REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-05-11-T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER
–
FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
/ Email : [email protected]
Pages
5/9
Ref.
FT2419B ENG
Rev.
01
Date
02/2020
CONTROL IN LOCAL MODE
1
Press the K3 button for 5 seconds, until “K3” flashes at the top right of the screen.
2
Enter the password “111”
3
Press the K2 button to manoeuvre clockwise. The screen displays the % of opening. Release when the desired
position is reached.
Press the K3 button to manoeuvre anti-clockwise. The screen displays the % of opening. Release when the desired
position is reached.
PARAMETER SETTING MENU OF THE ACTUATOR
The following functions can have their parameters set from the menu accessible on the screen:
STEP
TITLE
FUNCTION AND VALUES
1
Standby screen
If the actuator did not receive any signal in the last 5 minutes, the
screen switches to standby. Press any button for 5 s. Then reactivate
the screen.
2
Enter the password
Press the “M” button for more than 5 s.
Enter the code “333”
(use the keys K2 and K3)
Press again the button “M”
3
Choice of language
English or Mandarin
4
Choosing the control signal
Press “K3”
to chose the control signal
Possible signals: 4-20mA, 0-20mA, 2-10V, 0-10V
Press “M” again to continue