Note:
if wireless detectors are in use, this field also specifies how often the system checks for supervision
signals, identifying each of the system’s wireless detectors. The system generates a local trouble signal
identifying the zone of any wireless detectors from which a signal is not received during the specified interval.
Control panel then sends the supervision report code to the CMS.
0,0 seconds
- supervision is disabled;
0,1 seconds
- 1h supervision window;
0,2 seconds
- 2h supervision window;
...
2,4 seconds
- 24h supervision window;
2,5 seconds
- 25h supervision window;
Note:
it is recommended to set the supervision time to a minimum of 2 hours if SECOLINK detectors are in use.
Page 5
Short programming manual - basic information
Intruder alarm system
24h Fire supervisory
,
24h Low Water Level
,
24h RF Jam
,
24h Gas Detected
,
24h Water leakage
,
24h High
Temperature, 24h Low Temperature -
this group of definitions is used for the 24h technical zones to report about
abnormalities in the environment.
Control
-
z
one is mostly used to arm/disarm the system (
Key-switch
zone). Momentary and maintained key-
switch arming are available. This definition can also be used to turn On / Off the PGM output. Violation of this
zone will not trigger an alarm, regardless of the system’s state.
Follower -
usually assigned to motion detectors and to interior doors protecting the area between entry door
and the keypad. This zone(s) causes an immediate intrusion alarm when violated unless an
Entry/Exit
zone was
violated first. Violation of this zone will not trigger an alarm when the system is armed in
Night
or
Stay
mode.
Follower Night Armed
- this zone is the same as the
Follower
zone, but violation of this zone will not trigger
an alarm when the system is armed in
Stay
mode.
Interior Night Armed -
this zone is the same as the
Interior
zone, but violation of this zone will not trigger an
alarm when the system is armed
in
Stay
mode.
Entry/Exit Forced
- same as
Entry/Exit
zone but unlike a regular entry/exit zone this zone can be violated
before the arming.
The loop speed menu enables you to set the different times for which a zone violation must exist before the zone
will trigger an alarm condition. Normally zone speed is within 0,1 - 2,5 seconds range. With
Vibration
zone loop
type selected, the zone speed must be within 0,01 - 0,25 seconds range (fast zone). This zone loop speed time
can be defined only for zones located on the control panel.
Z01
|
Zone Speed
}
0,4 seconds
Z01 Attributes
|
+Limit report
}
Z01 Attributes
|
-Limit alarms
}
Z01 Attributes
|
-Fire Verific
}
Z01 Attributes
|
-In Exit Rout
}
Z01 Attributes
|
-In Entry Rou
}
Z01 Attributes
|
-Arm on Exit
}
Z01 Attributes
|
-No alarm
}
Z01 Attributes
|
+Bypass Enabl
}
Z01
|
Entry Delay
}
30 seconds
Z01
|
Pre-alarm
}
No
Z01
|
WL loop ID
}
Type 201
Repeated violation of the same zone, often resulting in a false alarm and usually arising due to a malfunction, an
environmental problem, or incorrect installation of a detector or sensor. By default,
the
system is set to make a
zone shutdown when 3 or 7 (use MASCAD to change this number) violations of the zone are detected. This
parameter specifies number of violations of the same zone (triggered the siren, keypad buzzer, and etc.), during
a single armed period before the zone is automatically shutdown.
By default, the system is set to make a zone shutdown when 3 or 7 (use MASCAD to change this number)
violations of zone are detected. This parameter specifies number of violations of the same zone reported to
central monitoring station during a single armed period, before the zone is automatically shutdown.
Implemented on detection of smoke or fire for verification. Power to the smoke detector(s) in the affected zone is
cut off and restored. If a subsequent detection occurs in the same zone within the predefined time of the first
detection, the system emits a fire alarm. It’s recommended to use +PGM as fire detector power supply.
With this attribute being set - a zone with
Interior
definition can be violated during an exit delay.
With this attribute being set - a zone with
Interior
definition can be violated during an entry delay.
This attribute is only used for
Entry/Exit
or
Entry/Exit Forced
. With this attribute being set - the system will finish
an exit delay countdown and will arm the system immediately after the entrance door will close.
Used for
24h High temperature
or
24h Low temperature
. A zone with this attribute will not trigger an alarm, but
can start PGM action.
This attribute permits zone bypassing by authorized system users. If
No
is displayed as an option, then the zone
cannot be manually bypassed.
Used for
Entry/Exit
or
Entry/Exit Forced
zones. Entry delay time is programmable within 1 - 255 seconds range.
Used for perimeter protection. When special arming mode
Pre-alarm
is turned on and the pre-alarm zone is
violated, the
system will make an alarm without reporting to central monitoring station or to the
user.
Enter wireless detector loop (zone) ID
number
and press
the
[ENT]
key to start
enrolling
. There is a 30-second
time-out for enrolling.
Also u
se this field for deleting
the detector from the module. The table with available
wireless detector loop (zone) ID numbers can be find in the wireless detector manual.
System with
KM2
0B
keypads