background image

Original Language Version

© Jack Sealey limited

SdH102   Issue 1  07/11/18

 

It is essential that electrical power is available before the task is commenced.

 

a) Become familiar with the equipment and its operation.

 

b) Isolate system electrically.

 

c) Before attempting the procedure, ensure that:

 

• mechanical handling equipment is available, if required, for handling refrigerant cylinders.

 

• all personal protective equipment is available and being used correctly.

 

• the recovery process is supervised at all times by a competent person.

 

• recovery equipment and cylinders conform to the appropriate standards.

 

d) Pump down refrigerant system, if possible.

 

e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.

 

f) make sure that cylinder is situated on the scales before recovery takes place.

 

g) Start the recovery machine and operate in accordance with instructions.

 

h) Do not overfill cylinders (no more than 80 % volume liquid charge).

 

i) do not exceed the maximum working pressure of the cylinder, even temporarily.

 

j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are    

 

   removed from site promptly and all isolation valves on the equipment are closed off.

 

k) Recovered refrigerant shall not be charged into another refrigerating system unless it has been cleaned and checked.

5.1.19.  labelling

5.1.19.1.  equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and    

  signed. For appliances containing flammable refrigerants, ensure that there are labels on the equipment stating the equipment    

  contains flammable refrigerant.

5.1.20.  recovery

5.1.20.1.  When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all  

 

  refrigerants are removed safely.

5.1.21.  When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. ensure that  

 

the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the  

 

 

recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be  

 

 

complete  with pressure-relief valve and associated shut-off valves in good working order. empty recovery cylinders  

 

 

 

are evacuated and, if possible, cooled before recovery occurs.

5.1.21.1.  The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be  

  suitable for the recovery of all appropriate refrigerants including, when applicable, flammable refrigerants. In addition, a set of  

 

  calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings  

  and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained  

  and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer  

  if in doubt.

5.1.21.2.  The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant waste transfer  

  note arranged. do not mix refrigerants in recovery units and especially not in cylinders.

5.1.21.3.  If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain  

  that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the   

  compressor to the suppliers. only electric heating to the compressor body shall be employed to accelerate this process. When oil is  

  drained from a system, it shall be carried out safely.

6.   mAiNteNANCe 

 

‰

  

WArNiNG! 

Switch the machine off and unplug from the mains before carrying out any maintenance or cleaning.

6.1.    

filter  CleANiNG

6.1.1.   

It is recommended that the air filter is cleaned every two weeks maximum.

6.1.2.   

To remove the filter, remove water tank (section 4.1.4.3.) and gently pull down exposed tab of filter.

6.1.3.   

The filter may only be washed with water. 

dO NOt

 use hot water. leave to dry naturally. 

dO NOt 

use solvent cleaners nor use heat to  

 

dry the filter.

6.1.4.   

once dry, replace the filter by snapping it back into place, making sure that the lower edge fits behind the casing locations and that all the  

 

lugs are sprung gently into place thus holding the filter up inside casing.

6.2.    

CleANiNG the CASiNG

6.2.1.   

The casing may be cleaned by rubbing over with a damp cloth. 

dO NOt 

use detergents, abrasive or solvent cleaners as these will    

 

damage the surface finish.

 

8

  

dO NOt

 allow the control panel to become wet. 

6.3.    

StOrAGe

6.3.1.    See section 4.1.2 for instruction on preparing the unit for any long term storage period.

Summary of Contents for SDH102

Page 1: ...alified electrician When a BS1363 A UK 3 pin plug is damaged cut the cable just above the plug and dispose of the plug safely Fit a new plug according to the following instructions UK only a Connect the GREEN YELLOW earth wire to the earth terminal E b Connect the BROWN live wire to the live terminal L c Connect the BLUE neutral wire to the neutral terminal N d After wiring check that there are no...

Page 2: ...ty is 5 greater than set value the unit will start If the room humidity is 5 less than the set value the unit will stop The Display fig 1 7 will display the current humidity level when running Options selected will be highlighted If Mode is set to Continuous the fan defaults to high speed and cannot be changed 4 1 2 INSIDE DRYING prior to long term storage 4 1 2 1 Turn machine on fig 1 5 Press Ins...

Page 3: ...sons authorized by an accredited agency certifying their competence to handle refrigerants in compliance with sector legislation should work on refrigerant circuit 9 9 All repairs must be carried out in accordance with the manufacturer s recommendations 9 9 Maintenance and repairs requiring the assistance of other qualified personnel must be carried out under the supervision of specialists in the ...

Page 4: ...anufacturer Other parts may result in the ignition of refrigerant in the atmosphere from a leak 5 1 14 Cabling 5 1 14 1 Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans 5 1 15 Detectio...

Page 5: ...s in good working order Empty recovery cylinders are evacuated and if possible cooled before recovery occurs 5 1 21 1 The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of all appropriate refrigerants including when applicable flammable refrigerants In addition a set of calibrated weighing...

Page 6: ...ith the EU Directive on Waste Electrical and Electronic Equipment WEEE When the product is no longer required it must be disposed of in an environmentally protective way Contact your local solid waste authority for recycling information Symptom Potential cause Possible remedy Unit does not operate Is power supply connected Insert the plug into an electrical outlet fully and securely check fuse in ...

Reviews: