TD_MRN3-3_08.06_GB
17
5
Operation and Settings
5.1 Display
Function
Display shows
Pressed pushbutton
Corresponding LED
Normal operation
SEG
Measured operating values
Actual measured value
Min. and max. values of
voltage, frequency and
vector surge and df/dt
<SELECT/RESET> one time
for each value
L1, L2, L3,
f, min, max
∆Θ
/
df
Transformer ratio of the CT’s
(SEK) 1.01–6500=prim <SELECT/RESET><+><->
L1, L2, L3
Setting values:
star/delta connection
Y/DELT <SELECT/RESET><+><->
∆
/Y
Selection vector surge or df/dt
dPhi/dfdt
<SELECT/RESET><+><->
∆Θ
/df
Parameter set change-over
switch/ext. triggering of FR
SET1, SET2, B_S2,
R_S2, B_FR, R_FR, S2_FR
<SELECT/RESET><+><-> P2
Switch-over LED flash
No LED flash
FLSH
NOFL
<SELECT/RESET><+><->
Starting point of the limit curve 1
Setting value in Volt
<SELECT/RESET><+> <->
one time for each value
Char1+U<Start
Selection symmetrical, asymmetri-
cal or general fault
SYM/ASYM/ALL <SELECT/RESET><+><->
Char1
Under voltage limit curve 1
Function
warn/trip <SELECT/RESET><+><->
Char1
1. Char. point_value 1 (U<1)
1. Char. point_value_2
Setting value in Volt
Setting value in seconds
<SELECT/RESET><+><->
set to 0s (fixed)
Char1+U<1
2. Char. point_value 1 (U<2)
2. Char. point_value_2 (tU<2)
Setting value in Volt
Setting value in seconds
<SELECT/RESET><+> <->
one time for each value
Char1+U<2
Char1+U<2+t>
3. Char. point_value 1 (U<3)
3. Char. point_value_2 (tU<3)
Setting value in Volt
Setting value in seconds
<SELECT/RESET><+> <->
one time for each value
Char1+U<3
Char1+U<3+t>
4. Char. point_value 1 (U<4)
4. Char. point_value_2 (tU<4)
Setting value in Volt
Setting value in seconds
<SELECT/RESET><+> <->
one time for each value
Char1+U<4
Char1+U<4+t>
5. Char. point_value 1 (U<5)
5. Char. point_value_2 (tU<5)
Setting value in Volt
Setting value in seconds
<SELECT/RESET><+> <->
one time for each value
Char1+U<5
Char1+U<5+t>
Permissible release time for under-
voltage limit curve 1
Setting value in seconds <SELECT/RESET><+> <->
one time for each value
Char1+tR
Starting point of the limit. curve 2 Setting value in Volt
<SELECT/RESET><+><->
one time for each value
Char2+U<Start
Selection symmetrical, asymmetri-
cal or general fault
SYM/ASYM/ALL <SELECT/RESET><+><->
Char2
Under voltage limit curve 2
Function
warn/trip <SELECT/RESET><+><->
Char2
1. Char. point_value 1 (U<1)
1. Char. point_value_2
Setting value in Volt
Setting value in seconds
<SELECT/RESET><+><->
set to 0s (fixed)
Char2+U<1
2. Char. point_value 1 (U<2)
2. Char. point_value_2 (tU<2)
Setting value in Volt
Setting value in seconds
<SELECT/RESET><+> <->
one time for each value
Char2+U<2
Char2+U<2+t>
3. Char. point_value 1 (U<3)
3. Char. point_value_2 (tU<3)
Setting value in Volt
Setting value in seconds
<SELECT/RESET><+> <->
one time for each value
Char2+U<3
Char2+U<3+t>
4. Char. point_value 1 (U<4)
4. Char. point_value_2 (tU<4)
Setting value in Volt
Setting value in seconds
<SELECT/RESET><+> <->
one time for each value
Char2+U<4
Char2+U<4+t>
5. Char. point_value 1 (U<5)
5. Char. point_value_2 (tU<5)
Setting value in Volt
Setting value in seconds
<SELECT/RESET><+> <->
one time for each value
Char2+U<5
Char2+U<5+t>
Permissible release time for under-
voltage limit curve 1
Setting value in seconds <SELECT/RESET><+> <->
one time for each value
Char2+tR
Function of the 1
st
voltage element U</U>
<SELECT/RESET><+><->
U1
Voltage threshold value U1
Tripping time delay tU1
Setting value in Volt
Setting value in seconds
<SELECT/RESET><+> <->
one time for each value
U1
U1+t>
Function of the 2
nd
voltage element U</U>
<SELECT/RESET><+><->
U2
Voltage threshold value U2
Tripping time delay tU2
Setting value in Volt
Setting value in seconds
<SELECT/RESET><+> <->
one time for each value
U2
U2+t>
Function of the 3
rd
voltage element U</U>
<SELECT/RESET><+><->
U3