Schweitzer Engineering Laboratories, Inc.

SEL-2241 Data Sheet

7

Digital Radio Telephone 

RF Immunity:

ENV 50204:1995 Severity Level: 10 V/m 

at 900 MHz and 1.89 GHz

Conducted RF Immunity: IEC 60255-22-6:2001 

Severity Level: 10 Vrms

IEC 61000-4-6:2008

Severity Level: 10 Vrms

Surge Immunity:

IEC 60255-22-5:2008 

Severity Level: 1 kV Line to Line, 
2 kV Line to Earth

IEC 61000-4-5:2005

Severity Level: 1 kV Line to Line, 
2 kV Line to Earth

Fast Transient, Burst 

Immunity:

IEC 60255-22-4:2008

Severity Level: Class A: 4 kV, 5 kHz;
2 kV, 5 kHz on communications ports

IEC 61000-4-4:2004 + CRGD:2006

Severity Level: 4 kV, 5 kHz

Power Supply Immunity: IEC 61000-4-11:2004

IEC 61000-4-29:2000
IEC 60255-11:2008

Magnetic Field 

Immunity:

IEC 61000-4-8:2009 

Severity Level: 1000 A/m for 3 seconds, 
100 A/m for 1 minute

IEC 61000-4-10:2001 
   Severity Level: 100 A/m

Surge Withstand 

Capability Immunity:

IEEE C37.90.1:2002, 

2.5 kV oscillatory, 4 kV fast transient

IEC 60255-22-1:2007 

2.5 kV common-mode 
1.0 kV differential-mode

Oscillatory Waves 

Immunity:

IEC 61000-4-12:2006 

Ring Wave: 2 kV common, 
1.0 kV differential 
Oscillatory: 2.5 kV common, 
1.0 kV differential

Common Mode 

Disturbance Immunity:

IEC 61000-4-16:2002 

Frequency: 0 Hz to 150 Hz 
Severity: Level 4, segment 4: 30 Vrms 
open-circuit, 15–150 kHz

Emissions

Radiated and Conducted 

Emissions:

IEC 60255-25:2000 
FCC 15-107:2014
FCC 15-109:2014

Severity Level: Class A

Canada ICES-001 (A) / NMB-001 (A)

Summary of Contents for SEL-2241

Page 1: ...2242 chassis backplane has ten slots labeled A through J Only Slot A supports the SEL 2241 RTAC module To install the RTAC tip the top of the module away from the chassis align the notch on the bottom...

Page 2: ...eb interface through the USB cable See Section 7 Security and Account Management in the ACSELERATOR RTAC SEL 5033 Instruction Manual for RTAC web password setup The SEL 2241 has four nonisolated seria...

Page 3: ...ection 1 Getting Started in the SEL 5033 Instruction Manual for instructions on how to back up and restore RTAC projects Step 2 De energize any power source connected to the power coupler s in the Axi...

Page 4: ...ection 3 Factory Reset in the SEL 2240 Instruction Manual describes Table 3 shows the configurable jumper positions SEL 2241 Disassembly To disassemble the SEL 2241 RTAC perform the fol lowing steps S...

Page 5: ...EtherNet IP Explicit Message Client Server DNP3 Serial DNP3 LAN WAN Modbus RTU Modbus TCP SEL Fast Messaging LG 8979 SES 92 IEEE C37 118 IEC 61850 MMS IEC 60870 5 101 104 FTP SFTP CDC Type II EtherNe...

Page 6: ...Ithe Rating 5 A Rated Frequency 50 60 5 Hz Operating Time coil energization to contact closure resistive load Pickup Dropout time 8 ms typical Electrical Durability Make VA Rating 3600 VA cos 0 3 Elec...

Page 7: ...Power Supply Immunity IEC 61000 4 11 2004 IEC 61000 4 29 2000 IEC 60255 11 2008 Magnetic Field Immunity IEC 61000 4 8 2009 Severity Level 1000 A m for 3 seconds 100 A m for 1 minute IEC 61000 4 10 200...

Page 8: ...oducts including without lim itation software firmware and documentation The information in this document is provided for informational use only and is subject to change without notice Schweitzer Engi...

Reviews: