background image

 

2

 

 

DESCRIPTION

 

 
 

The  SEI  DC-UPS  24VDC  is  a  compact  unit  designed  to  service  a  wide  range  of 
customer  equipment  requiring  battery-backed  24  VDC  power.  The  DC-UPS 
provides 125 Watts (4.5A), 250 Watts (9.0 Amps) or 320W (11.5 Amps) of rectifier 
power. The distribution is provided on the right side of the unit. Commercial power 
is applied to the left side of the unit. The SEI DC-UPS can be mounted on a wall or 
on a 19-inch rack. Optionally, SNMP communications via the Power Management 
Package is available. Also, an optional  Alarm Contacts Board is available. 

 

 

 

Three output distribution modules are available. The ‘M’ module contains two, 
individually fused 8-pin Molex

 Minifit

 connectors.  The ‘A’ module contains 

two, individually fused 2-pin AMP

 Mat-N-Lok

 connectors.  The ‘P’ module 

features two sets of individually fused 10-32 studs.  Customer-specified output 
modules are available.   
 
The DC UPS comes equipped with field replaceable, non spillable, sealed lead 
acid battery packs. Circuitry within the DC UPS monitors and periodically tests 
the condition of the batteries and displays the results via external LED’s as well as 
over the network, when equipped with the optional Power Management Package. 
The DC UPS also utilizes a Low Voltage Disconnect, (LVD), circuit that prevents 
damage to the Battery Packs during an extended AC outage 
 
 

 
 
 

Summary of Contents for SEI-125

Page 1: ...Installation and Operations Manual SEI DC UPS 24VDC SEI Incorporated 5115 Pegasus Court Suite Q Frederick Md 21704 Phone 301 694 9601 Fax 301 694 9608 Email Info seipower com Web http www seipower com ...

Page 2: ...ations 3 Environmental Specifications 3 Safety Information 4 Installation Instructions 5 Startup and Checkout 7 Theory of Operation 8 Remote Alarm Option 10 Power Management Package Option 10 Repair and Maintenance 11 Output Module A 12 Output Module M 13 Output Module P 14 ...

Page 3: ...tput distribution modules are available The M module contains two individually fused 8 pin Molex Minifit connectors The A module contains two individually fused 2 pin AMP Mat N Lok connectors The P module features two sets of individually fused 10 32 studs Customer specified output modules are available The DC UPS comes equipped with field replaceable non spillable sealed lead acid battery packs C...

Page 4: ...5 00 Inches Height 14 00 Inches Weight 32 lbs Battery Capacity 18Ahr Fuse 3AG 15A Littlefuse 0326015 or Equivalent SEI 250 Electrical Specifications Input Voltage 100 264 VAC Frequency 50 60 Hz Current 2 6 Amps Typical 115 Vac input 250 W output 5 0 Amps Max Output Voltage 21 28VDC Current 10 0 amps Mechanical Dimensions Width 19 00 Inches Depth 5 00 Inches Height 14 00 Inches Weight 32 lbs Batter...

Page 5: ...TAL SPECIFICATIONS Temperature Operating 0 C to 40 C Storage 20 C to 50 C Humidity 0 95 non condensing Thermal Load 100 BTU hr max SAFETY INFORMATION Always insure that the person assigned to the job can perform the job safely Always lift all equipment properly Always disconnect commercial power and remove the battery fuse before working on the unit Always replace the batteries with batteries of t...

Page 6: ...5 Service to the DC UPS should be performed by a qualified technician ...

Page 7: ...er for damage If damaged request that the carrier inspect the shipment Unpack the inner container from the shipping container and remove the unit from the packaging Inspect the unit for visible damage If a claim for damages is to be made it should be filed promptly with the transportation company In addition notify SEI within two days of delivery SEI will advise the customer of any further procedu...

Page 8: ...rd or equivalent is required The DC UPS should be fastened to the backboard using number ten wood screws A number 27 drill can be used to provide a pilot hole for the screws All of the screws should be tightened with a torque of 30 in lb minimum and 34 in lb maximum The unit should be mounted vertically in a clean dry area where the ambient temperature does not exceed 40 C 104 F It is important th...

Page 9: ...tioned Attach the supplied AC power cord to the left side of the DC UPS Plug in the DC UPS power cord into the commercial AC outlet made available for this unit When power is first applied the unit should display a flashing green Battery Charge Status LED and a solid green Battery Test Status LED Connect the user equipment to the DC UPS output connectors located on the right side of the unit Verif...

Page 10: ...f power The input of the rectifier is fused for protection System Controller LVD The System Controller has the following functions Distribution of the DC power Battery charge voltage and current control and monitoring Battery Low Voltage Disconnect Function LVD Battery charge and test status indicators Automatic and manual battery test Local and Remote Alarms optional LED Indicators There are two ...

Page 11: ...ry Test is disabled for 5 minutes following a Battery Test In both cases the Wait Then Test indication is displayed Low Voltage Disconnect Function The low voltage disconnect function will disconnect the battery when the battery voltage drops below a 21 Vdc This is done to prevent deep discharge of the batteries which can adversely affect battery life Both internal and external batteries are disco...

Page 12: ...nnection 5 No connection 6 AC Fail NC AC Failure has occurred 7 AC FAIL NO Operating Normally 8 AC Fail Common Figure 2 Power Management Package SEI s Power Management Package PMP for the SEI DC UPS provides a variety of functions necessary to monitor and control output power to DC powered devices as well as maximize the efficiency and reliability of the power systems and battery backup Ethernet c...

Page 13: ...ommended that a quality digital voltmeter DVM be used Rectifier Adjustment Procedure The rectifier should only be adjusted with the nominal system load connected Connect a DVM to one of the external battery connectors Measure the voltage it should be between 27 0 and 27 7 volts If the measured voltage is outside of this range perform the following steps 1 Remove the battery fuse located on the rig...

Page 14: ...nnector 1 480698 0 Mating Pin 350873 3 Wire Gauge 14 18 AWG Fuse GMT 15A Cooper Bussmann or Equivalent Note The fuse is sized to provide full output power from each connection If multiple connections are used the fuse can be re sized to limit current at a lower value 48V RTN 48V FUSE 1 FUSE 2 OUTPUT MODULE A Layout and Polarity ...

Page 15: ...2085 Mating Pin 39 00 0078 Strain relief 15 04 9343 Wire Gauge 14 18 AWG Fuse GMT 10A Cooper Bussmann or Equivalent Note The fuse is sized to provide full maximum power from each connection If multiple connections are used the fuse can be re sized to limit current at a lower value 24V 24V RTN 24V 24V RTN OUTPUT MODULE M Layout and Polarity ...

Page 16: ...s fused Fuses SEI 320 24 SEI 250 24 ATO 15A 0257015 Littlefuse or Equivalent SEI 125 24 ATO 7 5A 0257007 Littlefuse or Equivalent Note The fuse is sized to provide maximum output power from each connection If multiple connections are used the fuse can be re sized to limit current at a lower value PORT 1 PORT 2 48V 48VRTN 48V 48VRTN ...

Reviews: