91
Protection parameters: Mains decoupling
Relay type
Default
settings
Actual
settings
Symbol LED
Function
Unit
M
RG
3
M
RG
3
-I
M
RG
3
-U0
M
RG
3
-IE
M
RG
3
-IU0
M
RG
3
-IER
Set 1
Set 2
Set1
Set 2
U<
U+1+<
Pickup value for the
1
st
under voltage element
(low set)
%
X X X X X X 90
t
U
<
U+1+<+t>
Tripping delay for the
1
st
under voltage element
s
X X X X X X 0.04
U<<
U+2+<
Pickup value for the
2
nd
under voltage element
(high set)
%
X X X X X X 80
t
U
<<>
U+2+<+t>
Tripping delay for the
2
nd
under voltage element
S
X X X X X X 0.04
U>
U+1+>
Pickup value for the
1
st
overvoltage element (low
set)
%
X X X X X X 110
t
U
>
U+1+>+t>
Tripping delay for the
1
st
overvoltage element
S
X X X X X X 0.04
U>>
U+2+<
Pickup value for the
2
nd
overvoltage element
(high set)
%
X X X X X x 120
t
U
>>
U+2+>+t>
Tripping delay for the
2
nd
overvoltage element
S
X X X X X X 0.04
T
f
Frequency measuring repe-
tition in periods
perio-
ds
X X X X X X 4
f
1
<(>)
f+1+<(>)
Pickup value for frequency
element 1
Hz
X X X X X X 4800
t
f1
>
f+1+<(>)+t>
Tripping delay for
frequency element 1
S
X X X X X X 0.1
f2<(>)
f+2+<(>)
Pickup value for frequency
element 2
Hz
X X X X X X 4900
t
f2
>
f+2+<(>)+t>
Tripping delay for frequency
element 2
S
X X X X X X 0.1
f3<(>)
f+3+<(>)
Pickup value for frequency
element 3
Hz
X X X X X X 5100
t
f3
>
f+3+<(>)+t>
Tripping delay for frequency
element 3
S
X X X X X x 0.1
df
/df
Pickup value for rate of fre-
quency df/dt in
Hz/s
X X X X X X EXIT
dt
1-3/dt
Measuring repetition for
df/dt
perio-
ds
X X X X X X 4
_1/3
1-3/dt
Vector surge tripping logic
X X X X X X 1PH
/df
Pickup value for vector
surge
°
X X X X X X 2.0
U
B
>
f+
/df
Voltage threshold for fre-
quency, df/dt and vector
surge measuring
%
X X X X X X 20