Note:

 if wireless detectors are in use, this field also specifies how often the system checks for supervision 

signals,  identifying  each  of  the  system’s  wireless  detectors.  The  system  generates  a  local  trouble  signal 
identifying the zone of any wireless detectors from which a signal is not received during the specified interval. 
Control panel then sends the supervision report code to the CMS. 

      0,0 seconds

 - supervision is disabled;

      0,1 seconds

 - 1h supervision window;

      0,2 seconds

 - 2h supervision window;

      ...

      2,4 seconds

 - 24h supervision window;

      2,5 seconds

 - 25h supervision window;

Note:

 it is recommended to set the supervision time to a minimum of 2 hours if SECOLINK detectors are in use.

Page 5

Short  programming manual - basic information 

Intruder alarm system

     

24h Fire supervisory

,

 24h Low Water Level

24h RF Jam

,

 24h Gas Detected

,

 24h Water leakage

,

 24h High 

Temperature, 24h Low Temperature - 

this group of definitions is used for the 24h technical zones to report about 

abnormalities in the environment.

      Control

 - 

z

one is mostly used to arm/disarm the system (

Key-switch

 zone). Momentary and maintained key-

switch arming are available. This definition can also be used to turn On / Off the PGM output. Violation of this 
zone will not trigger an alarm, regardless of the system’s state.

      Follower  - 

usually assigned to motion detectors and to interior doors protecting the area between entry door 

and the keypad. This zone(s) causes an immediate intrusion alarm when violated unless an 

Entry/Exit

 zone was 

violated first. Violation of this zone will not trigger an alarm when the system is armed in 

Night

 or 

Stay

 mode.

      Follower Night Armed 

- this zone is the same as the 

Follower 

zone, but violation of this zone will not trigger 

an alarm when the system is armed in 

Stay

 mode.

      Interior Night Armed -  

this zone is the same as the 

Interior  

zone, but violation of this zone will not trigger an 

alarm when the system is armed

 in 

Stay

 mode.

      Entry/Exit Forced

 - same as 

Entry/Exit

 zone but unlike a regular entry/exit zone this zone can be violated 

before the arming. 

The loop speed menu enables you to set the different times for which a zone violation must exist before the zone 
will trigger an alarm condition. Normally zone speed is within 0,1 - 2,5 seconds range. With 

Vibration

 zone loop 

type selected, the zone speed must be within 0,01 - 0,25 seconds range (fast zone). This zone loop speed time 
can be defined only for zones located on the control panel.

Z01

|

Zone Speed   

}

 0,4   seconds

Z01 Attributes  

|

+Limit report   

}

Z01 Attributes  

|

-Limit alarms   

}

Z01 Attributes  

|

-Fire Verific   

}

Z01 Attributes  

|

-In Exit Rout   

}

Z01 Attributes  

|

-In Entry Rou   

}

Z01 Attributes  

|

-Arm on Exit    

}

Z01 Attributes  

|

-No alarm       

}

Z01 Attributes  

|

+Bypass Enabl   

}

Z01

|

Entry Delay  

}

 30    seconds   

Z01

|

Pre-alarm    

}

  No   

Z01

|

WL loop ID   

}

  Type        201  

Repeated violation of the same zone, often resulting in a false alarm and usually arising due to a malfunction, an 
environmental problem, or incorrect installation of a detector or sensor. By default, 

the

 system is set to make a 

 

zone shutdown when 3 or 7 (use MASCAD to change this number) violations of the zone are detected. This 
parameter specifies number of violations of the same zone (triggered the siren, keypad buzzer, and etc.), during 
a single armed period before the zone is automatically shutdown.

By default, the system is set to make a zone shutdown when 3 or 7 (use MASCAD to change this number) 
violations of zone are detected. This parameter specifies number of violations of the same zone reported to 
central monitoring station during a single armed period, before the zone is automatically shutdown. 

Implemented on detection of smoke or fire for verification. Power to the smoke detector(s) in the affected zone is 
cut off and restored. If a subsequent detection occurs in the same zone within the predefined time of the first 
detection, the system emits a fire alarm. It’s recommended to use +PGM as fire detector power supply.

With this attribute being set - a zone with 

Interior

 definition can be violated during an exit delay.

With this attribute being set - a zone with 

Interior

 definition can be violated during an entry delay.

This attribute is only used for 

Entry/Exit

 or 

Entry/Exit Forced

. With this attribute being set - the system will finish 

an exit delay countdown and will arm the system immediately after the entrance door will close.

Used for 

24h High temperature

 or 

24h Low temperature

.  A zone with this attribute will not trigger an alarm, but 

can start PGM action.

This attribute permits zone bypassing by authorized system users. If 

No 

is displayed as an option, then the zone 

cannot be manually bypassed.

Used for 

Entry/Exit 

or

 Entry/Exit Forced

 

 

zones. Entry delay time is programmable within 1 - 255  seconds range.

Used for perimeter protection. When special arming mode 

Pre-alarm

 is turned on and the pre-alarm zone is 

violated, the

 

system will make an alarm without reporting to central monitoring station or to the

 

user.

Enter wireless detector loop (zone) ID 

number 

and press

 the 

[ENT] 

key to start 

enrolling

. There is a 30-second 

time-out for enrolling.

 

Also u

se this field for deleting 

the detector from the module. The table with available 

wireless detector loop (zone) ID numbers can be find in the wireless detector manual. 

System with  

KM2

0B

 

keypads

Summary of Contents for KM20B

Page 1: ...send the default template or customized project to the control panel and all successfully registered system modules Press the ENT key Template is being sent to the system Registration of modules is i...

Page 2: ...ddress which is used by another module then the new module will overtake this address and the other module will stay unregistered Note a registered module will slowly flash its address on a green LED...

Page 3: ...counting when the module is installed indoors or outdoors If proximity reader is installed outdoors then the entry exit delay is excluded The preferred arming mode will appear as a first option With...

Page 4: ...s module EXT116S address P16 address 12 P32 address 12 and 13 The Loop type menu enables you to program the connection type used for each of the system s zones The actual physical loop type for each z...

Page 5: ...arms Z01 Attributes Fire Verific Z01 Attributes In Exit Rout Z01 Attributes In Entry Rou Z01 Attributes Arm on Exit Z01 Attributes No alarm Z01 Attributes Bypass Enabl Z01 Entry Delay 30 seconds Z01 P...

Page 6: ...on the selected technical zone SelectedAlarms output activates if a selected type of alarm occurs on the selected partition Chime output activates if the selected zone is violated when the system is...

Page 7: ...ll call again Program the Account number This account number will be used for all reporting events Use the key to enter additional hex symbols B C D E F Value programmed in this parameter determines h...

Page 8: ...et and the LAN module will automatically find that IPaddress on the internet The Time Settings menu contains parameters that enable the routing of periodic test event to CMS receivers Service Mode Rep...

Page 9: ...nu enables you to assign the partition s in which the user except for the 1st system user will operate Used to allow users to control the system during predefined time periods Note if the timer is not...

Page 10: ...modules The message First Start Press ENT will appear on keypad s LCD screen when this procedure will end If entered the control panel will start uploading the project to all registered system modules...

Page 11: ...Sessions PauseBTWsessio Dial Tone Test Method LineMonitoring LineLossDelay SERIAL Interface GPRS settings LAN settings APN User name Password Obtain IPauto Obtain DNS auto IPaddress Subnet mask Gatewa...

Reviews: