Electro-Pneumatic Positioner SP 520 Series
_________________________________________________________________________________________________________
Ver 1.20
46
SHIN HWA Eng.Co.,Ltd.
6-5 A
UTO/MANUAL conversion screw’s cleaning
- If the air pressure value of the regulator is output as OUT1 regardless of the supply pressure
input signal, the hole of the auto/manual switching screw located on the pilot valve is clogged
by foreign substances such as dirt and oil, so it must be cleaned.
- Loosen the lock screw on the upper part of the pilot valve, remove the auto/manual switching
screw, make a hole with a steel wire of 0.3mm or less, wash it, and assemble it again.
7. Error Check and solution method
7-1 Basic check point when positioner does not operate
-. Supply pressure check point : Over Min 1.4 kgf/cm
2
-. Input signal check : 4~20mA
-. Check ZERO, SPAN adjustment status.
-. Check whether air comes out well from the nozzle of the torque motor
-. Check Feedback lever installation status.
Fig 6-
5 : AUTO/MANUAL conversion screw’s cleaning