![Seg XRI1-IE Manual Download Page 35](http://html1.mh-extra.com/html/seg/xri1-ie/xri1-ie_manual_1233473035.webp)
TB XRI1-IE 11.01 E
35
Setting list
XRI1-IE
Note !
All settings must be checked at site and should the occasion arise, adjusted to the object / item to be protected.
Project:
SEG job.-no.:
Function group: =
Location: +
Relay code: -
Relay functions:
Password:
Date:
Setting of parameters
Function
Unit
Default
settings
Actual
settings
I>
Pickup value for phase overcurrent
x I
N
0.20
CHAR I>
Tripping characteristic for phase overcurrent element
DEFT
tI>
Trip delay for phase overcurrent element
s
0.03
I>+CHARI>+tI>
Reset Mode for inverse characteristics
s
I>>
Pickup value for overcurrent high set element
x I
N
1.00
tI>>
Trip delay for overcurrent high set element
s
0.03
I
E>
Pickup value for earth fault low set element
x I
N
0.01
WARN/TRIP
Warning/tripping setting
TRIP
CHAR I
E
Tripping characteristic for earth fault overcurrent ele-
ment
DEFT
tIE>
Trip delay for earth fault overcurrent element
s
0.03
IE>+CHARIE>+tIE>
Reset mode for inverse characteristics
IE>>
Pickup value for earth fault high set element
x I
N
0.01
tIE>>
Trip delay for earth fault high set element
s
0.03
t
CBFP
Circuit breaker failure protection
s
0.20
f
N
Nominal frequency
Hz
50
LED Flash
LED blinking after excitation
FLSH
RS
Slave Address of serial interface
1
RS
Baud rate of the serial interface *
Bd
9600
Parity bit of the serial interface *
even
* only Modbus Protocol