GC1100
SEDEMAC
Page | 27
Level 0
Level 1 (On
screen)
Level 2 (On screen) *
Parameters (On screen)
Over-frequency Shutdown
(OVER FREQ SHUTDOWN)
Disable/Enable
Over-frequency Shutdown
Threshold
(OF SHUTDWN THRESHLD)
26.0 – 75.0 Hz
Over-frequency Warning
(OVER FREQ WARNING)
Disable/Enable
Over-frequency Warning
Threshold
(OF WARNING THRESHOLD)
25.0 – 74.0 Hz
Current
Monitoring
(CURRENT
MONITOR)
CT Ratio
(CT RATIO)
0 – 8000 / 5
Over-current Action
(OVER CURR ACTION)
None/Notification/Warning
/Electrical Trip/Shutdown
Over-current Threshold
(OVER CURR THRESHOLD)
5 – 10000 Amp
Over-current Delay
(OVER CURR DELAY)
1 – 600 sec
CT Correction Factor
(Reserved)
0.900 – 1.100
CT Location
(CT LOCATION)
On Load Cable/On Alt
Output Cable
Load
Monitoring
(LOAD
MONITOR)
Generator Rating
(GEN RATING)
0 – 8000 kW
Over-load Action
(OVERLOAD ACTION)
None/Notification/Warning
/Electrical Trip/Shutdown
Over-load Threshold
(OVERLOAD THRESHOLD)
50 – 150 %
Over-load Monitoring Delay
(OVERLOAD MON DELAY)
1 – 600 sec
Unbalanced Load Action
(UNBAL LOAD ACTION)
None/Notification/Warning
/Electrical Trip/Shutdown
Unbalanced Load Threshold
(UNBAL LOAD THRESHOLD)
5 – 200 %
Unbalanced Load Delay
(UNBAL LOAD DELAY)
1 – 600 sec
Extended Over-Load Trip
(EXT OL TRIP)
Disable/Enable
Ext Over-load Trip Threshold
(EXT OL THRESHOLD)
50 – 150 %
Mains
(MAINS)
Configuration
(MAINS
CONFIG)
Mains Monitoring
(MAINS MONITORING)
Disable/Enable
Mains AC system
(MAINS AC SYSTEM)
1 Phase/3 Phase
Phase Reversal Detection
Disable/Enable