10
System Status Section:
LED
LED state
Indication
System
Voltage
Solid Green
Operating normally
Slow Flash Red
(once per
second)
System Voltage below optimal battery charge voltage.
If Battery Charge Status LED is also flashing, unit is
operating on battery
Fast Flash Red
(5 times per
second)
Battery almost depleted – less than 10% of battery life
remains
Temperature
Solid Green
Operating Normally
Flashing Yellow Warning Internal temperature > 40
C
Flashing Red
Fault - Internal temperature > 50
C – Battery charging
inhibited.
Overload
Solid Green
Operating Normally
Flashing Yellow Total Output power exceeds the user-settable
UTILIZATION ALARM THRESHOLD percentage
Flashing Red
Total Output power exceeded available power. In units
with multiple output ports, the lowest priority ports will
be SHUTDOWN until the OVERLOAD is removed.
Rectifier
Status
Solid Green
Operating Normally
Flashing Red
One of the Rectifiers has failed.
Battery Status Section:
LED
LED state
Indication
Battery
Charge
Status
Solid Green
Battery fully charged
Flashing Green
Battery charging
Flashing Red
Unit operating on battery power
Battery Test
Status
Off
Battery under Test
Green
Battery Test Pass – Battery OK
Slow Flash Red
(5 times per
second)
Battery Test Fail – Replace Battery Packs.
Fast Flash Red
(5 times per
second)
Battery Test not Allowed
Manual
Battery Test
Switch
Push to Test
Battery Test not allowed when battery is charging,
when there is a system fault condition, or within one
minute of a previous battery test