GC1100
SEDEMAC
Page | 21
7.1
List of Configurable Parameters
Following table gives a brief overview of configurable parameters in GC1100 controller
*
Level 2 names in sentence case are written how they display on Smart Config GUI and names in
bracket with capital case are written how they display on controller.
Table 20: Configurable parameters
Level 0
Level 1 (On
screen)
Level 2 (On screen) *
Parameters (On screen)
Module
(MODULE)
General
(GENERAL)
Profile Name
(PROFILE NAME)
profile 1
Power On Mode
(POWER ON MODE)
Manual/Auto
Power On Lamp Test
(POWER ON LAMP TEST)
Disable/Enable
Deep Sleep Mode
(DEEP SLEEP MODE)
Disable/Enable
Load Histogram
(LOAD HISTOGRAM)
Disable/Enable
Auto-Clear Warning Alarm
(WARNING AUTO CLEAR)
Disable/Enable
Language
(LANGUAGE)
English/Chinese
Display
(DISPLAY)
Contrast
(CONTRAST)
0 – 100 %
Power Save Mode
(POWER SAVE MODE)
Disable/Enable
Communication
(COMMUNICA
TION)
Communication Mode
(COMM MODE)
None/MODBUS –
SEDEMAC
Slave ID
(MODBUS SLAVE ID)
1 – 247
Baudrate
(MODBUS BAUDRATE)
1200/2400/4800/9600/
19200/38400/57600/115200
bps
Parity Bit
(PARITY)
None/Even/Odd
Auto Exercise
Event 1
(AUTO
EXERCISE-1)
Auto Exercise
(EVENT 1)
Disable/Enable
Event Occurrence
(EVENT OCCURENCE)
Daily/Weekly/Monthly
Event Day
(EVENT DAY)
Runs Every day/Week
Days/1 – 28
Start Time
(START TIME)
00:00 – 23:59 hour
Duration
(DG ON DURATION)
0-hour 1 min – 99 hour 59
mins
Load Transfer
(LOAD TRANSFER)
Disable/Enable