10
Detection area (Fig 3):
The detection range of the motion detector for ceiling mounting is approx. 6m and 360° (free area) at a mounting
height of 2.2-4m at the ceiling. The detection range of the motion detector for wall mounting is approx. 6m and
120° (on free area) with a mounting height of 1.8-2.5m on the wall. In closed rooms the detection distance can be
lower, according to room layout.
Connection of the protective conductor (PE):
When connecting a lamp with protective conductor contact, the
protective conductor must be bypassed from the supply line to the lamp
with the aid of an additional terminal in the in-wall socket.
Sensitivity when switching (with regard to the ambient brightness):
With this switch the switch-on sensitivity can be set to 10 (slide up) or 2.000 LUX
(slide down) depending on the ambient brightness. Note: When testing the device
in daylight, set the switch to the position shown.
Time setting (switching off delay):
The following times can be set:
5s, 30s, 1min, 3min, 5min, 8min
Note: The time is restarted if a movement is detected by the sensor before the end
of the set period.
Reach Setting:
With this switch, the detection range can be set to 3m (slide up) or 6m (slide down).
Function test:
Ensure that the motion detector is not obscured. Ensure that the coverage area is not restricted by items such as
through large furniture. To set the detection range and the daylight test, turn the knobs to the positions shown. The
motion detector is activated after a warm-up phase of approx. 30s. If no further movement takes place in the
sensing area of the sensor, the sensor switches off.