4.61
Date Code 20100129
Instruction Manual
SEL-751A Relay
Protection and Logic Functions
Reclose Logic
Lockout State
The reclosing relay goes to the Lockout State if any
one
of the following
occurs:
➤
The shot counter is equal to or greater than the last shot at time
of reclose initiation (e.g., all automatic reclosing attempts are
unsuccessful—see
).
➤
Reclose initiation is unsuccessful because of SEL
OGIC
control
equation setting 79RIS [see
Initiate Supervision Settings (79RI and 79RIS, Respectively) on
page 4.66
].
➤
The circuit breaker opens without reclose initiation (e.g., an
external trip).
➤
The shot counter is equal to or greater than last shot, and the
circuit breaker is open [e.g., the shot counter is driven to last
shot with SEL
OGIC
control equation setting 79DLS while open
interval timing is in progress. See
to-Last Shot Settings (79DTL and 79DLS, Respectively) on
page 4.68
].
➤
The close failure timer (setting CFD) times out (see
➤
SEL
OGIC
control equation setting 79DTL = logical 1 [see
Drive-to-Lockout and Drive-to-Last Shot Settings (79DTL and
79DLS, Respectively)
].
➤
The Reclose Supervision Limit Timer (setting 79CLSD) times
out (see
and top of
) and the reclose
enable setting, E79, has setting choices 1, 2, 3, or 4.
➤
A new reclose initiation occurs while the reclosing relay is
timing on an open interval (e.g., flashover in the tank while
breaker is open).
The
OPEN
command is included in the reclosing relay logic via the factory
SEL
OGIC
control equation settings:
79DTL :=
OC OR ...
(drive-to-lockout)
Relay Word bit OC asserts for execution of the
OPEN
command. See
Command (Open Breaker) on page 7.33
for more information on the
OPEN
command. Also, see
Drive-to-Lockout and Drive-to-Last Shot Settings
(79DTL and 79DLS, Respectively) on page 4.68
Reclosing Relay
States and Settings/
Setting Group
Changes
If individual settings are changed for the active setting group
or
the active
setting group is changed,
all
of the following occur:
➤
The reclosing relay remains in the state it was in before the
settings change.
➤
The shot counter is driven to last shot (last shot corresponding
to the new settings; see discussion on last shot that follows).
➤
The reset timer is loaded with reset time setting 79RSLD (see
discussion on reset timing later in this section).
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...