REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-05-11-T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER
–
FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
/ Email : [email protected]
Pages
8/9
Ref.
FT2419B ENG
Rev.
01
Date
02/2020
19
Modification of the output signal
4 mA
If a deviation is found on the 4mA output signal, this function is used to
adjust it. If the number is increased, the current is higher. If the number
is decreased, the current is lower.
Range
: 000_481_A
–
Value by default 191_A
NB
: always limit the lower value to 20 mA
20
Modification of the 20mA output
signal
If a deviation is found on the 20mA output signal, this function is used
to adjust it. If the number is increased, the current is higher. If the
number is decreased, the current is lower.
Range
: 191_1000_A
–
Value by default 909_A
21
Power supply position by default
Setting the position of the valve in the event of a power cut. This
manoeuvre will be carried out if the capacitor is sufficiently charged.
Possible values
:
KEEP
: unchanged position of the valve
ON
: opening of the valve
OFF
: valve closing
Value by default
: OFF
22
Response time
Used to set the response speed of the valve. The smaller the value, the
less sensitive the control. The bigger the value, the more sensitive it is.
Increase the value when the response speed is too low.
Setting range:
1x20x
–
Value by default
3x
23
Checking the feed signal
The actuator periodically tests its electrical power supply. A change of a
value will change the interval between two tests. In current use, there is
no need to change this parameter.