background image

 

Carefully slide the water tank forward making sure no spillage occurs.

 

Before replacing water tank dry it off thoroughly and also remove any mildew deposits.

4.1.5.   

Continuous  drainage:

4.1.5.1.    Connect a water pipe (not supplied) to the drain on the rear of the unit. The water pipe requires an inner diameter of 9mm and should  

  not be longer than 1.5 metres. ensure the connection does not leak.

 

‰

  

WArNiNG!

 The water pipe must 

AlWAYS

 be lower along all of it’s length than the unit outlet drain height.

5.   r 290 refriGerANt WArNiNGS 

5.1.    

iNStAllAtiON, SerViCe ANd rePAir Of APPliANCeS CONtAiNiNG r 290

 

‰

  

WArNiNG!

 To avoid damage place the unit in an upright position at least 24 hours before installation. 

 

‰

  

WArNiNG!

 make sure the air outlet and air inlet are never blocked.

 

‰

  

WArNiNG!

 only operate on a level surface to make sure no water leaks out.

 

8

  

dO NOt

 exceed impedance greater than 0.236 ohm in supply the appliance is connected to. Failure to comply may lead the supply  

  authority to impose restrictions to connection. Please consult your energy supply authority if the use of equipment exceeds 0.236 ohm.

 

9

   Any person who is involved with working on or breaking into a refrigerant a refrigerant circuit should hold a current valid certificate from  

  an industry-accredited assessment authority, which authorises their competence to handle refrigerants safety in accordance with an  

  industry recognized assessment specification.

 

9

   Remember the environment when disposing of packaging around the appliance and when the appliance has reached the end of its life.

 

9

   The appliance shall be stored in a well-ventilated area where the size corresponds to the room area as specified for operation.   

  Operate the unit in a well ventilated area where the size corresponds to the room area as specified for operation.

 

9

   Store in an area where mechanical damage can not occur.

 

Use care when storing the appliance to prevent mechanical faults.

5.1.1.   

information concerning refrigerant pipes

5.1.1.1.    The installation of pipe-work shall be kept to a minimum.

5.1.1.2. 

   Pipe-work shall be protected from physical damage and, in the case of flammable refrigerants, shall not be installed in an  

 

  unventilated space.

5.1.1.3.    Compliance with national gas regulations shall be observed.

5.1.1.4.    mechanical connections shall be accessible for maintenance purposes.

5.1.1.5. 

   Appliances containing flammable refrigerants, the minimum floor area of the room shall be mentioned in the form of a table or  a single  

  figure without reference to a formula.

 

‰

  

WArNiNG!

 Servicing shall be performed only as recommended by the manufacturer.

 

‰

  

WArNiNG!

 ducts connected to an appliance shall not contain a potential ignition source.

 

9

   When the dehumidifier is turned on, the fan can work continuously under normal conditions to provide the minimum air volume of   

  100m³/h even when the compressor is closed due to the temperature controller.

 

8

  

dO NOt

 pierce or burn.

 

9

   Use only implements recommended by the manufacturer for defrosting or cleaning.

 

8

  

dO NOt

 perforate any of the components in the refrigerant circuit. Refrigerant gas may be odourless.

 

9

   only persons authorized by an accredited agency certifying their competence to handle refrigerants in compliance with sector  

 

  legislation should work on refrigerant circuit.

 

9

   All repairs must be carried out in accordance with the manufacturer’s recommendations.

 

9

   Maintenance and repairs requiring the assistance of other qualified personnel must be carried out under the supervision of specialists  

  in the use of inflammable refrigerants.

 

8

  

dO NOt

 perforate any of the components in the refrigerant circuit. Refrigerant gas may be odourless.

5.1.2.   

Checks to the area

5.1.2.1. 

   Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is  

  minimised. For repair to the refrigerating system, the following precaution shall be completed prior to conducting work on the system.

5.1.3.   

Work procedure

5.1.3.1. 

   Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while  

  the work is being performed.

5.1.4.  

 

General work area

5.1.4.1. 

   All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined  

  spaces shall be avoided.

5.1.5.   

Checking for presence of refrigerant

5.1.5.1.    The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of    

  potentially toxic or flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with all applicable  

  refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.

5.1.6.   

Presence of fire extinguisher

5.1.6.1. 

   If any hot work is to be conducted on the refrigerating equipment or any associated parts, appropriate fire extinguishing equipment  

  shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area.

5.1.7.   

No ignition sources

5.1.7.1.    no person carrying out work in relation to a refrigerating system which involves exposing any pipe work shall use any sources of   

  ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette  

 

  smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which refrigerant  

  can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to  

  make sure that there are no flammable hazards or ignition risks. “No Smoking” signs shall be displayed.

5.1.8.   

Ventilated area

5.1.8.1.    ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A  

  degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released  

  refrigerant and preferably expel it externally into the atmosphere.

5.1.9.   

Checks to the refrigerating equipment

5.1.9.1. 

   Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the   

  manufacturer’s maintenance and service guidelines shall be followed. If in doubt, consult the manufacturer’s technical department for  

 assistance.

Original Language Version

© Jack Sealey limited

SdH102   Issue 1  07/11/18

Summary of Contents for SDH102

Page 1: ...alified electrician When a BS1363 A UK 3 pin plug is damaged cut the cable just above the plug and dispose of the plug safely Fit a new plug according to the following instructions UK only a Connect the GREEN YELLOW earth wire to the earth terminal E b Connect the BROWN live wire to the live terminal L c Connect the BLUE neutral wire to the neutral terminal N d After wiring check that there are no...

Page 2: ...ty is 5 greater than set value the unit will start If the room humidity is 5 less than the set value the unit will stop The Display fig 1 7 will display the current humidity level when running Options selected will be highlighted If Mode is set to Continuous the fan defaults to high speed and cannot be changed 4 1 2 INSIDE DRYING prior to long term storage 4 1 2 1 Turn machine on fig 1 5 Press Ins...

Page 3: ...sons authorized by an accredited agency certifying their competence to handle refrigerants in compliance with sector legislation should work on refrigerant circuit 9 9 All repairs must be carried out in accordance with the manufacturer s recommendations 9 9 Maintenance and repairs requiring the assistance of other qualified personnel must be carried out under the supervision of specialists in the ...

Page 4: ...anufacturer Other parts may result in the ignition of refrigerant in the atmosphere from a leak 5 1 14 Cabling 5 1 14 1 Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans 5 1 15 Detectio...

Page 5: ...s in good working order Empty recovery cylinders are evacuated and if possible cooled before recovery occurs 5 1 21 1 The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of all appropriate refrigerants including when applicable flammable refrigerants In addition a set of calibrated weighing...

Page 6: ...ith the EU Directive on Waste Electrical and Electronic Equipment WEEE When the product is no longer required it must be disposed of in an environmentally protective way Contact your local solid waste authority for recycling information Symptom Potential cause Possible remedy Unit does not operate Is power supply connected Insert the plug into an electrical outlet fully and securely check fuse in ...

Reviews: