46
TD_MRN3-3_08.06_GB
Setting list
MRN3-3
Project:
SEG
job.-no.:
Function group: =
Location: +
Relay code: -
Relay functions:
Password:
Date:
All settings must be checked at site and should the occasion arise, adjusted to the object/item to be protected.
Setting of the parameters
System parameter
Function
Unit
Default settings
Actual
settings
U
prim
/U
sek
Voltage transformer ratio
X
SEK
∆
/Y
input transformer connection
DELT
f
N
Rated
frequency
Hz f=50
∆Θ
/df
Selection vector surge or df/dt
dfdt
LED blinking after pick-up
FLSH
Protection parameter
Function
Unit
Default settings
Actual
settings
Voltage limit curve 1
Set1/Set2 Set1
Set2
U<Start
Start point of the characteristic curve 1
V 85/195/340/586*
Char 1
Selection symmetric or asymmetric fault
ALL
Char 1
Function of characteristic 1
warn
U<1
1. Char. point_value 1
V 45/104/180/310*
1. Char. point_value 2 (not changeable)
s
- / -
U<2
2. Char. point_value 1
V 45/104/180/310*
U<2+t>
2. Char. point_value 2
s 0,16
U<3
3. Char. point_value 1
V 70/161/280/482*
U<3+t>
3. Char. point_value 2
s 0,18
U<4
4. Char. point_value 1
V 70/161/280/482*
U<4+t>
4. Char. point_value 2
s 0,70
U<5
5. Char. point_value 1 (U-voltage band)
V 85/195/340/586*
U<5+t>
5. Char. point_value 2 (End time)
s 1,50
tR
Permissible release time for
characteristic curve 1
s 0,10
Voltage limit curve 2
U<Start
Start point of the characteristic curve 2
V 85/195/340/586*
Char 2
Selection symmetric or asymmetric fault
ALL
Char 2
Function of characteristic 2
trip
U<1
1. Char. point_value 1
V 15/34/60/104*
1. Char. point_value 2 (not changeable)
s
- / -
U<2
2. Char. point_value 1
V 15/34/60/104*
U<2+t>
2. Char. point_value 2
s 0,66
U<3
3. Char. point_value 1
V 85/195/340/586*
U<3+t>
3. Char. point_value 2
s 3,00
* Settings depending on the rated voltage 100 V/230 V/400 V or 690 V