- ENGLISH - 

RDXSM10001SE 022949A6 051213 

supplied with the product by writing the installation date of the 
product, the date when the CO and Methane modules must be 
replaced the first time and last time and finally the date before 
which the entire detector must be replaced. 
The latter is stated on 15 solar years from the installation date 
of the product. This label must be applied, at installer care, on 
a  visible side of the gas detector once it has been fixed in its 
typical installation position. 

Warning label: 

The  modules  can  be  replaced  up  to  twice  when  they  just 
empire at their end of life, or more than twice in case any fault 
has  occurred  (in  this  case  pay  attention  to  respect  the 
replacement date of the whole detector). 

This  device  is  intended  for  wall  mount  only,  with  relevant 
electrical wiring made through the fixed wiring, not exposed to 
people and connected to the fixed electrical wiring. The device 
safety  and  operational  features  are  only  granted  when  the 
electrical wiring is made through the proper opening for cabes 
located in the plastic plate. 
In order to reach the wiring zone, remove the plastic plate on 
the  cover  as  indicated  in  Fig.  2  and  remove  the  screw 
beneath.  
Make electrical wirings as indicated in Fig. 3, 4, 5, 6, 7 or 8. 
Please  note  that  the  intervention  delay  is  strictly  dependant 
both on a correct positioning of the detector in the room and to 
the type of gas to be detected. 
In  case  of  'heavy'  gases  as  for  LPG  an  installation  in  low 
places  is  advisable  (roughly  30  cm  from  floor),  instead  for 
’light’ gases as for methane in high places (roughly 30 cm from 
ceiling). 

Please  avoid  to  install  this  gas  detector  in  any  position  in 
which its operational features could be compromised, such as 
the following: 
-  in an enclosed space (e.g. in a cupboard or behind a curtain; 
-  directly above a sink; 
-  above or close to the cooking board; 
-  next to a door or window; 
-  next to an extractor fan; 
-  in an area where the temperature may drop below - 10°C or 

 40°C; 

-  where dirt and dust may block the sensor; 
-  in a damp or humid location. 

Do  not  use  the  following  substances  in  the device  immediate 
adjacency: 
-  alcohol, fuels 
-  solvents and diluents 
-  adhesives, silicones products and colours 
-  cleaning detergents 
-  perfumes 
-  spray products in general 
Clean the device only using a cloth damped with water. 

In order to grant a real safety, a gas detector must be coupled 
to  an  electro-valve  capable  of  blocking  the  gas  flow  in  the 
event of an alarm. 
Both the gas unit and the solenoid valve must comply with the 
law prescriptions in force in the country concerned. 

These electro-valves can be coupled to detector: 
-  230V~ normally open electro-valve 
-  230V~ normally closed electro-valve 
-  12V= normally open electro-valve, low absorption 

In order to check the proper efficiency of the device sensor a 
specific test gas bottle (optional) is made available which must 
be used according to the enclosed instructions. 

WARNING: Any other method for testing, such as the use 
of  cigarette  lighters,  flammable  vapours  etc.,  can  lead  to 
wrong  conclusions  as  well  as  to  the  irreversible  damage 
of the sensor itself. 

WARNING 

The  installer  is  reminded  to  fill in  and  apply  the sticking label 

INSTALLATION 

N

.O

.

E.V. N.O.

230V~

12V=

CO

N

.C

.

FAN

1

C

O

M

2

3

N

.O

.

5

4

C

O

M

N

.C

.

CH4

2

3

0

V

~

O

U

T

9

N

7

6

8

L

10

G

N

D

LOW POWER

Fig. 6

:

 

Wiring  diagram  with  a  manual  reset  Normally  Open 
12V=  electro-valve  and  230V~  fan.  Use  only  low 
absorption electro-valves. 

2

3

0

V

~

C

O

M

FAN
230V~

N

.C

.

2

1

C

O

M

3

N

.O

.

E.V. N.C.

230V~

N

.O

.

6

4

5

N

.C

.

7

N

8

9

L

O

U

T

10

G

N

D

CO

CH4

Fig. 8

:  Wiring  diagram  with  manual  reset  Normally  Closed 

230V~ electro-valve and 230V~ fan. 

N

.O

.

1

2

3

4

5

N

.C

.

C

O

M

CO

C

O

M

N

.O

.

N

.C

.

CH4

9

7

6

8

10

2

3

0

V

~

12V=

E.V. N.O.

LOW POWER

N

L

O

U

T

G

N

D

Fig. 5

:  Wiring  diagram  with  a  manual  reset  Normally  Open 

12V= electro-valve and 230V~ power supply. Use only 
low absorption electro-valves. 

C

O

M

230V~

230V~

2

3

0

V

~

E.V. N.O.

N

.C

.

N

.O

.

1

2

FAN

N

.C

.

4

3

C

O

M

6

5

N

.O

.

8

7

N

L

G

N

D

10

9

O

U

T

CH4

CO

Fig. 7

:  Wiring  diagram  with  manual  reset  Normally  Open 

230V~ electro-valve and 230V~ fan. 

CH4

N

.C

.

E.V. N.C.

230V~

230V~

C

O

M

N

.O

.

3

2

1

FAN

N

.C

.

4

C

O

M

CO

2

3

0

V

~

6

5

N

.O

.

8

7

N

L

9

10

O

U

T

G

N

D

Fig. 4: 

Wiring  diagram  with  manual  reset  Normally  Closed 
230V~ electro-valve and 230V~ fan. 

N

.O

.

230V~

FAN

1

2

N

.C

.

C

O

M

E.V. N.O.

230V~

3

4

C

O

M

5

6

N

.C

.

N

.O

.

10

G

N

D

2

3

0

V

~

L

7

8

N

9

O

U

T

CO

CH4

Fig. 3: 

Wiring  diagram  with  manual  reset  Normally  Open 
230V~ electro-valve and 230V~ fan. 

WIRING DIAGRAM

 

a

a

a

a

 

WARNING

THE  INSTALLATION  OF  THE  DETECTOR 
D O E S N ' T  

E X E M PT  

F R O M  

T H E 

OBSERVANCE  OF  ALL  RULES  ABOUT 
THE CHARACTERISTICS, INSTALLATIONS 
AND THE USE OF THE GAS DEVICES, THE 
VENTILATION  OF  THE  ROOMS  AND  THE 
EMISSIONS  OF  THE  PRODUCTS  OF  THE 
COMBUSTION  PRESCRIBED  FROM  UNI 
STANDARDS  AND  THE  PROVISIONS  OF 
THE LAW. 

60mm

Fig. 2

: Installation example. 