15
4.
To exit press ‘
OK
’
‘rEG’ REGULATION SENSOR CHOICE SETTING
This parameter sets whether the room temperature regulation is
made based on the chronostat internal sensor or the remote sensor,
wired at terminals 8 and 9.
For this parameter setting please find these directions:
1.
Select parameter ‘
rEG
’ then press key ‘
OK
’
2.
The display shows ‘
In
‘ or ‘
Out
‘.
3.
Press keys
‘ ’ and ‘ ‘
to change the value (
In
: internal sensor
-
Out
: remote sensor); each change is automatically stored in memory.
4.
Press key ‘
OK
’ to quit or wait 10 seconds without pressing any key.
WARNING: When the regulation is set according to the remote
sensor ‘ Out ‘ and in case this sensor is missing or broken, the
temperature regulation will be performed according to the
internal sensor, even if the parameter remains set on ‘ Out ‘.
SHUTDOWN - ANTI-FREEZE FUNCTION
To switch off the timer thermostat press ‘
o
‘.
The display will show the word ‘OFF’ and the ‘
o
‘ symbol.
If the timer thermostat was set in the heating mode, the antifreeze
function will be enabled and the ‘
‘ symbol will appear on the
display; in such a case the room temperature will be controlled
according to the programmed antifreeze temperature set point.
MANUAL OPERATION
Pressing the ‘
‘ button will cause the ‘
‘ symbol to appear on the
display and the timer thermostat will control the room temperature
according to the current comfort mode setting selected by means of knob
memorized
.
4.
To exit press the ‘
OK
’ button or else wait 10 seconds without
pressing any button.
‘OFS1’ INTERNAL SENSOR OFFSET SETTING
With this parameter it is possible to correct the temperature reading
of the internal sensor by ±5°C in order to correct any systematic
reading errors due to the positioning of the chronostat in areas
unsuitable for measuring the room temperature. The device leaves
the factory with the Offset set at 0.0°C.
To adjust the Offset value for the internal sensor, carry out the following steps:
1.
Select the ‘
OFS1
’ parameter and press the ‘
OK
’ button.
2.
The display will show the previously set Offset temperature.
3.
Press buttons
‘ ’ and ‘ ‘
to modify the setting (range:
-5.0°C .. +5.0°C);
every change will be automatically stored
in memory
.
4.
To exit press ‘
OK
’
‘OFS2’ REMOTE SENSOR OFFSET SETTING
With this parameter it is possible to correct the temperature reading
of the remote sensor by ±5°C in order to correct any systematic
reading errors due to the positioning of the remote sensor in areas
unsuitable for measuring the room temperature. The device leaves the
factory with the Offset set at 0.0°C.
To adjust the Offset value for the internal sensor, carry out the following steps:
1.
Select the ‘
OFS2
’ parameter and press the ‘
OK
’ button.
2.
The display will show the previously set Offset temperature.
3.
Press buttons
‘ ’ and ‘ ‘
to modify the setting (range:
-5.0°C .. +5.0°C);
every change will be automatically stored
in memory
.
ITALIANO
DEUTSCH
FRANÇAIS
ESPAÑOL
PORTUGUÊS
ENGLISH