TB XRI1-IE 11.01 E
9
3.2.4
Parameter settings (see chapter 6)
Device type XRI1-IE
Symbol
Function
Unit
Setting range
I>
Pickup value for phase overcurrent element
X In
0.20...4.0 (EXIT)
CHAR I>
Trip characteristic for phase overcurrent element
DEFT; NINV; VINV; EINV
tI>
Tripping delay (factor) for phase overcurrent ele-
ment
s
DEFT 0.03...260 (EXIT)
INVS 0.05...10.0 (EXIT)
I>+CHAR I>+tI>
Reset Mode for inverse-characteristics
s
0s/60s
I>>
Pickup value for overcurrent high set element
x In
1.00...40.0 (EXIT)
tI>>
Trip delay for overcurrent high set element
s
0.03...2.00 (EXIT)
IE>
Pickup value for earth fault low set element
x In
0.01...2.00 (EXIT)
Warn/trip
Warning/tripping setting
Warn/trip
CHAR IE>
Tripping characteristic for earth fault overcurrent
element
DEFT; NINV; VINV; EINV
tIE>
Trip delay (factor) for earth fault low set element
s
DEFT 0.03...260 (EXIT)
INVS 0.05...10.0 (EXIT)
IE>+CHAR IE>+tIE>
Reset modus for AMZ characteristic
s
0s/60s
IE>>
Pickup value for earth fault high set element
x In
0.01...15.0 (EXIT)
tIE>>
Trip delay for earth fault high set element
s
0.03...2.00 (EXIT)
tCBFP
Circuit breaker failure protection
s
0.10...2.00 (EXIT)
FN
Rated frequency
Hz
50 Hz/60 Hz
LED Flash
LED blinking after excitation
Hz
FLSH/NOFL
RS
Slave address for serial interface
1...32
RS
Baud rate der of the serial interface
1)
Bd
1200; 2400; 4800;
9600
RS
Parity bit of the serial interface
1)
Even; odd; no
1)
only Modbus protocol
Table 3.2: Parameter values
Additional parameters:
Relay-type XRI1-IE
Blocking mode
Relay parameterizing
Fault recorder
Table 3.3