Type:

LC

Multimode 

(100BASE-FX) Option:

62.5 µm fiber

Lowest TX Level:

–20 dBm

Lowest RX Sensitivity:

–31 dBm

Optical Budget: 

11 dBm

Max Distance:

2 km

Wavelength:

1300 nm

Single-Mode 

(100BASE-LX10) Option:

9 µm fiber

Lowest TX Level:

–15 dBm

Lowest RX Sensitivity:

–25 dBm

Optical Budget:

10 dBm

Max Distance:

15 km

Wavelength:

1310 nm

Environmental

Operating and Storage Temperature

–40° to +85°C (–40° to +185°F)
SEL-2725 UL Rating: –40° to +40°C (–40° to +104°F)

Relative Humidity

0% to 95% non-condensing

Altitude

2000 m

Note:

 Above 2000 m, derate dielectric strength and temperature according to 

IEEE 1613: 2009 Table 1 and Table 2. IEC 60255-27 certification below 
2000 m only.

Summary of Contents for SEL-2725

Page 1: ...for crossover cables autospeed detects for 10 or 100 Mbps links and automatically detects half or full duplex operation Reliable Power Supply 10 275 Vdc power supplies exceed all harsh environmental...

Page 2: ...supplied packaging and must be kept between 40 degrees to 176 degrees Fahrenheit Protective Ground Use 1 5 mm2 16 AWG wire or heavier to connect to the Protective Ground terminal Disconnect Device Dis...

Page 3: ...rol Address Table 1000 MAC addresses RJ45 Ports Recommended Cable Category 5 e Shielded Twisted Pair Cable STP SEL C627 Autonegotiation 10 or 100 Mbps full or half duplex and MDI MDI X crossover Fiber...

Page 4: ...pply Reverse Polarity and Slow Ramp IEC 60255 27 2013 Radiated RF Immunity IEC 60255 26 2013 IEC 61000 4 3 206 A1 2007 A2 2010 Severity Level 10 V m unmodulated 80 MHz 1 GHz 1 4 GHz 2 7 GHz IEEE C37 9...

Page 5: ...of any protective conductor connection must be checked before carrying out any other actions It is the responsibility of the user to ensure that the equipment is installed operated and used for its i...

Page 6: ...NT Ne pas appliquer une proc dure ou un ajustement qui n est pas d crit explicitement dans ce manuel d instruction WARNING During installation maintenance or testing of the optical ports use only test...

Page 7: ...he responsibility of the user to ensure that the equipment is installed operated and used for its intended function and in the manner this manual specifies The equipment should not be serviced If this...

Page 8: ...nternational copyright and patent laws in its products including without lim itation software firmware and documentation The information in this document is provided for informational use only and is...

Reviews: