Three Phase Duplex Control Panel 

Installation and Operation Manual

                 OSD3P-30XX

SEE WATER, INC.

Remote Monitoring Dry Contacts:

• 

Normally Open dry contacts for high oil, high level, 
pump run, and pump fault. Rated 0-60V AC/DC

www.seewaterinc.com 

951.487.8073 • 888.733.9283 • [email protected] 

22220 Opportunity Way, Suite 101 •  Riverside,  CA 92518

 

Oil Smart® Duplex System

The Oil Smart® OSD3P system incorporates pump controls and alarm 

sensors that differentiate between oil and water, allowing companies to 

responsibly discharge the water without the risk of pumping oil. Installation 

of the OSD3P keeps companies in compliance with Elevator Code      

ASME A17.1 and State/Federal regulations while reducing the risk of adverse 

publicity, fines, and expensive cleanup cost.

Model

FLA Range

OSD3P-3021

(1.0-1.6 FLA)

OSD3P-3022

(1.6-2.5 FLA)

OSD3P-3023

(2.5-4.0 FLA)

OSD3P-3024

(4.0-6.3 FLA)

OSD3P-3025

(6.0-10.0 FLA)

OSD3P-3026

(9.0-14.0 FLA)

OSD3P-3027

(13.0-18.0 FLA)

OSD3P-3028

(17.0-23.0 FLA)

OSD3P-3029

(20.0-25.0 FLA)

OSD3P-3030

(24.0-32.0 FLA)

OSD3P-3031

(30.0-40.0 FLA)

OSD3P-3032

(37.0-50.0 FLA)

OSD3P-3033

(48.0-65.0 FLA)

Page 1-3

IM 804 REV. 02/20

Panel Installation:

1.  Caution: To maintain the NEMA 4X rating, make 

all wiring connections with seal tight cable grips or 

conduit connections.

2.  Run pump cable and Oil Smart® cables through 

conduit. Make field connections as shown on wiring 

schematic.

3.  Run power line conductor through conduit. Wire to 

terminals per enclosed schematic. 

4.  Branch circuit protection to be provided by 

installer.

5.  Panel circuit breakers are closed.

6.  Mount Oil Smart® pump switch and Liquid Smart® 

alarm sensor with provided mounting hardware to 

pump discharge pipe. The ‘OFF’ sensor of the Oil 

Smart® pump switch shall be positioned at least 3” 

above the impeller of the pump.

7.  Mounting of the High Water Lag Sensor is 

application driven and is to be placed where high 

demand pump is to be activated.

8.  Mounting of the Liquid Smart® sensor is 

application driven and is to be placed where a high 

liquid is deemed necessary. The Liquid Smart® 

sensor is typically mounted 3” - 6” above the Oil 

Smart® pump switch.

9.  Connect service conductors 208/240/480V to 

proper location

Enclosure Mounting: NEMA 4X RATED

Mounting Brackets - A mounting bracket and screw pack are provided 

with the premium enclosures. To assemble, turn the enclosure upside down 

on a flat surface, place the mounting bracket over the square boss either 

horizontally or vertically, and fasten the mounting bracket with the 1/4”-20 

x 0.5 SS, countersunk phillips drive screws or vertically, with the mounting 

brackets in any config., using any acceptable fastening technique.

Covers/Doors - Covers/doors have a gasket pre-assembled to seal against 

the base.

Note: The control panel should not be mounted in a location that may be 

subject to submersion.