- ENGLISH -
TRD03B0000SE 036247 270121
holding down the '
' or '
' keys, allows to increase or decrease
the value quickly.
Reset installer configuration
To reset installer configuration, in order to bring all the
parameters to factory default values, access the configuration
and, when the display shows '
Con
', simultaneously press '
'
and '
' for a few seconds until the screen goes back to normal
mode.
Description of configuration parameters
The installer configuration parameters are shown in table 1 and
explained below.
Some installer parameters may not be displayed as only
the parameters currently required by the configuration are
shown (the configuration value of a parameter, may
exclude one or more subsequent parameters).
P01
: allows to customise the regulation modes that can be
selected with the key ' '. The regulation modes available
are Comfort, Economy and OFF: each of these can be enabled
or disabled by changing
P01
.
The OFF mode will be replaced by Antifrost mode in case
P02
is set with an antifrost temperature.
P02
: by this parameter the Antifrost temperature can be set:
this will be maintained when the thermostat is turned off.
The antifrost temperature can be set in the range 0.5 .. 25 °C or
disabled by setting the parameter until the value ‘no’ appears.
By factory default this parameter is set at 6 °C.
P03
: room temperature offset.
The detected room temperature can be corrected by ±10.0 °C
with the offset, in order to correct any systematic reading error
due to thermostat positioning in unsuitable areas to detect the
room temperature.
By default the device is set with 0.0 °C offset.
P04
: sampling time.
To ensure long battery life, the thermostat waits a period of
time between one transmission and another. The period can be
chosen from 1 to 10 minutes. Therefore it’s normal that the
temperature displayed is not immediately updated; moreover
for the same reason it can be necessary to wait some minutes
(up to the sampling time value) to see the receiver's output
switching. A sampling time of 1 to 3 minutes should be chosen
when the heating/cooling system is fast, while with slower
heating systems based on radiators or floor heating, even a
time of 10 minutes allows excellent accuracy and comfort. In
any case, at any time, pressing the ' ' key forces an update
to the receiver. Choosing a longer sampling time will get a
longer battery life.
P05
and
P06
: these two parameters set the temperature range
within which the set-point temperature can be chosen when the
thermostat is in heating mode.
P05
is the lower limit and can be
freely set from 5.0 .. 35.0 °C, while
P06
is the higher limit that
can be set in a range from the lower limit, chosen in
P05
, up to
35.0°C.
Therefore, the widest temperature range is 5 .. 35 °C and can
be easily reduced based on installation requirements.
P07
and
P08
: these two parameters configure the temperature
range within which the set-point temperature can be set when
the thermostat is in cooling mode, with the same logic of the
previous two points.
The set-point temperature limits are re-defined upon changing
the cooling/heating settings.
P09
: NTC sensor configuration.
The thermostat is set by default prepared to operate with the
internal NTC (
P09= Int
). Alternatively to the internal sensor a
remote sensor can be wired to the connector 'REMOTE
SENSOR', shown with
B
in Fig. 6 and set parameter P10 as
'Ext': this way the internal sensor is disabled while the external
is enabled. Make sure to use the proper remote sensor type,
and respect the maximum wire length allowed.
P10
: reserved parameter, do not modify.
P11
: reserved parameter, do not modify.
P12
: hysteresis, represents the amplitude of the hysteresis
which will be used for the room temperature regulation.
P13
: reserved parameter, do not modify.
P14
: reserved parameter, do not modify.
P15
: reserved parameter, do not modify.
P16
: reserved parameter, do not modify.
P17
: set-point temperature displayed by default.
The thermostat is set by factory default on “no” parameter, so
the thermostat shows the detected room temperature, but if this
parameter s set on “YES”, the displayed temperature is the set
point one, but the room temperature can be temporarily
displayed after the set-point temperature is modified. Instead, if
the parameter is set on “
OnL
”, “set-point only”, the thermostat
shows only the set-point temperatures (set-point comfort, set-
point economy) and it is not possible to display the room
temperature.
WARRANTY
In the view of a constant development of their products, the
manufacturer reserves the right to amend technical data and
features without prior notice. The consumer is guaranteed
against any lack of conformity according to the European
Directive 1999/44/EC as well as to the manufacturer’s
document about the warranty policy. The full text of the
warranty is available on request from the seller.
TEMPERATURE REGULATION
The thermostat regulates the output on the receiver with ON/
OFF type regulation with configurable hysteresis on parameter
P12
.
DISPLAY BACK-LIGHTING
Switch-on of the display Switch-off is automatic after 20
seconds from last button pressure.
BATTERIES INSERTION/REPLACEMENT
The display permanently shows the batteries charge state by
means of symbol ' '. Batteries are charged to maximum if
all three level indicators inside the symbol are on.
On the contrary, the batteries are drained and must be replaced
when the symbol appears completely empty ' '.
The symbol ' ' flashes when the batteries are excessively
drained to allow radio transmission.
For batteries replacement proceed as explained on points
1
,
2
and
4
at page 3.
COMPATIBILITY WITH BIDIRECTIONAL WIRELESS
SYSTEM
The thermostat works with the following bidirectional wireless
technology receivers:
DA0311
: Modbus receiver.
TECHNICAL FEATURES
Power supply:
2 x 1.5V
alkaline AA type
batteries
Duration of the batteries:
5 years with P04=10 minutes
3 years with P04=3 minutes
Frequency:
868.450 MHz
Modulation:
GFSK
Max. RF power transmitted: 1 mW
Type of antenna:
Internal
Max. distance from receiver: >300 m in free field
>50 m in buildings (depending on
the building and environment)
Temperature sensor (internal sensor or remote as alternative)
Regulation range:
5.0 .. 35.0°C
Hysteresis:
0.2°C configurable 0.1 .. 5.0 °C
Type of sensor:
NTC 10kohm ±1% @25°C
B(25/85)=3977
Resolution:
0.1°C
Range:
-9.9°C .. +50.0°C
Precision:
±1.0°C
Maximum length of the wires
to the remote sensor:
15 m
Antifrost:
6.0°C adjustable OFF
|
0.5 .. 25.0 °C
Offset:
± 10.0°C. (Default 0.0°C)
Backlighting switch-off:
20 seconds from last pressing
Protection rating:
IP 30
Type of action:
1
Overvoltage category:
II
Pollution degree:
2
Tracking Index (PTI):
175
Class of protection against
electric shocks:
III
Rated impulse voltage:
2500V
Number of manual cycles: 50000
Number of automatic cycles: unlimited
Software class:
A
EMC test voltage:
3V
EMC test current:
35mA
Distances tolerances fault
mode ‘short’ exclusion:
±0,15mm
Ball pressure test temp.:
75° C
Operating temperature:
0°C .. +40°C
Storage temperature:
-10°C .. +50°C
Humidity limits:
20% .. 80% RH (non-condensing)
Enclosure:
Material:
ABS+PC V0 self-extinguishing
Colour:
Signal White (RAL 9003)
Weight:
~ 115 gr
CLASSIFICATION UNDER REG. 2013.811.EC
Class:
I
Contribution to energy efficiency:
1%
DIMENSIONS
23.6mm
85mm
85m
m
2