Sectoriel TCR 05T-KT32 Manual Download Page 5

REGULATING ELECTRICAL ACTUATOR  

+ RETURN BY SUPER-CAPACITOR TCR-05-11-T-KT  

 

Information given as an indication only, and subject to possible modifications 

 

 

SECTORIEL S.A.  
45 rue du Ruisseau 
38290 SAINT QUENTIN-FALLAVIER 

 FRANCE 

Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95 

www.sectoriel.fr

 / Email : [email protected] 

Pages 

5/9 

Ref. 

FT2419B ENG 

Rev. 

01 

Date 

02/2020 

 

CONTROL IN LOCAL MODE 

 

Press the K3 button for 5 seconds, until “K3” flashes at the top right of the screen. 

 

 

Enter the password “111” 

 

Press the K2 button to manoeuvre clockwise. The screen displays the % of opening. Release when the desired 
position is reached. 

 

Press the K3 button to manoeuvre anti-clockwise. The screen displays the % of opening. Release when the desired 
position is reached. 

 

 

PARAMETER SETTING MENU OF THE ACTUATOR 

The following functions can have their parameters set from the menu accessible on the screen: 

 

STEP 

TITLE 

FUNCTION AND VALUES 

Standby screen 

If the actuator did not receive any signal in the last 5 minutes, the 
screen switches to standby. Press any button for 5 s. Then reactivate 
the screen. 

Enter the password 

Press the “M” button for more than 5 s.

 

Enter the code “333”

  (use the keys K2 and K3) 

Press again the button “M”

 

 

Choice of language 

English or Mandarin 

 

Choosing the control signal 

Press “K3” 

to chose the control signal 

Possible signals: 4-20mA, 0-20mA, 2-10V, 0-10V 

Press “M” again to continue

 

 

Summary of Contents for TCR 05T-KT32

Page 1: ...doors and possibly outdoors under a shelter Manual control with a key AVAILABLE MODELS Supply voltages 230V AC 24V AC DC Control 4 20 mA 0 20 mA 2 10V 0 10V LIMITS OF USE MECHANICAL FEATURES Actuator TCR 05T KT32 TCR 11T KT32 Torques Nm 50 80 Voltage 24V AC DC 95 265V AC DC 24V AC DC 95 265V AC DC Adjustment signal 4 20 mA 0 20 mA 2 10V 0 10V Feedback signal 4 20 mA 0 20 mA 2 10V 0 10V Manoeuvring...

Page 2: ...ctoriel fr Email sectoriel sectoriel fr Pages 2 9 Ref FT2419B ENG Rev 01 Date 02 2020 CONSTRUCTION TCR 05T KT32 DIMENSIONS mm TCR 05T KT32 No Name Material No Name Material 1 Casing lid Plastic ABS 7 1 3 LCD display OLED 2 Position indicator Polycarbonate plastic 8 Rating plate PVC 3 Screw x 6 Ansi 304 9 Packing gland Nylon 4 Backup control stem Ansi 304 10 Hex key Steel 5 Gasket NBR 11 Key suppor...

Page 3: ...ectoriel sectoriel fr Pages 3 9 Ref FT2419B ENG Rev 01 Date 02 2020 CONSTRUCTION TCR 11T KT32 DIMENSIONS mm TCR 11T KT32 No Name Material No Name Material 1 Casing lid Plastic ABS 7 1 3 LCD display OLED 2 Position indicator Polycarbonate plastic 8 Rating plate PVC 3 Screw x 6 Ansi 304 9 Key support Plastic ABS 4 Backup control stem Ansi 304 10 Hex key Steel 5 Gasket NBR 11 X 2Packing gland Nylon 6...

Page 4: ...G DIAGRAM DESCRIPTION OF THE 1 3 LCD SCREEN 1 3 LCD angle without any blind spot strong luminosity automatic switching to the economy saving mode at the end of 5 minutes The control screen displays the set value and the of opening of the valve BU Neutral Blue RD Closing control Red Y G Earth Yellow Green BK Alarm return information Black GR Alarm return information Green PL 0 10V and 2 10V control...

Page 5: ...e desired position is reached Press the K3 button to manoeuvre anti clockwise The screen displays the of opening Release when the desired position is reached PARAMETER SETTING MENU OF THE ACTUATOR The following functions can have their parameters set from the menu accessible on the screen STEP TITLE FUNCTION AND VALUES 1 Standby screen If the actuator did not receive any signal in the last 5 minut...

Page 6: ...the band the lower the accuracy the narrower the band the more oscillating the system can be Setting range 0 1 to 9 9 Setting by default 0 8 8 Hysteresis adjustment This parameter setting is a prerequisite for the next YES adjustment is possible NO no adjustment is possible value by default 9 Hysteresis value If the previous parameter is YES it is possible to set the hysteresis value between 0 1 a...

Page 7: ...5 Setting the speed for the stroke This setting is used for setting a of the actuator stroke during which it will slow down before reaching the setpoint value position Range 1 20 Value by default 10 16 Braking time In order to increase the stability of the motor the motor will slow down after a short time before reaching its setpoint value position During current use this function is not useful Ra...

Page 8: ...mA output signal this function is used to adjust it If the number is increased the current is higher If the number is decreased the current is lower Range 191_1000_A Value by default 909_A 21 Power supply position by default Setting the position of the valve in the event of a power cut This manoeuvre will be carried out if the capacitor is sufficiently charged Possible values KEEP unchanged positi...

Page 9: ...fault ON 27 Exiting the menu Press K3 to exit the menu The system will switch back in the automatic checking mode TROUBLESHOOTING Defect met Cause of defect Method of solving Inactive actuator Non connected electrical grid Connect to the electrical grid Wrong voltage Check the actuator s voltage Motor overheating Check the torque on the valve Faulty connection Check the connection to the terminal ...

Reviews: